Plan Review Details - Permit 15110807
Plan Review Stops For Permit 15110807
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-01-06 Cont ID  
Sent By pleduc Date 2016-01-06 Time   Rev Time 0.00
Received By pleduc Date 2015-12-23 Time 08:46 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-24 Cont ID  
Sent By pleduc Date 2015-11-25 Time   Rev Time 0.00
Received By pleduc Date 2015-11-20 Time 13:56 Sent To PC
Notes
2015-11-23 16:01:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FORLLOWING COMMENTS:
  
 1. THE VALUE OF THE PERMIT IS BASED UPON THE VALUE OF
 THE OVERALL CONSTRUCTION VALUE OF THE PROJECT NOT JUST
 A PORTION OF IT. PLEASE ADJUST THE VALUE ACCORDINGLY.
  
 2. SHEETTTT LS 051 - THIS SHEET HAS INCORRECT
 INDICATIONS OF THE FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 3. SHEET LS 051 - THIS SHEET HAS INCORRECT INDICATIONS
 OF THE BUILDING CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF THE FLORIDA BUILDING CODE.
  
 4. SHEET LS 051 - THIS SHEET INDICATES REFERENCE TO
 NFPA 130, 2014.
  
 THE FLORIDA FIRE PREVENTION CODE, 5TH EDITION REFENCES
 NFPA 130, 2010. REFERENCES TO THE FIRE CODE CAN NOT BE
 CHERRY PICKED.
  
 5. PLEASE SPECIFY WHAT EDITION OF THE FIRE CODE YOU
 WILL BE REFERENCING AND REVIEW THE SUBMITTED PLANS PER
 THAT CODE.
  
 6. SHEET LS 054 - THE ADDITION OF THE KITCHEN AREA IS
 NEW AND WAS NOT PART OF THE PRE- REVIEW ANALYSIS. THIS
 ADDITION TO THE CONCOURSE IS SIGNIFICANT TO THE
 PROTECTION OF THAT AREA. THE AREA OF THE KITCHEN SHALL
 BE PROTECTED BY A 1-HOUR FIRE WALL/FIRE RATING.
  
 7. SHEET A ? - THERE IS NO SHEET FOR THE EQUIPMENT PLAN
 FOR THE KITCHEN.
  
 8. THE KITCHEN SHALL BE EQUIPPED WITH VENTILATION
 EQUIPMENT PER NFPA 96, 2011
  
 9. SHEET LS 055 - PROVIDE AN EXIT SIGN AT THE SERVICE
 EGRESS DOOR IN THE EGRESS PATH OF TRAVEL.
  
 10. SHEET LS 055 - THE BOH ROOM 211 THE WALL IS NOT
 RATED. THE FIRE RATING SHALL BE EXTENDED TO THE INCLUDE
 THE WALL AND DOOR TO THAT ROOM.
  
 11. SHEET A 211 - DOOR 108.6 OPENS INTO THE PATH OF
 EGRESS TRAVEL. THERE ARE NO DIMENSIONS PROVIDED FOR
 THAT CORRIDOR SPACE.
  
 NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 12. SHEET A 211 & A 801 - DOOR(S) 108.1 (2) INDICATE NO
 RATING. ACCORDING TO SHEE LS 055 IS WITHIN A FIRE RATED
 WALL.
  
 13. SHEET A 211 & A 801 - ROOM 114, INTERIOR DOOR, IS
 NOT INDICATED OR RATED, INCLUDING HARDWARE.
  
 14. SHEET A 211 & 801 - DOOR(S) 108.6 (2) INDICATE NO
 RATING. ACCORDING TO SHEE LS 055 IS WITHIN A FIRE RATED
 WALL.
  
 15. SHEET A ? - NO STAIR DETAIL IS PROVIDED FOR ANY
 STAIR. SPECIFIC DETAIL SHALL BE PROVIDED FOR EACH
 STAIRWAY.
  
 16. SHEET A ? -T HERE IS NO DETAIL FOR THE ESCALATORS
 INCLUDING THE EMERGENCY STOPS AT EACH LEVEL.
  
 17. SHEET A 801 - THERE IS NO REFERENCE INDICATED FOR
 THE EXIT HARDWARE TYPES AND/OR FIRE RATINGS.
  
 18. SHEET A 801 - THERE IS NO REFERENCE INDICATED FOR
 THE TYPE "A, B, C, D ETC." INDICATED. EACH DOOR SHALL
 HAVE IT'S OWN SPECIFIC RATING INDICATED.
  
