Plan Review Stops For Permit 15120198 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2015-12-17 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2015-12-17 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2015-12-17 |
Time |
16:01 |
Sent To |
|
|
Notes |
2015-12-07 16:15:24 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6700 | | [email protected] | | ALTERNATE CONTACT | | PHIL PETTY | | 561-805-6742 | | [email protected] | | | | | | | | | | PROVISO. | | | | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO | | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | FEET OF EACH SLEEPING ROOM. | | | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | | | FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES. | | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- | | AND 20-AMPERE RECEPTACLES SHALL BE LISTED | | TAMPER-RESISTANT RECEPTACLES. | | | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-12-07 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2015-12-17 |
Time |
16:37 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2015-12-17 |
Time |
16:47 |
Sent To |
|
|
Notes |
2015-12-17 16:49:07 | 12/17/15 SMALL APPROVED "M" | 2015-12-07 08:41:53 | ELEC -$5000 |
|
|
|