Plan Review Details - Permit 15120298
Plan Review Stops For Permit 15120298
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-01-11 Cont ID  
Sent By cthroop Date 2016-01-11 Time 15:12 Rev Time 0.00
Received By cthroop Date 2016-01-11 Time 15:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-01-11 Cont ID  
Sent By mvaldes Date 2016-01-11 Time 14:07 Rev Time 0.00
Received By mvaldes Date 2016-01-11 Time 14:07 Sent To  
Notes
2016-01-11 14:11:19FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 1- PLEASE SITE CURRENT CODE STANDARDS NEC 2011
 2- PROVISO FBC-ER 404.1.1 / 402.4.4
 RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT
 AS WELL AS IC RATED AND SEALED TO NOT COMPROMISE
 BUILDING THERMAL ENVELOPE. ( 2 CFM )
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-01-25 Cont ID  
Sent By gjohnson Date 2016-01-25 Time 12:26 Rev Time 0.00
Received By gjohnson Date 2016-01-25 Time 12:26 Sent To  
Notes
2016-01-25 12:27:15A SEPARATE PERMIT REQUIRED FOR GAS GAS PERMIT
 APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-01-21 Cont ID  
Sent By fmittner Date 2016-01-21 Time 11:33 Rev Time 0.00
Received By fmittner Date 2016-01-21 Time 11:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-25 Cont ID  
Sent By gjohnson Date 2016-01-25 Time 12:27 Rev Time 0.00
Received By gjohnson Date 2015-12-08 Time 10:16 Sent To  
Notes
2015-12-09 10:18:03R12

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-01-25 Cont ID  
Sent By hmoser Date 2016-01-25 Time 09:40 Rev Time 0.00
Received By hmoser Date 2016-01-25 Time 09:33 Sent To  
Notes
2016-01-25 09:40:41NO AIR CONDITIONING WORK AT THIS TIME.
 HAVE AIR CONDITIONING CONTRACTOR PROVIDE
 SEPARATE APPLICATION AND PLANS FOR PERMIT
 BE FOR THEY START WORK
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-01-26 Cont ID  
Sent By gjohnson Date 2016-01-26 Time 13:34 Rev Time 0.00
Received By gjohnson Date 2016-01-26 Time 13:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-12 Cont ID  
Sent By gjohnson Date 2015-12-12 Time 12:55 Rev Time 0.00
Received By gjohnson Date 2015-12-12 Time 12:55 Sent To  
Notes
2015-12-12 13:01:181ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING PROVISO
  
 PROVIDE A APROVED RISER DIAGRAM BEFORE 1ST ROUGH
 INSPECTION.
  
 1.PLUMBING FOR THE NEW LAUNDRY TRAY NOT SHOWN ON RISER
 DIAGRAM PLEASE PROVIDE COMPLETE RISER DIAGRAM. PER WPB
 AMEND. TO FBC SEC 107.2.1
 2.MASTER BATH LABEL ALL FIXTURES ON RISER DIAGRAM. PER
 WPB AMEND. TO FBC SEC 107.2.1
 3. A SEPARATE PERMIT REQUIRED FOR GAS GAS PERMIT
 APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-01-11 Cont ID  
Sent By cthroop Date 2016-01-11 Time 15:12 Rev Time 0.00
Received By cthroop Date 2016-01-11 Time 15:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-21 Cont ID  
Sent By fmittner Date 2016-01-21 Time 11:33 Rev Time 0.00
Received By fmittner Date 2016-01-21 Time 11:33 Sent To  
Notes
***NONE***