2015-12-15 17:50:25 | RE-ROOF SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC-5TH EDITION (2014). |
| |
| 1- ACCORDING TO SEC. 1609.4 OF FBC-BUILDING, 5TH |
| EDITION THIS BUILDING IS LOCATED IN EXPOSURE "D" NOT |
| "C". ENGINEER DOING THE RAS 117 CALCULATIONS TO REVISE |
| CALCULATIONS AS REQUIRED.. NOTE: NEED TO SELECT ANOTHER |
| FLAT ROOF ASSEMBLY THAT MEETS THE CALCULATED REVISED |
| DESIGN PRESSURES. |
| |
| RESPONSE: THE CALCULATIONS WERE REVISED. THERE WERE TWO |
| NEW ROOF ASSEMBLIES SELECTED FROM FLORIDA PRODUCT |
| APPROVAL FL2948-R10. ASSEMBLY # C-54 IS A NON-INSULATED |
| ASSEMBLY. AND, ASSEMBLY #R-23 IS A RECOVER INSULATED |
| ASSEMBLY. THE FOLLOWING IS REQUIRED. |
| A) ACCORDING TO NOTE #11 OF FLORIDA PRODUCT APPROVAL |
| FL2648-R10 SUBMITTED THE EXISTING ROOF SURFACE SHALL BE |
| FIELD TESTED FOR RECOVER ASSEMBLIES. SEE NOTE #11 FOR |
| FIELD TEST STANDARD OPTIONS AND PROVIDE 2 SIGNED AND |
| SEALED COPIES. |
| |
| B) PROVIDE SKETCH (2 COPIES) CLEARLY SHOWING AREAS TO |
| HAVE NON-INSULATED ROOF ASSEMBLY AND AREA TO HAVE |
| INSULATED ROOF ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- THE BUILDING HEIGHT OF THIS BUILDING IS 110'. |
| PROVIDE SIGNED AND SEALED DETAILS AND SPECIFICATIONS |
| FOR THE ATTACHMENT OF THE COPING CAPS AND DRIP EDGE |
| SHOWING COMPLIANCE WITH THE WIND LOADS OF SEC. 1609 OF |
| FBC-BUILDING, 5TH EDITION. |
| RESPONSE: THE DRAWINGS SUBMITTED WERE NOT SIGNED AND |
| SEALED BY THE ENGINEER. |
| |
| 3- SCOPE OF WORK SUBMITTED INCLUDES MECHANICAL UNITS |
| STANDS, MECHANICAL SHROUDS, CONSTRUCTION OF KNEE WALL, |
| REPLACE DOOR. THIS SCOPE OF WORK TO BE DONE UNDER |
| SEPARATE PERMITS. PROVIDE COMPLETE DETAILS/ |
| SPECIFICATIONS AND PRODUCT APPROVALS UNDER SEPARATE |
| PERMITS. NOTE: THIS SCOPE OF WORK CAN NOT BE DONE BY |
| THE ROOFING CONTRACTOR UNLESS THE ROOFING CONTRACTOR |
| POSSES A LICENSE TO PERFORM SUCH SCOPE OF WORK. SEC. |
| 489.113 FLORIDA STATUTES. |
| RESPONSE: THIS ITEM WAS NOT ADDRESSED. |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |