Plan Review Details - Permit 15120083
Plan Review Stops For Permit 15120083
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-15 Cont ID  
Sent By tklarge Date 2016-03-15 Time 05:32 Rev Time 0.00
Received By tklarge Date 2016-03-14 Time 14:42 Sent To  
Notes
2016-03-14 14:42:48TLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-23 Cont ID  
Sent By tklarge Date 2015-12-23 Time 03:14 Rev Time 0.00
Received By tklarge Date 2015-12-22 Time 15:30 Sent To  
Notes
2015-12-22 15:31:02PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-15 Cont ID  
Sent By tklarge Date 2016-03-15 Time 05:32 Rev Time 0.00
Received By tklarge Date 2016-03-15 Time 05:06 Sent To  
Notes
2016-03-15 05:32:041)THE COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT BEEN
 ADDRESSED. COMPLY WITH ALL PREVIOUS COMMENTS.
 2) THE IRRIGATION LEGEND SHOWS A WILKINS #720-A
 BACKFLOW PREVENTER AND IT IS CALLED OUT AS AN RPZ. THIS
 DEVICE IS A PRESSURE VACUUM BREAKER, NOT AN RPZ. ALSO,
 YOU HAVE SUBMITTED COPIES OF THE END OF A BOX OR
 WHATEVER IT IS FOR A WATTS LF919QT BACKFLOW PREVENTER.
 THIS IS NOT A MANUFACTURER'S SPECIFICATION AS
 PREVIOUSLY REQUESTED. SUBMIT TWO COPIES OF COMPLETE
 MANUFACTURER'S SPECIFICATIONS FOR REVIEW.
 3) THE BACKFLOW DEVICE MUST BE INSTALLED BY A PROPERLY
 LICENSED PLUMBING CONTRACTOR. SUBMIT AN APPLICATION BY
 A PLUMBING CONTRACTOR FOR THE INSTALLATION OF THIS
 DEVICE. F.S. 489.103.
 4) INDICATE THE SIZE OF THE BACKFLOW PREVENTION DEVICE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-23 Cont ID  
Sent By tklarge Date 2015-12-23 Time 03:14 Rev Time 0.00
Received By tklarge Date 2015-12-23 Time 02:44 Sent To  
Notes
2015-12-23 03:06:511) SUBMIT 2 COPIES OF ALL DOCUMENTS/SPECIFICATIONS FOR
 THE IRRIGATION SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1.
 ONLY ONE COPY HAS BEEN SUBMITTED.
 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE BACKFLOW PREVENTION DEVICE. THE BACKFLOW
 PREVENTION DEVICE MUST BE:
 A) LEAD FREE
 B) MUST BE ON THE UNIVERSITY OF SOUTHERN CALIFORNIA
 (USC) LIST OF APPROVED DEVICES.
 C) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO
 CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE
 CITY?S REQUIREMENTS.
 3) SHOW THE PIPE SIZES ON THE PLAN.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  