Plan Review Details - Permit 15120098
Plan Review Stops For Permit 15120098
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-12-08 Cont ID  
Sent By albarran Date 2015-12-08 Time 10:17 Rev Time 0.00
Received By albarran Date 2015-12-08 Time 09:47 Sent To I
Notes
2015-12-08 10:17:50IMPORTANT NOTICE: THE FOLLOWING SHALL BE COMPLETED FOR
 FINAL INSPECTION:
 1. NEC 408.4 COMPLETE CIRCUIT DIRECTORY SHALL BE
 APPLIED TO THE PANEL.
 2. NEC 250.94 THE INTER-SYSTEM BONDING TERMINAL SHALL
 BE INSTALLED.
 3. FBC-R314.3.1 REQUIRES THAT YOU ARE IN COMPLIANCE
 WITH THE SMOKE DETECTOR REQUIREMENTS. IF NOT ALREADY
 INSTALLED, SMOKE DETECTOR SHALL BE INSTALLED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-08 Cont ID  
Sent By albarran Date 2015-12-08 Time 10:19 Rev Time 0.00
Received By albarran Date 2015-12-02 Time 10:50 Sent To  
Notes
2015-12-08 10:20:5212/8/15 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL READY BIN "S". MA
2015-12-02 10:50:20ELEC -$5000