Plan Review Details - Permit 15120113
Plan Review Stops For Permit 15120113
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-14 Cont ID  
Sent By ccole Date 2015-12-14 Time 07:49 Rev Time 0.00
Received By ccole Date 2015-12-11 Time 14:06 Sent To  
Notes
2015-12-11 14:06:56RESUB ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-14 Cont ID  
Sent By ccole Date 2015-12-14 Time 07:50 Rev Time 0.00
Received By ccole Date 2015-12-14 Time 07:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-02 Cont ID  
Sent By ccole Date 2015-12-02 Time 14:21 Rev Time 0.00
Received By ccole Date 2015-12-02 Time 14:21 Sent To  
Notes
2015-12-02 14:26:511ST REVIEW 2010 MECHANICAL
 REVISION #15120113
 PRIMARY #15030075
 12/2/15
  
 1) THE SUBMITTED PLAN TO INSTALL A 16 SEER 2.5- TON AC
 SYSTEM DOES NOT CORRELATE WITH THE ORIGINAL ENERGY
 CALCULATIONS WHICH INDICATE AN 18 SEER 5-TON SYSTEM TO
 BE INSTALLED. PLEASE PROVIDE THE FOLLOWING: A) REVISED
 ENERGY CALCULATIONS. B) AC COOLING AND HEATING
 CALCULATIONS. C) REVISED ELECTRICAL PLAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER