Plan Review Details - Permit 15120060
Plan Review Stops For Permit 15120060
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-02 Cont ID  
Sent By jwitmer Date 2016-03-02 Time 05:59 Rev Time 0.00
Received By jwitmer Date 2016-03-02 Time 05:30 Sent To  
Notes
2016-03-02 05:58:35BUILDING PROVISO:
 DEFERRED SUBMITTAL:
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
 FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO
 HAVE HAD THE SOUND UNDERLAYMENT TESTED TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
 A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-21 Cont ID  
Sent By jwitmer Date 2016-01-21 Time 10:46 Rev Time 0.00
Received By jwitmer Date 2016-01-21 Time 07:31 Sent To  
Notes
2016-01-21 11:11:18PROVISO:
 FLOOR INSULATION TO BE SUBMITTED AS A DEFERRED
 SUBMITTAL, 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION. 107.3.4.2 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 TYPE III-TYPE V CONSTRUCTION:
 FBC-B-2014 720.2 CONCEALED INSTALLATION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By jwitmer Date 2015-12-09 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2015-12-09 Time 09:42 Sent To E
Notes
2015-12-09 11:29:02BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120060
 ADD: 701 NORTHPOINT # 400
 CONT: KAST CONSTRUCTION
 TEL: 561-689-2910
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. DEC. 09/2015
 ACTION: DENIED
  
 1) SHEET A0:
  
 1A) SHEET A0 UNDER THE HEADING THE HEADING OF OCUUPANT
 LOAD FOR KAST OFFICES HAS A OCCUPANT LOAD OF 42 WITH
 2427 SQ. FT. PLEASE PROVIDE A BREAK DOWN OF THE SQ. FT.
 IN THE TRAINING ROOM AND OCCUPANT LOAD OF THE TRAINING
 ROOM (CLASSROOM) WITH THE OCCUPANT LOAD TAKEN AT 20 SQ.
 FT PER 2014 FBC-B TABLE 1004.1.2 AND THE REMAINDER OF
 THE OFFICE OCCUPANT LOAD TAKEN AT 100 SQ. FT. GROSS. I
 BELIEVE THE OCCUPANT LOAD WILL INCREASE.
  
 1B) SHEET A0 UNDER NOTE 13 AND THE 3 UNDERLAYMENT
 SYSTEMS BELOW THERE WILL NEED TO BE A CONSIDERATION
 THAT THE UNDERLAYMENST MEET THE REQUIREMENTS FOUND IN
 2014 FBC-B FBC-B-2014 720.2 CONCEALED INSTALLATION.
 TYPE III- TYPE V CONSTRUCTION.
 INSULATING MATERIALS, WHERE CONCEALED AS INSTALLED IN
 BUILDINGS OF ANY TYPE OF CONSTRUCTION, SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450.
  
 BOAF INFORMAL INTERPRETATION
 DATE: WED APR 29 2015
 REPORT: 7481
 CODE: BUILDING CODE YEAR: 2010
 SECTION: 719.2
 QUESTION:
 IS IT THE INTENT OF 2010 FBC-B 719.2 TO INCLUDE FLOOR
 INSULATION IN BUILDING TYPES III, IV & V.
 COMMENT:
 THE 2007 FBC-B COMMENTARY 719.1 WITHIN THE LAST
 PARAGRAPH STATES THE ADDITION OF INSULATION HAS THE
 POTENIAL TO EITHER ADD TO
 OR REDUCE THE FIRE-RESISTANCE RATING OF AN ASSEMBLY.
 THE REDUCTION OF RATINGS IS MORE OF A PROBLEM WHEN THE
 INSULATION IS ADDES
 INTO A HORIZONTAL ASSEMBLY. NOTED FLOOR CEILING
 ASSEMBLIES LIST THE TYPE OF INSULATION WITHIN THE
 ASSEMBLY. THE QUESTION IS DOES
 THE CODE SECTION 719.2 REQUIRE FLAME SPREAD AND SMOKE
 DEVELOPMENT FOR BUILDING TYPES III, IV OR V?
 ANSWER:
 YES. PLEASE SEE THE ATTACHED COMMENTARY FOR
 INFORMATION.
 COMMENTARY:
 FLOORING INSULATION, WHETHER IT BE THERMAL OR SOUND
 INSULATION, PLACED IN A FLOOR (CONCEALED) WOULD BE
 REQUIRED TO MEET THE FLAME
 SPREAD REQUIREMENTS OF SECTION 719.2. THERE ARE SOME
 EXCEPTIONS AND SPECIAL CONDITIONS CALLED OUT, HOWEVER,
 IF IT IS A FIRE RATED
 ASSEMBLY, THE FIRE TESTING OF THE ASSEMBLY WOULD HAVE
 TO INCLUDE THE MATERIALS USED. IN ADDITION, THE
 MATERIALS WOULD HAVE TO
 MEET THE STC REQUIREMENTS AT SECTION 1207. THERE ARE
 MANY TYPE 3 & 5 BUILDINGS OUT THERE BEING BUILT. SOME
 MAY HAVE WOOD
 FLOOR SYSTEMS OTHERS CONCRETE, BUT THE REQUIREMENTS
 FOUND IN 719.2 ARE MORE RESTRICTIVE THAN FOR TYPE I
 TYPE II CONSTRUCTION.
  
 1C) SHEET A0 UNDER THE NOTE 13 THERE ARE 3 UNDERLAYMENT
 SYSTEMS AND OR ALTERNATIVES. 2014 FLORIDA BUILDING CODE
 W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. SUCH DRAWINGS
 AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 2) SHEET A3.1 THERE IS A EXISITNG DOOR IN A COORIDOR
 NEXT TO ROOM IT CLOSET K-104, THIS DOOR DOES NOT HAVE
 18 INCHES ON THE LATCH SIDE OF THE DOOR. 2014
 FBC-ACCESSIBILITY CODE 404.2.4 MANEUVERING CLEARANCES.
 THE CONTRACT VALUE OF $30,000 DOLLORS, 20 % OF THE
 CONTRACT VALUE CAN BE SPENT ON ACCESSIBLE UPGRADES TO
 MAKE THE BUILDING MORE ACCESSIBLE SEE 2014
 FBC-ACCESSIBILITY CODE 202.4 & 202.4.1.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-14 Cont ID  
Sent By mvaldes Date 2016-03-14 Time 13:16 Rev Time 0.00
Received By mvaldes Date 2016-03-14 Time 13:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-17 Cont ID  
Sent By mvaldes Date 2016-02-17 Time 16:02 Rev Time 0.00
Received By mvaldes Date 2016-02-17 Time 16:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-04 Cont ID  
Sent By mvaldes Date 2016-01-04 Time 19:32 Rev Time 0.00
Received By mvaldes Date 2016-01-04 Time 19:32 Sent To  
Notes
2016-01-04 20:04:481ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 PLEASE REFERENCE CURRENT CODE CYCLE NEC 2011 FBC 2014
 SUSPENDED CEILINGS. FRAMING MEMBERS OF SUSPENDED
 CEILING SYSTEMS USED TO SUPPORT LUMINAIRES SHALL BE
 SECURELY
 FASTENED TO EACH OTHER AND SHALL BE SECURELY ATTACHED
 TO THE
 BUILDING STRUCTURE AT APPROPRIATE INTERVALS. LUMINAIRES
 SHALL
 BE SECURELY FASTENED TO THE CEILING FRAMING MEMBER BY
 MECHANICAL
 MEANS SUCH AS BOLTS, SCREWS, OR RIVETS. NEC 410.36
 PLEASE SHOW SHORT-CIRCUIT RATING OF EQUIPMENT AND AIC
 RATING OF
 OCPD. NEC 110.9 , 110.10
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-03-03 Cont ID  
Sent By pleduc Date 2016-03-03 Time   Rev Time 0.00
Received By pleduc Date 2016-03-03 Time 11:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-15 Cont ID  
Sent By pleduc Date 2016-01-15 Time   Rev Time 0.00
Received By pleduc Date 2016-01-15 Time 15:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-12-04 Cont ID  
Sent By pleduc Date 2015-12-04 Time   Rev Time 0.00
Received By pleduc Date 2015-12-04 Time 10:10 Sent To  
Notes
2015-12-04 10:28:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET AO - INDICATES AND OCCUPANY LOAD OF SPACE # 1
 AS 42. SHEET A1.1 INDICATES AN OCCUPANY LOAD OF
 36+2+14= 52. PLEASE CORRECT.
  
