Plan Review Details - Permit 15111015
Plan Review Stops For Permit 15111015
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-12-10 Cont ID  
Sent By   Date 2015-12-10 Time 06:30 Rev Time 0.00
Received By jwitmer Date 2015-12-10 Time 05:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-12-17 Cont ID  
Sent By albarran Date 2015-12-16 Time 18:00 Rev Time 0.00
Received By albarran Date 2015-12-16 Time 15:41 Sent To  
Notes
2015-12-16 18:01:26THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. ELECTRICAL SPECIFICATIONS SECTION ON SHEET E0.1
 MISQUOTED FBC-E SECTIONS: FBC-EC405.7.3 VOLTAGE DROP.
 FEEDERS & CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE
 SIZED FOR A MAXIMUM OF 2% VOLTAGE DROP. BRANCH CIRCUITS
 SHALL BE SIZED FOR A MAXIMUM OF 3% VOLTAGE DROP.
 2. TRENCHING FOR FPL CONDUCTORS BETWEEN EXISTING POLE
 AND THE PROPOSED FPL TRANSFORMER, IF UNDER THE SCOPE OF
 THIS PERMIT, AS WELL AS ALL OTHER UNDERGROUND WIRING
 SHALL REMAIN OPEN FOR INSPECTION UNLESS PRIOR
 ARRANGEMENTS ARE MADE WITH ELECTRICAL INSPECTOR, OR RUN
 VIA DIRECT BORING. SHEET E2.1
 3. FBC 1006.1 MEANS OF EGRESS ILLUMINATION REQUIRED.
 THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE,
 SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE
 SERVED BY THE MEANS OF EGRESS ARE OCCUPIED. SHEET E2.1
 4. THE SERVICE RACK SHALL BE GUARDED AGAINST PHYSICAL
 DAMAGE AS INDICATED IN NEC 110.27(B). SHEET E2.1
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2015-12-23 Cont ID  
Sent By dharvey Date 2015-12-23 Time 10:32 Rev Time 0.00
Received By dharvey Date 2015-12-23 Time 10:32 Sent To  
Notes
2015-12-23 13:26:02SPOKE WITH ROBERT BROWN, BUILDING OFFICIAL, AND KELLY
 CRANFORD, ENGINEERING PLAN REVIEWER, AND BASED ON THE
 CONVERSATIONS AND NOTES, A "NOT REQUIRED" RESULT IS
 ADDED TO THE ENGINEERING STOP AT THIS TIME. THIS WILL
 BE CONSIDERED PHASE 1 OF THE PROCESS AND INCLUDE ONLY
 THE SUPERINTENDENTS TRAILER AND INSTALLATION OF SAME.
 NO ELECTRIC OR WATER IS BEING CONSIDERED AT THIS TIME.
 SEPARATE PERMITS FOR ELECTRIC AND WATER, WITH COMPLIANT
 DRAWINGS ARE REQUIRED FOR THOSE PORTIONS OF THE WORK
 AND WILL BE SUBMITTED IN THE ANTICIPATED NEAR FUTURE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-12-17 Cont ID  
Sent By cranford Date 2015-12-17 Time 13:34 Rev Time 0.00
Received By cranford Date 2015-12-17 Time 13:16 Sent To  
Notes
2015-12-17 13:34:17ONCE THE PROPOSED POTABLE WATER SERVICE LINE IS NO
 LONGER UTILIZED, THE LINE IS TO BE REMOVED BACK TO THE
 MAIN. (SECTION 2.23 OF THE CITY RIGHT OF WAY
 CONSTRUCTION STANDARDS MANUAL)
  
 PLEASE UPDATE THE DETAIL SHEETS TO UTILIZE THE MOST
 RECENT VERSION OF THE CITY OF WEST PALM BEACH DETAILS.
 DETAILS MAY BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ .
 PAVEMENT RESTORATION WITHIN THE HAVERHILL RIGHT-OF-WAY
 MUST COMPLY WITH PALM BEACH COUNTY STANDARDS.
  
 PLEASE SUBMIT A LEGIBLE COPY OF THE SITE PLAN, SHEET
 SP-1.
  
 AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL BE
 REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 KELLY CRANFORD, P.E.
 CAPITAL IMPROVEMENT PLAN MANAGER
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-12-02 Cont ID  
Sent By wjolin Date 2015-12-02 Time 15:35 Rev Time 0.00
Received By wjolin Date 2015-12-02 Time 13:58 Sent To  
Notes
2015-12-02 15:35:185444 NORTH HAVERHILL ROAD - CONSTRUCTION TRAILERS
 PERMIT #15111015
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 WEST TRAILER EXITS (X3) APPEAR TO DISCHARGE INTO THE
 GRASS. EXIT DISCHARGES SHALL BE ILLUMINATED AND SHALL
 TERMINATE AT A PUBLIC WAY SUCH AS A SIDEWALK, STREET,
 PARKING LOT, ETC.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NOTE: SEPARATE PLANS AND PERMITS NEEDED FOR PRIVATE
 UNDERGROUND FIRE LINE/FIRE HYDRANT AND FIRE SPRINKLER
 SYSTEM.
  
 NOTE: REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE
 THE OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF
 COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4). FBC
 SECTION 105.4.1 PERMIT INTENT: A PERMIT ISSUED SHALL BE
 CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND
 NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET ASIDE
 ANY OF THE PROVISIONS OF THE TECHNICAL CODES, NOR SHALL
 ISSUANCE OF A PERMIT PREVENT THE BUILDING OFFICIAL FROM
 THEREAFTER REQUIRING A CORRECTION OF ERRORS IN PLANS,
 CONSTRUCTION OR VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-17 Cont ID  
Sent By lmarchan Date 2015-12-17 Time 13:37 Rev Time 0.00
Received By lmarchan Date 2015-12-01 Time 14:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-12-08 Cont ID  
Sent By ccole Date 2015-12-08 Time 10:06 Rev Time 0.00
Received By ccole Date 2015-12-08 Time 10:06 Sent To  
Notes
2015-12-08 10:16:56PROVISOS
 12/8/15
  
 1) COMPLETE THE MANDATORY REQUIREMENTS CHECKLIST (SEE
 PAGE 7) ON EACH ENERGY COMPLIANCE FORM 506-2014 FOR THE
 MODULAR BUILDINGS. THE ENERGY FORMS MUST BE ON SITE AT
 TIME OF INSPECTION.
 2) MANUFACTURER'S SPECIFICATIONS FOR THE AC UNITS SHALL
 BE ON-SITE AT TIME OF INSPECTION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-12-06 Cont ID  
Sent By gjohnson Date 2015-12-06 Time 10:39 Rev Time 0.00
Received By gjohnson Date 2015-12-06 Time 10:39 Sent To  
Notes
2015-12-06 10:45:301ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING PROVISO
  
  
  
 PERMITS REQUIRED FROM HEALTH DEPTMENT FOR HOLDING TANKS
 BEFORE FINAL INSPECTION

Review Stop Z ZONING
Rev No 1 Status P Date 2015-12-07 Cont ID  
Sent By dkittred Date 2015-12-07 Time 14:35 Rev Time 0.00
Received By dkittred Date 2015-12-07 Time 14:31 Sent To  
Notes
2015-12-07 14:35:45PLANNING AND ZONING COMMENTS:
  
 12/7/15
  
 1. 'TEMPORARY OFFICES AND FACILITIES FOR CONSTRUCTIONS,
 STORAGE AND SECURITY' - ALL SUCH STRUCTURES, INCLUDING
 TRAILERS, SHALL BE REMOVED WITHIN SEVEN DAYS OF THE
 FINAL CONSTRUCTION INSPECTION BY THE CITY AND PRIOR TO
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY IN
 ACCORDANCE WITH ZLDR SEC. 94-273(D)(74).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  