Plan Review Details - Permit 15120087
Plan Review Stops For Permit 15120087
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-23 Cont ID  
Sent By tklarge Date 2015-12-23 Time 03:16 Rev Time 0.00
Received By tklarge Date 2015-12-23 Time 03:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-23 Cont ID  
Sent By tklarge Date 2015-12-23 Time 03:16 Rev Time 0.00
Received By tklarge Date 2015-12-23 Time 03:16 Sent To  
Notes
2015-12-23 03:16:181) SUBMIT 2 COPIES OF ALL DOCUMENTS/SPECIFICATIONS FOR
 THE IRRIGATION SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 ONLY ONE COPY HAS BEEN SUBMITTED.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE BACKFLOW PREVENTION DEVICE. THE BACKFLOW
 PREVENTION DEVICE MUST BE:
 A) LEAD FREE
 B) MUST BE ON THE UNIVERSITY OF SOUTHERN CALIFORNIA
 (USC) LIST OF APPROVED DEVICES.
 C) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 3) SHOW THE PIPE SIZES ON THE PLAN.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  