2015-11-23 16:01:19 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FORLLOWING COMMENTS: |
| |
| 1. THE VALUE OF THE PERMIT IS BASED UPON THE VALUE OF |
| THE OVERALL CONSTRUCTION VALUE OF THE PROJECT NOT JUST |
| A PORTION OF IT. PLEASE ADJUST THE VALUE ACCORDINGLY. |
| |
| 2. SHEETTTT LS 051 - THIS SHEET HAS INCORRECT |
| INDICATIONS OF THE FIRE CODE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2010 EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2010 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2009 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2010 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| |
| 3. SHEET LS 051 - THIS SHEET HAS INCORRECT INDICATIONS |
| OF THE BUILDING CODE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 5TH EDITION OF THE FLORIDA BUILDING CODE. |
| |
| 4. SHEET LS 051 - THIS SHEET INDICATES REFERENCE TO |
| NFPA 130, 2014. |
| |
| THE FLORIDA FIRE PREVENTION CODE, 5TH EDITION REFENCES |
| NFPA 130, 2010. REFERENCES TO THE FIRE CODE CAN NOT BE |
| CHERRY PICKED. |
| |
| 5. PLEASE SPECIFY WHAT EDITION OF THE FIRE CODE YOU |
| WILL BE REFERENCING AND REVIEW THE SUBMITTED PLANS PER |
| THAT CODE. |
| |
| 6. SHEET LS 054 - THE ADDITION OF THE KITCHEN AREA IS |
| NEW AND WAS NOT PART OF THE PRE- REVIEW ANALYSIS. THIS |
| ADDITION TO THE CONCOURSE IS SIGNIFICANT TO THE |
| PROTECTION OF THAT AREA. THE AREA OF THE KITCHEN SHALL |
| BE PROTECTED BY A 1-HOUR FIRE WALL/FIRE RATING. |
| |
| 7. SHEET A ? - THERE IS NO SHEET FOR THE EQUIPMENT PLAN |
| FOR THE KITCHEN. |
| |
| 8. THE KITCHEN SHALL BE EQUIPPED WITH VENTILATION |
| EQUIPMENT PER NFPA 96, 2011 |
| |
| 9. SHEET LS 055 - PROVIDE AN EXIT SIGN AT THE SERVICE |
| EGRESS DOOR IN THE EGRESS PATH OF TRAVEL. |
| |
| 10. SHEET LS 055 - THE BOH ROOM 211 THE WALL IS NOT |
| RATED. THE FIRE RATING SHALL BE EXTENDED TO THE INCLUDE |
| THE WALL AND DOOR TO THAT ROOM. |
| |
| 11. SHEET A 211 - DOOR 108.6 OPENS INTO THE PATH OF |
| EGRESS TRAVEL. THERE ARE NO DIMENSIONS PROVIDED FOR |
| THAT CORRIDOR SPACE. |
| |
| NFPA 101 CHAPTER 7, MEANS OF EGRESS |
| 7.2.1.4.3 DOOR LEAF ENCROACHMENT |
| 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS |
| OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE |
| REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, |
| OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT |
| MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A |
| CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN, |
| UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN |
| EXISTING BUILDING. |
| (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS |
| PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED |
| WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY |
| OPEN. |
| |
| 12. SHEET A 211 & A 801 - DOOR(S) 108.1 (2) INDICATE NO |
| RATING. ACCORDING TO SHEE LS 055 IS WITHIN A FIRE RATED |
| WALL. |
| |
| 13. SHEET A 211 & A 801 - ROOM 114, INTERIOR DOOR, IS |
| NOT INDICATED OR RATED, INCLUDING HARDWARE. |
| |
| 14. SHEET A 211 & 801 - DOOR(S) 108.6 (2) INDICATE NO |
| RATING. ACCORDING TO SHEE LS 055 IS WITHIN A FIRE RATED |
| WALL. |
| |
| 15. SHEET A ? - NO STAIR DETAIL IS PROVIDED FOR ANY |
| STAIR. SPECIFIC DETAIL SHALL BE PROVIDED FOR EACH |
| STAIRWAY. |
| |
| 16. SHEET A ? -T HERE IS NO DETAIL FOR THE ESCALATORS |