 19. SHEET A 801 - THERE IS NO RATING"C" INDICATED FOR
 THE DOOR JAMB/FRAME FOR EACH RATED DOOR.
  
 20. SHEET A 211 AND LS 055 - ONCE A PERSON LEAVES A
 RATED AREA THEY SHALL BE PROTECTED WITH THAT RATING
 UNTIL THEY REACH A PUBLIC WAY. THE EGRESS PATH FROM
 DOOR (S) 108.1 & 106.1 SHALL BE PROTECTED ALONG THE
 EXIT PATH TO THE PUBLIC WAY. THE NORTH WALL IN ROOMS
 108 & 114 SHALL BE FIRE RATED. DOOR(S) 115.1 SHALL BE
 FIRE RATED.
  
 21. SHEET A 211 - NO DETAIL IS PROVIDED FOR THE FIRE
 RATED OPENING/DOOR AT THE AREA OF ELEVATOR PE 1 AND THE
 BAGGAGE HANDLING 108 WALL.
  
 22. SHEET A 221 - THE DOOR TO THE STORAGE ROOM IS NOT
 INDICATED.
  
 23. SHEET A 221 - THE DOOR TO THE MEN W/C IS NOT
 INDICATED.
  
 24. SHEET A 221 - THE DOOR TO THE LOST & FOUND IS NOT
 INDICATED OR RATED.
  
 25. SHEET A 232 - DOOR TO THE MENS W/C IS NOT
 INDICATED.
  
 26. SHEET A 232 - THE DOOR TO THE MENS W/C IS NOT
 RATED. ACCORDING TO SHEE LS 053 IS WITHIN A FIRE RATED
 WALL.
  
 27. SHEET A 801 - DOOR 304 HAS NO HARDWARE INDICATED
  
 28. SHEET A 801 - DOOR 316 HAS NO RATING OF THE FRAME
 INDICATED.
  
 29. SHEET A 801 - DOOR 310 HAS NO HARDWARE INDICATED
  
 30. SHEET A 671 IN THE METAL FRAMED PARTITION CALL OUT
 INDICATES A REFERENCE TO SHEET A 676 AND AND A 677 FOR
 THE UL DESIGN. THOSE SHEETS ARE NOT ATTACHED.
  
 31. SHEET FP ? - THERE ARE NO SPRINKLER HEAD LOCATIONS
 INDICATED ON ANY PROPOSED SPRINKLER PLAN.
  
 32. SHEET FP 201 - PROVIDE A 2 1/2 FDVALVE AT EACH
 GROUND FLOOR ESCALTOR VESTIBULE. THIS ALLOWS FOR FIRE
 DEPARTMENT AND FOR FIREFIGHTING OPERATIONS ACCESS UP
 INTO INTO THE CONCOURSE AREA.
  
 33. SHEET FP 202 - PROVIDE A 2 1/2 FDVALVE AT DOOR
 207.1. FD OPERATIONS NEED WATER SUPPLY ACCESS AT THE
 FLOOR BELOW THE FIRE. THE STAIRWELL DOES NOT PROVIDE
 ACCESS TO THE CONCOURSE LEVEL. HAVING FDV INSIDE THE
 DOOR 207.1 PROVIDES PROTECTION FROM THE STAIR AS WELL
 AS ACCESS TO THE CONCOURSE LEVEL.
  
 34. SHEET FP 203 - REMOVE 2 1/2 FDV FROM THE OPEN
 UNPROTECTED CONCOURSE CORRIDOR.
  
 35. SHEET FP 203 - PROVIDE 2 1/2 FDV INSIDE THE 1 HOUR
 PROTECTED BAGGAGE VESTIBULE 316. THIS ALLOWS FOR
 ELEVATOR ACCESS TO THE CONCOURSE LEVEL INTO A FIRE
 RATED ROOM FOR FIREFIGHTING OPERATIONS SETUP INTO THE
 CONCOURSE AREA.
  
 36. SHEET FP 203 - PROVIDE 2 1/2 FDV INSIDE THE 1 HOUR
 PROTECTED BAGGAGE VESTIBULE 314. THIS ALLOWS FOR
 ADDITIONAL ELEVATOR ACCESS TO THE CONCOURSE LEVEL INTO
 A FIRE RATED ROOM FOR FIREFIGHTING OPERATIONS SETUP
 INTO THE CONCOURSE AREA.
  
 37. SHEET FA 211 - THERE IS NO INDICATION OF A FIRE
 COMMAND CENTER / OPERATION CONTROL CENTER.
  
 38. SHEET FA 211 - THERE IS NO INDICATION THE THE FIRE
 ALARM SYSTEM IS CLASS A SYSTEM; CLASS A REQUIRED PER
 THE AHJ.
  
 39. SHEET FA 211 - THERE IS NO INDICATION FO THE
 MECHANICAL EMERGENCY VENTILATION SYSTEM
 CONTROL/OPERATION.
  
 40. SHEET FA 211 - MANUAL PULL STATIONS ARE NOT
 REQUIRED IN THE BATHROOM AND MANAGER ROOM.
  
 41. SHEET FA 211 - THERE IS NO INDICATION OF FIRE
 DEPARTMENT PHONE JACKS IN A FIRE COMMAND
 CENTER/OPERATIONS CENTER.
  
 42. SHEET FA 211 - PROVIDE A HEAT DETECTOR AT F & B
 STORAGE 107.
  
 43. SHEET FA 211 - PROVIDE A SMOKE DETECTOR AT BAGGAGE
 108.
  
 44. SHEET FA 221 - MANUAL PULL STATIONS ARE NOT
 REQUIRED AT AREA 206, 209, 210.1, AND 212.
  
 45. SHEET FA 221 - PROVIDE A MANUAL PULL STATION THE
 STAIR # 1 DOOR 204
  
 46. SHEET FA 221 - PROVIDE A MANUAL PULL STATION AT
 DOOR 207.1.
  
 47. SHEET FA 221 - PROVIDE A SMOKE DETECTOR AT EMPLOYEE
 BREAK ROOM 210.
  
 48. SHEET FA 231 - MANUAL PULL STATIONS ARE NOT
 REQUIRED AT AREA 313.
  
 49. SHEET FA 231 - MANUAL PULL STATIONS ARE NOT
 REQUIRED AT AREA 316.
  
 50. SHEET FA 231 - PROVIDE A MANUAL PULL STATION AT
 ESCALATOR RUNOFF AREA 301.
  
 51. SHEET FA 231 - PROVIDE A MANUAL PULL STATION
 OUTSIDE OF AREA TO 318 ESCALATOR VESTIBULE.
  
 52. SHEET FA 232 - PROVIDE A MANUAL PULL STATION
 OUTSIDE OF AREA TO 306 ESCALATOR VESTIBULE.
  
 53. SHEET FA 232 - MANUAL PULL STATIONS ARE NOT
 REQUIRED AT AREA 311.
  
 54. SHEET ? - PROVIDE INDICATIONS AND SHEETS REGARDING
 THE AGENTS AND INFORMATION BOOTHS SHALL BE CONSTRUCTED
 OF NONCOMBUSTIBLE MATERIALS, PER NFPA 130
  
 55. SHEET ? - PROVIDE INDICATIONS AND SHEETS REGARDING
 THE SEATING FURNITURE SHALL BE NONCOMBUSTIBLE OR MEET
 ASTM E 1537 PER NFPA 130
  
 56. SHEET M 301 - PROVIDE INDICATIONS AND SHEETS
 REGARDING THE EMERGENCY VENTILATION SYSTEM
 CONTROL/OPERATION, INCLUDING THE LOCATION OF THE
 OPERATIONS CONTROL CENTER, PER NFPA 130.
  
 57. SHEET M 301 - THERE IS NO INDICATIONS FOR EMERGENCY
 VENTILATION FOR THE 2ND FLOOR LEVEL.
  
 58. SHEET ? - ALL NEW ELEVATORS SHALL CONFORM TO THE
 FIRE FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF
 ASME A17.1/CSA B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 PROVIDE INDICATIONS AND SHEETS COMPLYING WITH THE ABOVE
 REQUIREMENTS
  
 59. SHEET LS 051 - PROVIDE A STATEMENT INDICATING THE
 GENERATOR WILL BE INSTALLED UNDER SEPARATE PERMIT AND
 SHOP DRAWINGS.
  
 60. SHEET EP ? - PROVIDE INDICATIONS AND SHEETS FOR
 COMPLIANCE WITH ELECTRICAL WIRING REQUIREMENTS PER NFPA
 130, 5.4.
  
 61. SHEET EP ? - PROVIDE INDICATIONS AND SHEETS FOR
 COMPLIANCE WITH ELECTRICAL WIRING REQUIREMENTS PER NFPA
 130, 5.4.8 FOR EMERGENCY LIGHTING AND COMMUNICATION
 CIRCUITS.
  
 62. BASED ON THE CURRENT REVIEW AND THE LIST OF ABOVE
 ITEMS THE BUREAU ENCOURAGES A MORE DETAILED REVIEW
 PRIOR TO THE NEXT SUBMITTAL. ADDITIONAL COMMENTS MAY BE
 GENERATED BASED ON WHAT IS CONTAINED IN THE NEXT
 SUBMITTAL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-06 Cont ID  
Sent By pleduc Date 2016-01-06 Time   Rev Time 0.00
Received By pleduc Date 2015-12-22 Time 10:50 Sent To  
Notes
2015-12-22 10:50:24RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-24 Cont ID  
Sent By pleduc Date 2015-11-24 Time   Rev Time  
Received By pleduc Date   Time   Sent To  
Notes
***NONE***