Plan Review Details - Permit 15120123
Plan Review Stops For Permit 15120123
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-12-14 Cont ID  
Sent By mvaldes Date 2015-12-14 Time 14:59 Rev Time 0.00
Received By mvaldes Date 2015-12-14 Time 14:59 Sent To  
Notes
2015-12-14 16:01:411ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
 TALK TO PROJECT MANAGER AND HE STATED POLARIS WILL BE
 USED TO MAKE ATS EQUIPMENT TAPS
 NOTE MAKE SURE TAPS DON'T EXCEED 75 % OF CUBIC INCHES.
  
 312.8 SWITCH AND OVERCURRENT DEVICE ENCLOSURES WITH
 SPLICES, TAPS, AND FEED-THROUGH CONDUCTORS. THE WIRING
 SPACE OF ENCLOSURES FOR SWITCHES OR OVERCURRENT DEVICES
 SHALL BE PERMITTED FOR CONDUCTORS FEEDING THROUGH,
 SPLICED,
 OR TAPPING OFF TO OTHER ENCLOSURES, SWITCHES, OR
 OVERCURRENT
 DEVICES WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE TOTAL OF ALL CONDUCTORS INSTALLED AT ANY CROSS
 SECTION
 OF THE WIRING SPACE DOES NOT EXCEED 40 PERCENT OF THE
 CROSS-SECTIONAL AREA OF THAT SPACE.
 (2) THE TOTAL AREA OF ALL CONDUCTORS, SPLICES, AND TAPS
 INSTALLED
 AT ANY CROSS SECTION OF THE WIRING SPACE DOES NOT
 EXCEED 75 PERCENT OF THE CROSS-SECTIONAL AREA OF THAT
 SPACE.
 (3) A WARNING LABEL IS APPLIED TO THE ENCLOSURE THAT
 IDENTIFIES
 THE CLOSEST DISCONNECTING MEANS FOR ANY FEEDTHROUGH
 CONDUCTORS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-15 Cont ID  
Sent By lmarchan Date 2015-12-15 Time 09:06 Rev Time 0.00
Received By lmarchan Date 2015-12-02 Time 11:15 Sent To  
Notes
2015-12-03 11:15:32ROUTED TO GENERATOR INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-09 Cont ID  
Sent By sgraham Date 2015-12-09 Time 12:32 Rev Time 0.00
Received By sgraham Date 2015-12-09 Time 12:32 Sent To E
Notes
***NONE***