| INCLUDING THE EMERGENCY STOPS AT EACH LEVEL. |
| |
| 17. SHEET A 801 - THERE IS NO REFERENCE INDICATED FOR |
| THE EXIT HARDWARE TYPES AND/OR FIRE RATINGS. |
| |
| 18. SHEET A 801 - THERE IS NO REFERENCE INDICATED FOR |
| THE TYPE "A, B, C, D ETC." INDICATED. EACH DOOR SHALL |
| HAVE IT'S OWN SPECIFIC RATING INDICATED. |
| |
| 19. SHEET A 801 - THERE IS NO RATING"C" INDICATED FOR |
| THE DOOR JAMB/FRAME FOR EACH RATED DOOR. |
| |
| 20. SHEET A 211 AND LS 055 - ONCE A PERSON LEAVES A |
| RATED AREA THEY SHALL BE PROTECTED WITH THAT RATING |
| UNTIL THEY REACH A PUBLIC WAY. THE EGRESS PATH FROM |
| DOOR (S) 108.1 & 106.1 SHALL BE PROTECTED ALONG THE |
| EXIT PATH TO THE PUBLIC WAY. THE NORTH WALL IN ROOMS |
| 108 & 114 SHALL BE FIRE RATED. DOOR(S) 115.1 SHALL BE |
| FIRE RATED. |
| |
| 21. SHEET A 211 - NO DETAIL IS PROVIDED FOR THE FIRE |
| RATED OPENING/DOOR AT THE AREA OF ELEVATOR PE 1 AND THE |
| BAGGAGE HANDLING 108 WALL. |
| |
| 22. SHEET A 221 - THE DOOR TO THE STORAGE ROOM IS NOT |
| INDICATED. |
| |
| 23. SHEET A 221 - THE DOOR TO THE MEN W/C IS NOT |
| INDICATED. |
| |
| 24. SHEET A 221 - THE DOOR TO THE LOST & FOUND IS NOT |
| INDICATED OR RATED. |
| |
| 25. SHEET A 232 - DOOR TO THE MENS W/C IS NOT |
| INDICATED. |
| |
| 26. SHEET A 232 - THE DOOR TO THE MENS W/C IS NOT |
| RATED. ACCORDING TO SHEE LS 053 IS WITHIN A FIRE RATED |
| WALL. |
| |
| 27. SHEET A 801 - DOOR 304 HAS NO HARDWARE INDICATED |
| |
| 28. SHEET A 801 - DOOR 316 HAS NO RATING OF THE FRAME |
| INDICATED. |
| |
| 29. SHEET A 801 - DOOR 310 HAS NO HARDWARE INDICATED |
| |
| 30. SHEET A 671 IN THE METAL FRAMED PARTITION CALL OUT |
| INDICATES A REFERENCE TO SHEET A 676 AND AND A 677 FOR |
| THE UL DESIGN. THOSE SHEETS ARE NOT ATTACHED. |
| |
| 31. SHEET FP ? - THERE ARE NO SPRINKLER HEAD LOCATIONS |
| INDICATED ON ANY PROPOSED SPRINKLER PLAN. |
| |
| 32. SHEET FP 201 - PROVIDE A 2 1/2 FDVALVE AT EACH |
| GROUND FLOOR ESCALTOR VESTIBULE. THIS ALLOWS FOR FIRE |
| DEPARTMENT AND FOR FIREFIGHTING OPERATIONS ACCESS UP |
| INTO INTO THE CONCOURSE AREA. |
| |
| 33. SHEET FP 202 - PROVIDE A 2 1/2 FDVALVE AT DOOR |
| 207.1. FD OPERATIONS NEED WATER SUPPLY ACCESS AT THE |
| FLOOR BELOW THE FIRE. THE STAIRWELL DOES NOT PROVIDE |
| ACCESS TO THE CONCOURSE LEVEL. HAVING FDV INSIDE THE |
| DOOR 207.1 PROVIDES PROTECTION FROM THE STAIR AS WELL |
| AS ACCESS TO THE CONCOURSE LEVEL. |
| |
| 34. SHEET FP 203 - REMOVE 2 1/2 FDV FROM THE OPEN |
| UNPROTECTED CONCOURSE CORRIDOR. |
| |
| 35. SHEET FP 203 - PROVIDE 2 1/2 FDV INSIDE THE 1 HOUR |
| PROTECTED BAGGAGE VESTIBULE 316. THIS ALLOWS FOR |
| ELEVATOR ACCESS TO THE CONCOURSE LEVEL INTO A FIRE |
| RATED ROOM FOR FIREFIGHTING OPERATIONS SETUP INTO THE |
| CONCOURSE AREA. |
| |
| 36. SHEET FP 203 - PROVIDE 2 1/2 FDV INSIDE THE 1 HOUR |
| PROTECTED BAGGAGE VESTIBULE 314. THIS ALLOWS FOR |
| ADDITIONAL ELEVATOR ACCESS TO THE CONCOURSE LEVEL INTO |
| A FIRE RATED ROOM FOR FIREFIGHTING OPERATIONS SETUP |
| INTO THE CONCOURSE AREA. |
| |
| 37. SHEET FA 211 - THERE IS NO INDICATION OF A FIRE |
| COMMAND CENTER / OPERATION CONTROL CENTER. |
| |
| 38. SHEET FA 211 - THERE IS NO INDICATION THE THE FIRE |
| ALARM SYSTEM IS CLASS A SYSTEM; CLASS A REQUIRED PER |
| THE AHJ. |
| |
| 39. SHEET FA 211 - THERE IS NO INDICATION FO THE |
| MECHANICAL EMERGENCY VENTILATION SYSTEM |
| CONTROL/OPERATION. |
| |
| 40. SHEET FA 211 - MANUAL PULL STATIONS ARE NOT |
| REQUIRED IN THE BATHROOM AND MANAGER ROOM. |
| |
| 41. SHEET FA 211 - THERE IS NO INDICATION OF FIRE |
| DEPARTMENT PHONE JACKS IN A FIRE COMMAND |
| CENTER/OPERATIONS CENTER. |
| |
| 42. SHEET FA 211 - PROVIDE A HEAT DETECTOR AT F & B |
| STORAGE 107. |
| |
| 43. SHEET FA 211 - PROVIDE A SMOKE DETECTOR AT BAGGAGE |
| 108. |
| |
| 44. SHEET FA 221 - MANUAL PULL STATIONS ARE NOT |
| REQUIRED AT AREA 206, 209, 210.1, AND 212. |
| |
| 45. SHEET FA 221 - PROVIDE A MANUAL PULL STATION THE |
| STAIR # 1 DOOR 204 |
| |
| 46. SHEET FA 221 - PROVIDE A MANUAL PULL STATION AT |
| DOOR 207.1. |
| |
| 47. SHEET FA 221 - PROVIDE A SMOKE DETECTOR AT EMPLOYEE |
| BREAK ROOM 210. |
| |
| 48. SHEET FA 231 - MANUAL PULL STATIONS ARE NOT |
| REQUIRED AT AREA 313. |
| |
| 49. SHEET FA 231 - MANUAL PULL STATIONS ARE NOT |
| REQUIRED AT AREA 316. |
| |
| 50. SHEET FA 231 - PROVIDE A MANUAL PULL STATION AT |
| ESCALATOR RUNOFF AREA 301. |
| |
| 51. SHEET FA 231 - PROVIDE A MANUAL PULL STATION |
| OUTSIDE OF AREA TO 318 ESCALATOR VESTIBULE. |
| |
| 52. SHEET FA 232 - PROVIDE A MANUAL PULL STATION |
| OUTSIDE OF AREA TO 306 ESCALATOR VESTIBULE. |
| |
| 53. SHEET FA 232 - MANUAL PULL STATIONS ARE NOT |
| REQUIRED AT AREA 311. |
| |
| 54. SHEET ? - PROVIDE INDICATIONS AND SHEETS REGARDING |
| THE AGENTS AND INFORMATION BOOTHS SHALL BE CONSTRUCTED |
| OF NONCOMBUSTIBLE MATERIALS, PER NFPA 130 |
| |
| 55. SHEET ? - PROVIDE INDICATIONS AND SHEETS REGARDING |
| THE SEATING FURNITURE SHALL BE NONCOMBUSTIBLE OR MEET |
| ASTM E 1537 PER NFPA 130 |
| |
| 56. SHEET M 301 - PROVIDE INDICATIONS AND SHEETS |
| REGARDING THE EMERGENCY VENTILATION SYSTEM |
| CONTROL/OPERATION, INCLUDING THE LOCATION OF THE |
| OPERATIONS CONTROL CENTER, PER NFPA 130. |
| |
| 57. SHEET M 301 - THERE IS NO INDICATIONS FOR EMERGENCY |
| VENTILATION FOR THE 2ND FLOOR LEVEL. |
| |
| 58. SHEET ? - ALL NEW ELEVATORS SHALL CONFORM TO THE |
| FIRE FIGHTER?S EMERGENCY OPERATIONS REQUIREMENTS OF |
| ASME A17.1/CSA B44, SAFETY CODE FOR ELEVATORS. |
| |
| ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN |
| WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL |
| LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET |
| MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER |
| ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN |
| AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE |
| IN THE HORIZONTAL POSITION. |
| |
| PROVIDE INDICATIONS AND SHEETS COMPLYING WITH THE ABOVE |
| REQUIREMENTS |
| |
| 59. SHEET LS 051 - PROVIDE A STATEMENT INDICATING THE |
| GENERATOR WILL BE INSTALLED UNDER SEPARATE PERMIT AND |
| SHOP DRAWINGS. |
| |
| 60. SHEET EP ? - PROVIDE INDICATIONS AND SHEETS FOR |
| COMPLIANCE WITH ELECTRICAL WIRING REQUIREMENTS PER NFPA |
| 130, 5.4. |
| |
| 61. SHEET EP ? - PROVIDE INDICATIONS AND SHEETS FOR |
| COMPLIANCE WITH ELECTRICAL WIRING REQUIREMENTS PER NFPA |
| 130, 5.4.8 FOR EMERGENCY LIGHTING AND COMMUNICATION |
| CIRCUITS. |
| |
| 62. BASED ON THE CURRENT REVIEW AND THE LIST OF ABOVE |
| ITEMS THE BUREAU ENCOURAGES A MORE DETAILED REVIEW |
| PRIOR TO THE NEXT SUBMITTAL. ADDITIONAL COMMENTS MAY BE |
| GENERATED BASED ON WHAT IS CONTAINED IN THE NEXT |
| SUBMITTAL. |
| |
| |
| PETER LEDUC |