 2. SHEET A 3.1 - WITHIN THE TRAINING ROOM (AN ASSEMBLY
 SPACE) IT INDICATES AN OCCUPANY LOAD OF 36, EQUALING
 THE CHAIR COUNT. NO DIMENSIONS OR OCCUPANY LOAD
 CLASSIFICATION CALCULATION ARE PROVIDED FOR THIS SPACE.
 PLEASE PROVIDE.
  
 3. SHEET 3.1 - DOOR # 5 MAYBE REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS BASED ON THE SUBMITTAL INFORMATION
 OF # 2 ABOVE. PER SECTION NFPA 101, DOOR SWING
 DIRECTION, 7.2.1.4.2, DOOR IS REQUIRED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL FOR AN OCCUPANT LOAD OF 50
 OR GREATER PERSONS.
  
 4. SHEET A3.1 - DOOR # 3 SWING INTO THE EGRESS
 CORRIDOR. PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-14 Cont ID  
Sent By mvaldes Date 2016-03-14 Time 13:17 Rev Time 0.00
Received By mvaldes Date 2016-02-26 Time 15:27 Sent To  
Notes
2016-02-26 15:27:52B24

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-26 Cont ID  
Sent By lmarchan Date 2016-02-26 Time 15:26 Rev Time 0.00
Received By lmarchan Date 2016-01-12 Time 09:36 Sent To  
Notes
2016-01-13 09:37:04B19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-05 Cont ID  
Sent By cpuell Date 2016-01-05 Time 08:13 Rev Time 0.00
Received By cpuell Date 2015-12-01 Time 10:14 Sent To  
Notes
2015-12-02 10:14:23B12

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-03-10 Cont ID  
Sent By hmoser Date 2016-03-10 Time 08:45 Rev Time 0.00
Received By hmoser Date 2016-03-08 Time 13:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-20 Cont ID  
Sent By ccole Date 2016-01-20 Time 11:13 Rev Time 0.00
Received By ccole Date 2016-01-20 Time 11:13 Sent To  
Notes
2016-01-20 11:35:201ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120060
 01/20/16
  
 1) M1.1: LABEL THE RETURN AIR GRILLS IN WORK SPACES #2
 & #4- REFER TO THE DEVICE SCHEDULE ON M0.1.
 2) M1.1: PROVIDE NOTE #8 AT VAV-2 & 3.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-07 Cont ID  
Sent By ccole Date 2015-12-07 Time 10:20 Rev Time 0.00
Received By ccole Date 2015-12-07 Time 10:20 Sent To  
Notes
2015-12-07 10:35:131ST REVIEW 2014 MECHANICAL
 PERMIT #15120060
 12/7/15
  
 1) SHEET M1.1: PLEASE PROVIDE COMPLETE AC DUCT LAYOUT
 PLANS. THE PLAN IS INDICATING DUCTS SUPPLYING AIR TO A
 PORTION OF TENANT SPACE #1 HAVE BEEN CAPPED, HOWEVER
 THE ARCHITECTURAL PLANS INDICATE THE AREAS OF THE
 OFFICE POOL, AND WORK SPACES #1- 4, & 7 ETC. WILL BE
 OCCUPIED, AND NOT UNDER A SECOND PHASE. PLEASE CLARIFY
 AND SEE SECTION 309.1 FBC-14 MECHANICAL: A
 SPACE-HEATING SYSTEM IS REQUIRED FOR ALL OCCUPIED
 SPACES.
 2) REFER TO SECTION 809.2 FBC-14 EXISITING BUILDING
 CODE AND SHOW COMPLIANCE: 809.2 ALTERED EXISTING
 SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2016-01-16 Cont ID  
Sent By tklarge Date 2016-01-16 Time 07:48 Rev Time 0.00
Received By tklarge Date 2016-01-16 Time 07:45 Sent To  
Notes
***NONE***