2015-12-02 09:26:47 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-12-02 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2015-11-19 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2015-11-17 |
Time |
10:21 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2015-12-07 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-12-07 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-12-07 |
Time |
12:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2015-12-04 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-12-04 |
Time |
07:32 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-12-04 |
Time |
07:32 |
Sent To |
|
|
Notes |
2015-12-04 07:38:20 | 2ND REVIEW 2014 MECHANICAL | | PERMIT #15110746 | | 12/4/15 | | | | 1) AS PREVIOUSLY REQUESTED IN THE 1ST REVIEW, PROVIDE | | THE THE AMOUNT OF SUPPLY CFM'S AT EACH DIFFUSER | | LOCATION. PLEASE NOTE THAT THE THE TRANSFER GRILLS | | SIZED AT 48 SQ. INCHES WILL ONLY RETURN 100 CFM'S OF | | SUPPLY AIR FROM THE BEDROOMS- SEE SECTION M1602.4 | | FBC-14 RESIDENTIAL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-11-19 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2015-12-02 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-11-19 |
Time |
14:48 |
Sent To |
|
|
Notes |
2015-11-19 14:50:25 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15110746 | | 11/19/15 | | | | 1) PROVIDE THE SUPPLY DIFFUSER AND RETURN TRANSFER | | GRILL SIZES ON THE PLAN. | | 2) AIR DISTRIBUTION NOT SHOWN ON THE PLAN: PLEASE | | INDICATE THE SUPPLY CFM'S AT EACH DIFFUSER LOCATION, | | AND AT EACH RETURN OR TRANSFER GRILL. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
|