|
 |
 |
 |
 |
 |
Plan Review Details - Permit 15120083
Plan Review Stops For Permit 15120083 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-03-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-15 |
Time |
05:32 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-14 |
Time |
14:42 |
Sent To |
|
|
Notes |
2016-03-14 14:42:48 | TLARGE'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-12-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-23 |
Time |
03:14 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-22 |
Time |
15:30 |
Sent To |
|
|
Notes |
2015-12-22 15:31:02 | PLUMB <5K |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2016-03-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-15 |
Time |
05:32 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-15 |
Time |
05:06 |
Sent To |
|
|
Notes |
2016-03-15 05:32:04 | 1)THE COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT BEEN | | ADDRESSED. COMPLY WITH ALL PREVIOUS COMMENTS. | | 2) THE IRRIGATION LEGEND SHOWS A WILKINS #720-A | | BACKFLOW PREVENTER AND IT IS CALLED OUT AS AN RPZ. THIS | | DEVICE IS A PRESSURE VACUUM BREAKER, NOT AN RPZ. ALSO, | | YOU HAVE SUBMITTED COPIES OF THE END OF A BOX OR | | WHATEVER IT IS FOR A WATTS LF919QT BACKFLOW PREVENTER. | | THIS IS NOT A MANUFACTURER'S SPECIFICATION AS | | PREVIOUSLY REQUESTED. SUBMIT TWO COPIES OF COMPLETE | | MANUFACTURER'S SPECIFICATIONS FOR REVIEW. | | 3) THE BACKFLOW DEVICE MUST BE INSTALLED BY A PROPERLY | | LICENSED PLUMBING CONTRACTOR. SUBMIT AN APPLICATION BY | | A PLUMBING CONTRACTOR FOR THE INSTALLATION OF THIS | | DEVICE. F.S. 489.103. | | 4) INDICATE THE SIZE OF THE BACKFLOW PREVENTION DEVICE. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-12-23 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-23 |
Time |
03:14 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-23 |
Time |
02:44 |
Sent To |
|
|
Notes |
2015-12-23 03:06:51 | 1) SUBMIT 2 COPIES OF ALL DOCUMENTS/SPECIFICATIONS FOR | | THE IRRIGATION SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. | | ONLY ONE COPY HAS BEEN SUBMITTED. | | 2) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS | | FOR THE BACKFLOW PREVENTION DEVICE. THE BACKFLOW | | PREVENTION DEVICE MUST BE: | | A) LEAD FREE | | B) MUST BE ON THE UNIVERSITY OF SOUTHERN CALIFORNIA | | (USC) LIST OF APPROVED DEVICES. | | C) CONTACT FIELD CUSTOMER SERVICE AT 561-822-2240 TO | | CONFIRM IF THE DEVICE YOU ARE PURCHASING MEETS THE | | CITY?S REQUIREMENTS. | | 3) SHOW THE PIPE SIZES ON THE PLAN. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |