Plan Review Details - Permit 15110808
Plan Review Stops For Permit 15110808
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-05-12 Cont ID  
Sent By jwitmer Date 2016-05-12 Time 11:09 Rev Time 0.00
Received By jwitmer Date 2016-05-12 Time 07:45 Sent To  
Notes
2016-05-12 10:42:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110808
 ADD: 6870 OKEECHOBEE BLVD
 CONT: NORTH AMERICAN AUTO SERVICES
 TEL: 772-418-1384
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: FRI. MARCH 05/ 2016
 ACTION: BUILDING PROVISO
  
 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE OR EXHAUST FANS NO ROOFING APPROVALS!!!!!!!!!
 (G) PRE-ENGINEERED A/C STANDS
  
 APPROVALS SUBMITTED:
 NOA 15-0122.02 TRULITE 3100 REGISTER STOREFRONT WINDOW
 WALL SYSTEM L.M.I.
 NOA 15-0622.12 GENERAL IMPACT GLASS & WINDOW 21000 HIGH
 IMPACT FIXED L.M.I.
 NOA 14-0225.02 TRULITE 351 OUTSWING ENT. DOOR L.M.I.
 NOA 15-0304.01 DAB DOOR HURRICANE MASTER GARAGE DOOR
 L.M.I.
 NOA 12-0214.12 PAREX USA, EFIS WALL SYSTEM
 NOA 15-1014.05 ACME PDU & PNU ALUMINUM ROOF TOP EXHAUST
 FANS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-04 Cont ID  
Sent By jwitmer Date 2016-03-04 Time 06:57 Rev Time 0.00
Received By jwitmer Date 2016-03-04 Time 05:25 Sent To  
Notes
2016-03-04 06:45:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110808
 ADD: 6870 OKEECHOBEE BLVD
 CONT: NORTH AMERICAN AUTO SERVICES
 TEL: 772-418-1384
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: FRI. MARCH 05/ 2016
 ACTION: DENIED
  
 1) COMPLIED. SOILS REPORT.
  
 2) SEMI COMPLIED. RESIDENT INSPECTOR.
  
 2A) COMPLIED. RESIDENT INSPECTOR FORMS MUST BE SIGNED
 BY ALL PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
  
 2B) COMPLIED. FOR THE RESIDENT INSPECTOR HAS PROVIDED A
 RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT.
  
 2C) 2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
 RESPONSE INDICATES THAT IT WAS SUBMITTED WITH THE
 RESIDENT INSPECTOR PACKAGE, NOT FOUND IN ANY OF THE (3)
 SETS SUBMITTED.
  
 2D)COMPLIED. NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS
 (PLANS & PRODUCT APPROVALS) ARE REQUIRED
 2E) NOTICE, NO ACTION NEED TO BE TAKEN AT THIS TIME.
 PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE OR EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
 APPROVALS SUBMITTED:
 NOA 15-0122.02 TRULITE 3100 REGISTER STOREFRONT WINDOW
 WALL SYSTEM L.M.I.
 NOA 15-0622.12 GENERAL IMPACT GLASS & WINDOW 21000 HIGH
 IMPACT FIXED L.M.I.
 NOA 14-0225.02 TRULITE 351 OUTSWING ENT. DOOR L.M.I.
 NOA 15-0304.01 DAB DOOR HURRICANE MASTER GARAGE DOOR
 L.M.I.
 NOA 12-0214.12 PAREX USA, EFIS WALL SYSTEM
  
 PRODUCT APPROVALS SUBMITTED WILL NOT BE REVIEWED UNTIL
 APPROVED BY THE DESIGNER OF RECORD.
  
 3C) 2ND REQUEST. (3) SETS OF APPROVALS WERE SUBMITTED
 BUT THE DESIGNER OF RECORD HAS NOT APLIED THEIR SHOP
 DRAWING STAMP OF APPROVAL ON THE SUBMITED APPROVALS
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. 107.3.4.1
 THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4-5) COMPLIED.
  
 6) 2ND REQUEST. SHEET M1.1 SHOWS NEW EXHAUST ROOF TOP
 FANS.
 6A) THE PREVIOUSLY REQUESTED WIND LOAD ENGINEERING FOR
 HE ROOFTOP EXHAUST FANS HAS NOT BEEN PROVIDED.
 6B) PRODUCT APPROVALS WITH THE ENGINEERS SHOP DRAWING
 STAMP OF APPROVAL WERE NOT SUBMITTED.
 6C) THE STRUCTURAL ENGINEER OF RECORD IS TO REVIEW ALL
 ROOF TOP CONNECTION DETAILS OF THE CURB AND THE EXHAUST
 FAN TO THE CURB AND AFIX THEIR SHOP DRAWING STAMP OF
 APPROVAL BEFORE SUBMISSION TO THE BUILDING DEPARTMENT.
  
 PLEASE SHOW COMPLIANCE WITH: 2014 FBC-B 406.6.2
 VENTILATION. A MECHANICAL VENTILATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. SEE MECHANICAL COMMENTS.
  
 7) BUILDING PROVSIO: SHEET THE COVERSHEET INDICATES
 THERE ARE COMPONENTS OF THIS PROJECT TO BE CONSIDERED
 NEW WORK (ADDITION) BUT THERE ARE NO FIRE SPRINKLER
 PLANS WITHIN THIS SUBMITTAL. 107.3.5.1.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS. (5) SCHEMATIC
 FIRE SPRINKLERS.
  
 8) COMPLIED.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-17 Cont ID  
Sent By jwitmer Date 2015-12-17 Time 10:14 Rev Time 0.00
Received By jwitmer Date 2015-12-16 Time 15:29 Sent To E
Notes
2015-12-17 10:14:54BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110808
 ADD: 6870 OKEECHOBEE BLVD
 CONT: NORTH AMERICAN AUTO SERVICES
 TEL: 772-418-1384
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: THURS. DEC.17/2015
 ACTION: DENIED
  
 1) SHEET S-1 MENTIONS SLAB ON GRADE COMPACTION, BUT THE
 PLANS DO NOT PROVIDE WHAT THE MINIMUM SAFE BEARING
 VALUE WOULD BE FOR THE ADDITION, NEITHER WAS A SOILS
 REPORT SUBMITTED REVIEWED BY THE ENGINEER OF RECORD.
 2014 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 2) THE STRUCTURAL SHEETS INDICATE THE USE OF STRUCTURAL
 STEEL CONSTRUCTION. THIS BUILDING QUALIFIES FOR A
 RESIDENT INSPECTOR BECAUSE OF EITHER BOLTED STEEL
 CONNECTIONS OR WELDED CONNECTIONS. RESIDENT INSPECTORS
 ARE HIRED THROUGH THE OWNER AND PAID THROUGH THE OWNER.
 UNDER A RESIDENT INSPECTOR THE INSPECTIONS CAN BE
 LIMITED TO THE STRUCTURAL STEEL CONNECTIONS AND WELDED
 CONNECTIONS. FOR MORE INFORMATION PLEASE CALL KEN
 CONRAD AT 561-805-6666. THE CITY WILL SUBMIT FORMS TO
 THE OWNERS REPRESENTATIVE: [email protected]
  
 2A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
  
 2B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'.
 2C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 2D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS (PLANS &
 PRODUCT APPROVALS) ARE REQUIRED
 2E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
 3) THE CONTRACTOR AND OR DESIGNER OF RECORD HAS NOT
 SUPPLIED THE PRODUCT APPROVALS FOR THE REMODEL AND
 ADDITION. THE PRODUCT APPROVALS CAN BE SUBMITTED AT THE
 NEXT REVIEW OR ON WRITTEN REQUEST BE CONSIDERED AS A
 DEFERRED SUBMITTAL.
 3A) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON
 THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE BUILDING
 OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW
 THEM AND FORWARD THEM TO THE
 BUILDING OFFICIAL WITH A NOTATION INDICATING THAT THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 3B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP CURBS,
 INTAKE OR EXHAUST FANS
 (G) PRE-ENGINEERED A/C STANDS
  
  
 3C) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4) SHEET S-1 THE WIND DESIGN CRITERIA HAVE BEEN
 PROVIDED BUT THE PRESSURES HAVE NOT BEEN PROVIDED FOR
 ZONES 1-5, NOR THE MEAN ROOF HEIGHT FOR THE BUILDING.
 PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B 1603.1.4(5)
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 SEE: TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 5) SHEET A1 SHOWS IN THE ADDITION AREA VEHICLE DELIVERY
 AREA AN ENCLOSED GARAGE. THE PLANS INDICATE A DETAIL 2/
 A12.0. THIS DETAIL IS FOR AN OVERHEAD IMPACT GLASS DOOR
 SYSTEM . PLEASE PROVIDE COMPLIANCE WITH SECTION : 2014
 FBC-B 2405.2 ALLOWABLE GLAZING MATERIALS AND
 LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS.
  
 5. 1. FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING
 MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE
 LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM)
 POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED
 GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE
 REQUIREMENTS OF SECTION 2607, HEAT-STRENGTHENED GLASS
 OR FULLY TEMPERED GLASS.
  
 5.2. FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT OR
 LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
  
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED
 WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3.
  
 6) PLEASE SHOW COMPLIANCE WITH: 2014 FBC-B 406.6.2
 VENTILATION. A MECHANICAL VENTILATION SYSTEM SHALL BE
 PROVIDED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. SEE MECHANICAL COMMENTS.
  
 7) SHEET THE COVERSHEET INDICATES THERE ARE COMPONENTS
 OF THIS PROJECT TO BE CONSIDERED NEW WORK (ADDITION)
 BUT THERE ARE NO FIRE SPRINKLER PLANS WITHIN THIS
 SUBMITTAL. 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS. (5) SCHEMATIC FIRE SPRINKLERS.
  
 8) SHEET A10.0SHOWS 3 AREAS OF CONCERN FOR
 ACCESSIBILITY:
 8A) THE CAF? HAS 2 AREAS IN QUESTION; (1) 226.1
 GENERAL. WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902. IN ADDITION, WHERE WORK
 SURFACES ARE PROVIDED FOR USE BY OTHER THAN EMPLOYEES,
 AT LEAST 5 PERCENT SHALL COMPLY WITH 902.
 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND WORK
 SURFACES SHALL BE 28 INCHES (710 MM) MINIMUM AND 34
 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 (2) THE HEIGHT OF COFFEE BAR. 904.5.1 SELF-SERVICE
 SHELVES AND DISPENSING DEVICES. SELF-SERVICE SHELVES
 AND DISPENSING DEVICES FOR TABLEWARE, DISHWARE,
 CONDIMENTS, FOOD AND BEVERAGES SHALL COMPLY WITH 308.
  
 8B) PARTS RETAIL COUNTER / 116. 904.3.2 COUNTER. THE
 COUNTER SURFACE HEIGHT SHALL BE 38 INCHES (965 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. THE TOP OF
 THE COUNTER EDGE PROTECTION SHALL BE 2 INCHES (51 MM)
 MAXIMUM ABOVE THE TOP OF THE COUNTER SURFACE ON THE
 AISLE SIDE OF THE CHECK-OUT COUNTER.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 8C) SALES MANAGERS COUNTER 104. . THE COUNTER SURFACE
 HEIGHT SHALL BE 38 INCHES (965 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND. THE TOP OF THE COUNTER EDGE
 PROTECTION SHALL BE 2 INCHES (51 MM) MAXIMUM ABOVE THE
 TOP OF THE COUNTER SURFACE ON THE AISLE SIDE OF THE
 CHECK-OUT COUNTER.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-05-16 Cont ID  
Sent By mvaldes Date 2016-05-16 Time 17:36 Rev Time 0.00
Received By mvaldes Date 2016-05-16 Time 17:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-24 Cont ID  
Sent By mvaldes Date 2016-02-24 Time 19:06 Rev Time 0.00
Received By mvaldes Date 2016-02-24 Time 19:06 Sent To  
Notes
2016-02-24 19:06:52ROUTED BACK TO BIN C 36
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-04 Cont ID  
Sent By mvaldes Date 2016-02-04 Time 10:13 Rev Time 0.00
Received By mvaldes Date 2016-02-04 Time 10:13 Sent To  
Notes
2016-02-04 10:35:37JOB PERMIT NUMBER: 15110808
 JOB ADDRESS: 6870 OKEECHOBEE RD
 WEST PALM BEACH
 DATE: FEB 4 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1 EXTERIOR SIGNS ON A SEPARATE PERMIT
 2 FIRE ALARMS ON A SEPARATE PERMIT
 3 PLEASE ADD TO NOTES MANDATORY LIGHTING CONTROLS PER
 SECTION FBC- E C405
 4 FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS. A
 BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 5 NEW REQUIREMENT AVAILABLE FAULT CURRENT FIELD
 LABELING SHALL INCLUDE DATE OF CALCULATION AND WILL BE
 DURABLE TO WITHSTAND ENVIRONMENT. NEC 110.24 A & B.
 6 KEEP IN MIND WERE SERVICE BAY/GARAGES OUTLETS ARE
 INSTALLED GFCI PROTECTION IS REQUIRED NEC 210.8 B 8
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700 EXT 6713
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-04-28 Cont ID  
Sent By scaldero Date 2016-04-28 Time 17:24 Rev Time 0.00
Received By scaldero Date 2016-04-26 Time 17:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-03-07 Cont ID  
Sent By scaldero Date 2016-03-07 Time 12:18 Rev Time 0.00
Received By scaldero Date 2016-03-07 Time 12:12 Sent To  
Notes
2016-03-07 12:19:58PERMIT # 15110808
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT.
  
 DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY THE
 FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE
 BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-30 Cont ID  
Sent By scaldero Date 2015-11-30 Time 16:02 Rev Time 0.00
Received By scaldero Date 2015-11-30 Time 15:49 Sent To  
Notes
2015-11-30 16:02:35PERMIT #15110808
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 2) PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 3) NOTES INDICATE THET BUILDING IS FULL SPRINKLERED,
 HOWEVER THERE ARE NO DRAWINGS FOR WORK BEING DONE TO
 SPRINKLER SYSTEM. ENGINEERED FIRE ALARM AND FIRE
 SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A
 GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS
 BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP
 DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION
 DOCUMENTS) FOR A SUB-PERMIT. SEPARATE PLANS AND PERMITS
 ARE REQUIRED FOR THE INSTALLATION OR MODIFICATION OF
 THE FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 4) SEE MECHANICAL PLAN REVIEWER COMMENTS. IF SMOKE
 DETECTORS ARE INSTALLED OR WILL BE INSTALLED, PER LOCAL
 AHJ POLICY, DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM CONDITION.
  
  
 SUE ELLEN CALDERON
 ASST. FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-05-17 Cont ID  
Sent By ccole Date 2016-05-17 Time 14:44 Rev Time 0.00
Received By ccole Date 2016-05-16 Time 15:22 Sent To  
Notes
2016-05-16 15:22:45RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-12 Cont ID  
Sent By jwitmer Date 2016-05-12 Time 11:09 Rev Time 0.00
Received By jwitmer Date 2016-04-12 Time 11:28 Sent To  
Notes
2016-04-13 11:29:10C36

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-08 Cont ID  
Sent By shill Date 2016-03-08 Time 09:33 Rev Time 0.00
Received By shill Date 2016-02-16 Time 10:05 Sent To  
Notes
2016-02-17 10:05:54C36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-04 Cont ID  
Sent By cpuell Date 2016-02-04 Time 11:05 Rev Time 0.00
Received By cpuell Date 2015-11-18 Time 13:09 Sent To  
Notes
2015-11-19 13:10:46C37

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2016-05-12 Cont ID  
Sent By jwitmer Date 2016-05-12 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2016-05-12 Time 07:45 Sent To  
Notes
2016-05-12 08:32:04IMPACT FEES;
 RECEIPT # MU 2016-007912-0000
 FEES; $13,323.38

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-03-04 Cont ID  
Sent By jwitmer Date 2016-03-04 Time 06:57 Rev Time 0.00
Received By jwitmer Date 2016-03-04 Time 06:57 Sent To  
Notes
2016-03-04 06:57:47IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-16 Cont ID  
Sent By jwitmer Date 2015-12-16 Time 15:29 Rev Time 0.00
Received By jwitmer Date 2015-12-16 Time 15:29 Sent To  
Notes
2015-12-16 15:29:29BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-05-17 Cont ID  
Sent By ccole Date 2016-05-17 Time 14:44 Rev Time 0.00
Received By ccole Date 2016-05-17 Time 14:44 Sent To  
Notes
2016-05-17 14:47:29MECHANICAL PROVISO
 5/17/16
  
 1) THE PLANS HAVE BEEN "APPROVED WITH EXCEPTION".
 A REVISON IS REQUIRED TO ELIMINATE RE-CIRCULATION OF
 THE AIR FROM THE VEHICLE DELIVERY GARAGE TO THE
 ADJOINING SHOWROOM AND OFFICES- TABLE 403.3 FOOTNOTE B
 FBC-14 MECHANICAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-04-15 Cont ID  
Sent By ccole Date 2016-04-15 Time 08:32 Rev Time 0.00
Received By ccole Date 2016-04-15 Time 08:32 Sent To  
Notes
2016-04-15 08:53:333RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110808
 4/15/16
  
 1) THE AIR SUPPLIED TO THE NEW VEHICLE DELIVERY GARAGE
 FROM RTU'S 3 & 6 CANNOT BE RETURNED TO THE UNITS AND
 RECIRCULATED- SEE TABLE 403.3 (STORAGE OCCUPANCY-
 ENCLOSED PARKING GARAGES) AND FOOTNOTES B AND D.
 2) THE MOTORIZED DAMPERS (MD-1 & MD-2) FOR THE RETURN
 DUCTS FROM THE VEHICLE DELIVERY GARAGE ARE MISLABELED
 O/A DAMPERS.
 3) THE SUBMITTED NOA FOR THE ACME ROOF-MOUNTED EXHAUST
 FAN DOES NOT MATCH THE GREENHECK FAN THAT IS SPECIFIED
 IN THE SCHEDULE ON SHEET M0.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-22 Cont ID  
Sent By ccole Date 2016-02-22 Time 14:19 Rev Time 0.00
Received By ccole Date 2016-02-22 Time 14:19 Sent To  
Notes
2016-02-22 15:01:132ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110808
 2/22/16
  
 1) THE SUBMITTALS FOR THE CO AND NO2 DETECTORS DO NOT
 INDICATE A UL LISTING NUMBER FOR THE ELECTRICAL
 COMPONENTS OF THE DEVICES, ONLY FOR THE PLASTIC
 ENCLOSURE. PLEASE PROVIDE UL LISTED DEVICES WITH MAKE
 AND MODEL NUMBERS AND AND THE SENSOR RANGES OF EACH
 DEVICE. PLEASE NOTE THAT THE FORMER 2010 FBC-10
 MECHANICAL REQUIRED THE CO DETECTORS TO ALARM UPON
 DETECTION OF CO AT 25 PPM.
 2) THE PREVIOUSLY REQUESTED WIND LOAD ENGINEERING FOR
 THE ROOF TOP EXHAUST FANS HAS NOT BEEN PROVIDED: A)
 NOA'S WITH APPROVAL SIGNATURES FROM THE DESIGN
 PROFESSIONAL WERE NOT SUBMITTED. B) THE ENGINEERING IS
 NOT SHOWN ON THE STRUCTURAL DRAWINGS AS INDICATED IN
 THE RESPONSE NARRATIVE FROM RICHARD TAVARRES P.E. DATED
 2/11/16.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-24 Cont ID  
Sent By ccole Date 2015-11-24 Time 10:56 Rev Time 0.00
Received By ccole Date 2015-11-24 Time 10:56 Sent To  
Notes
2015-11-24 11:59:161ST REVIEW 2014 MECHANICAL
 PERMIT #15110808
 11/24/15
  
 1) IN REFERENCE TO THE VEHICLE DELIVERY GARAGE PLEASE
 SEE SECTION 404.1 ENCLOSED PARKING GARAGES.
 MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED PARKING
 GARAGES SHALL BE PERMITTED TO OPERATE INTERMITTENTLY IN
 ACCORDANCE WITH ITEM 1, ITEM 2 OR BOTH.
 1. THE SYSTEM SHALL BE ARRANGED TO OPERATE
 AUTOMATICALLY UPON DETECTION OF VEHICLE OPERATION OR
 THE PRESENCE OF OCCUPANTS BY APPROVED AUTOMATIC
 DETECTION DEVICES.
 2. THE SYSTEM SHALL BE ARRANGED TO OPERATE
 AUTOMATICALLY BY MEANS OF CARBON MONOXIDE DETECTORS
 APPLIED IN CONJUNCTION WITH NITROGEN DIOXIDE DETECTORS.
 SUCH DETECTORS SHALL BE INSTALLED IN ACCORDANCE WITH
 THEIR MANUFACTURER'S RECOMMENDATIONS.
 A) SHEET M1.1: BASED ON THE CODE SECTION ABOVE,
 NITROGEN DIOXIDE DETECTORS SHALL BE INSTALLED ALONG
 WITH THE CO DETECTORS. REVISE THE PLANS ACCORDINGLY AND
 SUBMIT CUT SHEETS FOR THE DETECTORS REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD.
 B) EXHAUST VENTILATION AT A RATE OF .75 CFM/SF. SHALL
 BE INSTALLED IN THE VEHICLE DELIVERY GARAGE- TABLE
 403.3. REVISE THE PLANS TO SHOW THE LCATIONS OF THE
 EXHAUST FAN(S) AND PROVIDE A SEQUENCE OF OPERATION.
 PROVIDE AN EQUIPMENT SCHEDULE FOR THE FANS AND SUBMIT
 PRODUCT SPECS.
 C) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN FOR THE
 NEW EXHAUST FAN(S) AT THE SERVICE/RECEPTION AREAS, AND
 SUBMIT MANUFACTUTERS'S CUT SHEETS AND MIAMI DADE NOA'S
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD.
 3) SHEET M0.1 & M1.1: DUCT SMOKE DETECTORS ARE LISTED
 AS NOT REQUIRED IN THE SCHEDULE, HOWEVER, IN ACCORDANCE
 WITH SECTION 606.2.1 DETECTORS ARE REQUIRED TO BE
 PLACED IN THE RETURN AIR PLENUMS OF RTU'S 1, 3, 6, & 9.
 PLEASE PROVIDE AN INSTALLATION DETAIL AND EQUIPMENT
 SCHEDULE ON THE PLAN, AND SUBMIT MANUFACTURER 'S
 SPECIFICATIONS REVIEW AND APPROVED BY THE DESIGN
 PROFESSIONAL OF RECORD,
 4) M0.1 THE DESIGN CRITERIA FOR THE AC SYSTEM LISTS
 INCORRECT WET AND DRY BULB TEMPERATURES. SEE APPENDIX D
 FBC-14 PLUMBING, AS SHOWN IN THE TABLE THE DRY BULB
 TEMP FOR WPB IS 91 DEGREES, AND THE WET BULB IS 79
 DEGREES: PLEASE CORRECT THE PLAN.
 5) M1.1: BALANCED RETURN AIR IS REQUIRED FOR AHU-1,
 HOWEVER THE PLAN DOESN'T SHOW HOW AIR BEING SUPPLIED
 INTO THE GEN. MANAGER'S OFFICE AND THE MIDDLE CONSULT
 ROOM IS BEING RETURNED TO THE UNIT- SEE SECTION 601.5
 FBC-14 MECHANICAL.
 6) PROVIDE SITE SPECIFIC WIND LOAD TIE DOWN ENGINEERING
 FOR THE NEW ROOF TOP EXHAUST FANS- SECTION 301.15,, AND
 SUBMIT NOA'S OR FL. PRODUCT APPROVALS FOR THE EQUIPMENT
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL OF
 RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-25 Cont ID  
Sent By gjohnson Date 2016-02-25 Time 17:34 Rev Time 0.00
Received By gjohnson Date 2016-02-25 Time 17:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-30 Cont ID  
Sent By tklarge Date 2015-11-30 Time 04:22 Rev Time 0.00
Received By tklarge Date 2015-11-29 Time 08:42 Sent To  
Notes
2015-11-29 09:38:141) CLEARLY INDICATE ON THE PLANS THE EXTENT OF PLUMBING
 WORK BEING DONE TO THE EXISTING RESTROOMS. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
 REVIEW NOT COMPLETE.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-04-25 Cont ID  
Sent By dkittred Date 2016-04-25 Time 13:08 Rev Time 0.00
Received By dkittred Date 2016-04-25 Time 12:09 Sent To  
Notes
2016-04-25 13:10:134/25/16 - ISPR 15-07 FOR ADDITION APPROVED 3/16/16. DK

Review Stop Z ZONING
Rev No 2 Status F Date 2016-03-01 Cont ID  
Sent By dkittred Date 2016-03-01 Time 08:39 Rev Time 0.00
Received By dkittred Date 2016-03-01 Time 08:29 Sent To  
Notes
2016-03-01 08:39:13PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/1/16
  
 PREVIOUS ZONING COMMENT FROM 12/1/15 IS STILL
 APPLICABLE. SITE PLAN STILL UNDER REVIEW WITH THE
 PLANNING DIVISION AND SUBMITTED PLAN MUST MATCH
 APPROVED SITE PLAN ONCE APPROVED.
  
 1. PROPOSED RENOVATION INCLUDES A 1,892 SQUARE FOOT
 EXPANSION. BECAUSE THE EXPANSION IS GREATER THAN 1,000
 SQUARE FEET, A LEVEL I - INFORMAL SITE PLAN REVIEW
 APPLICATION MUST BE SUBMITTED THROUGH THE PLANNING
 DIVISION FOR REVIEW AND APPROVAL PRIOR TO ZONING
 APPROVAL OF THIS BUILDING PERMIT. THE DEVELOPMENT
 APPLICATION FOR SITE PLAN REVIEW CAN BE ACCESSED
 THROUGH THE CITY'S WEBSITE:
 HTTP://WPB.ORG/PLANNING/PLANNING-ZONING-REQUEST-FORMS/
 OR BY CONTACTING ME DIRECTLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2015-12-01 Cont ID  
Sent By dkittrid Date 2015-12-01 Time 09:30 Rev Time 0.00
Received By dkittred Date 2015-12-01 Time 09:14 Sent To  
Notes
2015-12-01 09:30:52PLANNING AND ZONING COMMENTS: ***FAILED***
  
 12/1/15
  
 1. PROPOSED RENOVATION INCLUDES A 1,892 SQUARE FOOT
 EXPANSION. BECAUSE THE EXPANSION IS GREATER THAN 1,000
 SQUARE FEET, A LEVEL I - INFORMAL SITE PLAN REVIEW
 APPLICATION MUST BE SUBMITTED THROUGH THE PLANNING
 DIVISION FOR REVIEW AND APPROVAL PRIOR TO ZONING
 APPROVAL OF THIS BUILDING PERMIT. THE DEVELOPMENT
 APPLICATION FOR SITE PLAN REVIEW CAN BE ACCESSED
 THROUGH THE CITY'S WEBSITE:
 HTTP://WPB.ORG/PLANNING/PLANNING-ZONING-REQUEST-FORMS/
 OR BY CONTACTING ME DIRECTLY.
  