Plan Review Stops For Permit 15110782 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2016-05-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2016-05-03 |
Time |
11:27 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2016-05-03 |
Time |
11:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-04-23 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2016-04-23 |
Time |
16:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2016-04-23 |
Time |
16:13 |
Sent To |
|
|
Notes |
2016-04-23 16:17:28 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. SEE THE DCA APPROVAL: | | | | EACH CODE CHANGE WILL MAKE YOUR PLANS OBSOLETE UNTIL | | THEY HAVE BEEN REVIEWED, APPROVED AND INDICATED (ON THE | | COVER PAGE OF THE PLANS) FOR COMPLIANCE WITH THE CODE . | | . . | | | | IT APPEARS THAT, ALTHOUGH THE DCA APPROVAL HAS AN | | EXPIRATION DATE OF 9/23/2016, DUE TO THE CODE CHANGE | | FROM FBC 2010 TO FBC 2014, THE DCA APPROVAL IS EXPIRED. | | PLEASE PROVIDE A CURRENT APPROVAL. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2015-12-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-12-05 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-12-05 |
Time |
14:07 |
Sent To |
|
|
Notes |
2015-12-05 14:09:19 | ****PROVISO**** | | ISSUED AT CONTRACTOR?S RISK | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | NO INFORMATION WAS SUBMITTED REGARDING THE "PROPOSED | | 11X16 EQUIPMENT SHELTER." | | | | PROVIDE EITHER ENGINEERING FOR THE SHELTER STRUCTURE OR | | FLORDA DCA MODULAR APPROVAL AT INSPECTION | | | | SUBJECT TO FIELD INSPECTOR'S DISCRETION, A REVISION | | (WITH FEES) MAY BE REQUIRED. | | | | FBC 1609 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-05-23 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-05-23 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-05-23 |
Time |
16:05 |
Sent To |
ENG |
|
Notes |
2016-05-04 17:33:00 | NOT YET RETURNED TO BIN BY FIRE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-01-21 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-01-21 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-01-21 |
Time |
11:12 |
Sent To |
|
|
Notes |
2016-01-21 13:12:39 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN | | REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, | | (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, | | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST | | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF | | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. | | | | 1. GENERAL NOTES #12: THE WORDS ?ROMEX? & ?BX? AS USED | | IN THIS NOTE IS TO IDENTIFY A TYPE OF CABLE. ROMEX IS A | | BRAND NAME AND NOT A CABLE TYPE, REFER TO CABLE TYPES | | ?NM?, ?NMC? OR ?NMS? AND CORRECT THE NOTE ACCORDINGLY. | | 2. GENERAL NOTES #14 PROHIBIT THE USE OF FUSES. THE | | DISCONNECT ON THE EXTERIOR SURFACE OF THE SHELTER SHALL | | HAVE A PROPERLY RATED CIRCUIT BREAKER. | | 3. CORRECT THE UTILITY SOURCE CONDUCTOR LABELING IN THE | | METER DETAIL ON SHEET E4 FOR A REGULAR 120/240 SINGLE | | PHASE SERVICE. | | 4. PROVIDE LOAD CALCS FOR THE PROPOSED 800 AMP SERVICE. | | 5. PROVIDE A CIRCUIT DIRECTORY. | | 6. PROVIDE SHELTER DETAILS. IF THE SHELTER IS TO BE A | | SELF-CONTAINED PREMANUFACTURERD UNIT, PROVIDE THE | | ELECTRICAL SPEC SHEET WITH THE REQUIREMENTS. IF IT IS | | TO BE SITE BUILT, SUBMIT A CODE COMPLIANT ELECTRICAL | | FLOOR PLAN. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE | | LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE | | NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE | | STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE | | INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK | | VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
2 |
Status |
P |
Date |
2016-06-03 |
|
|
Cont ID |
|
Sent By |
Mgonzale |
Date |
2016-06-03 |
Time |
|
Rev Time |
1.00 |
Received By |
mgonzale |
Date |
2016-06-03 |
Time |
|
Sent To |
I |
|
Notes |
2016-06-03 14:21:01 | PASSED WITH PROVISOS: | | | | #1 CALL 811 AND LOCATE ALL PUBLIC UTILITIES. | | | | #2 WORK IN THE PROXIMITY OF CITY OF WPB PUBLIC SANITARY | | SEWER MAIN SHALL BE COORDINATED IN CONJUNCTION WITH THE | | RELOCATION | | AND ABANDONMENT OF THE SANITARY PIPE. PIPE IS LOCATED | | ON YOUR PRIVATE PROPERTY AND SHALL NOT BE PLACED OUT OF | | SERVICE. | | | | #3 ALL PRECONSTRUCTION MEETINGS SHALL NOTIFY CITY OF | | WPB PUBLIC UTILITY CONTACT : LAURA LE, P.E. 401 | | CLEMATIS ST, WEST PALM BEACH, FL 33401 | | (561) 494-1093. EMAIL: [email protected] | | | | ENGINEERING SERVICES | | PUBLIC WORKS DEPARTMENT | | 401 CLEMATIS STREET, 4TH FLOOR | | WEST PALM BEACH, FL 33401 | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | MAIN PHONE: (561) 822-1200 | | FAX: (561) 494-1116 | | | | | | |
|
|
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2016-01-21 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-01-21 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
cranford |
Date |
2016-01-21 |
Time |
14:27 |
Sent To |
|
|
Notes |
2016-01-21 14:17:28 | REVIEW BY KCRANFORD |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-05-04 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-05-04 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-05-04 |
Time |
12:22 |
Sent To |
|
|
Notes |
2016-05-04 12:23:19 | 1ST REVIEW COMMENTS RE-SUBMITTED" | | | | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. IT IS RECOMMENDED THAT A KNOX PADLOCK BE PROVIDED AT | | THE GATE AND A KNOX BOX AT THE DOOR IN THE EVENT OF | | EMERGENCY ACCESS. | | | | 2. PROVIDE A FIRE EXTINGUISHER THAT MEETS THE NEEDS FOR | | THE TYPE OF EQUIPMENT INSTALLED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2015-11-30 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2015-11-30 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2015-11-30 |
Time |
10:54 |
Sent To |
|
|
Notes |
2015-11-30 10:58:58 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. IT IS RECOMMENDED THAT A KNOX PADLOCK BE PROVIDED AT | | THE GATE AND A KNOX BOX AT THE DOOR IN THE EVENT OF | | EMERGENCY ACCESS. | | | | 2. PROVIDE A FIRE EXTINGUISHER THAT MEETS THE NEEDS FOR | | THE TYPE OF EQUIPMENT INSTALLED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-06-03 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2016-06-03 |
Time |
15:23 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2016-04-19 |
Time |
10:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-01-21 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-01-21 |
Time |
14:16 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-11-18 |
Time |
14:14 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2015-12-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-12-05 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-12-05 |
Time |
14:09 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2016-05-23 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2016-05-23 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2016-05-06 |
Time |
14:43 |
Sent To |
|
|
Notes |
2016-05-23 14:21:55 | PROVISO | | | | 1. PRIOR TO THE ISSUANCE OF A CERTIFICATE OF COMPLETION | | FOR THE TOWER AND ENCLOSURE, LANDSCAPING ADJACENT TO | | THE ENCLOSURE WALL SHALL BE PERMITTED AND INSTALLED PER | | THE LANDSCAPE PLAN APPROVED FOR THE SITE. | | | | 2. ALL FEED LINES SHALL BE ROUTED INTERNAL TO THE | | MONOPOLE. | | | | 3. THE TOWER, ANTENNA, FEED LINES, BRACKETS, AND ALL | | OTHER EQUIPMENT/COMPONENTS MOUNTED TO AND VISIBLE ON | | THE OUTSIDE OF THE TOWER SHALL BE PAINTED WHITE. | | | | 4. PURSUANT TO SECTION 94-325(D)(7) OF THE CITY?S | | ZONING AND LAND DEVELOPMENT REGULATIONS, THE EXISTING | | TOWER, INCLUDING TOWER BASE, SHALL BE REMOVED WITHIN 90 | | DAYS OF COMPLETION OF THE NEW TOWER. | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL | | PLANNER, AT [email protected] OR (561) 822-1448. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2015-12-14 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2015-12-14 |
Time |
16:40 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2015-12-14 |
Time |
16:40 |
Sent To |
|
|
Notes |
2015-12-14 16:42:06 | ZONING PLAN REVIEW | | ___________________________________________ | | | | DATE OF REVIEW: 12.14.2015 | | PERMIT NO.: 15110782 | | ADDRESS: 501 PALM STREET | | CONTRACTOR/CONTACT: | | TELEPHONE NO.: | | SCOPE OF REVIEW: REPLACE EXISTING COMMUNICATIONS TOWER | | (MITIGATION) | | ___________________________________________ | | | | REVIEW STATUS: FAILED | | ___________________________________________ | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | REVIEW COMMENTS: | | | | 1. PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | WIRELESS COMMUNICATIONS ANTENNAS AND EQUIPMENT, A | | WIRELESS COMMUNICATION FACILITY DEVELOPMENT APPLICATION | | SHALL BE APPROVED BY THE DEVELOPMENT SERVICES | | DEPARTMENT ? PLANNING DIVISION. SUCH APPLICATION HAS | | BEEN SUBMITTED AND IS CURRENTLY BEING REVIEWED, BUT | | WILL NEED TO BE APPROVED PRIOR TO ISSUANCE OF THE | | BUILDING PERMIT. | | ___________________________________________ | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | ___________________________________________ | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | 401 CLEMATIS STREET - P.O. BOX 3147 | | WEST PALM BEACH, FLORIDA 33402 | | | | P: 561.822.1448 | | F: 561.822.1460 | | | | E: [email protected] | | | | W: WPB.ORG | | |
|
|