Plan Review Details - Permit 15110686
Plan Review Stops For Permit 15110686
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-04-21 Cont ID  
Sent By jgomez Date 2016-04-21 Time 18:20 Rev Time 0.00
Received By jgomez Date 2016-04-21 Time 18:20 Sent To  
Notes
2016-04-21 18:21:24BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FIXED
 WINDOWS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-04-14 Cont ID  
Sent By jgomez Date 2016-04-14 Time 17:14 Rev Time 0.00
Received By jgomez Date 2016-04-14 Time 16:17 Sent To  
Notes
2016-04-14 17:16:21BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE BEFORE INSTALLATION.
 NOTE: NEED SHUTTERS FOR FIXED WINDOWS AND EXTERIOR
 DOORS WITH GLAZING THAT HAVE NON-IMPACT GLASS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-04-14 Cont ID  
Sent By jgomez Date 2016-03-29 Time 11:20 Rev Time 0.00
Received By jgomez Date 2016-03-29 Time 11:11 Sent To  
Notes
2016-03-29 11:13:17BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE BEFORE INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-02 Cont ID  
Sent By jgomez Date 2016-03-01 Time 13:57 Rev Time 0.00
Received By jgomez Date 2016-03-01 Time 13:57 Sent To  
Notes
2016-03-01 14:00:42RESIDENTIAL (R3) ALTERATION SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
  
 ***NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT THE PERMIT WILL BE ISSUED AND CONTRACTOR
 WILL ADDRESS THE COMMENTS BELOW AFTER THE PERMIT IS
 ISSUED AND BEFORE ANY INSPECTIONS. REVISION FEES WILL
 APPLY. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED.
  
 1- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. NO SCHEDULE SUBMITTED THIS TIME. SEC. 107.2.1
 CITY AMENDMENTS.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) ENGINEER WHO SIGNED AND SEALED THE ENERGY
 CALCULATIONS TO LEGIBLY PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY F.A.C. SEC. 61G15-23.002(2).
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) PROVIDE COMPLETE INFORMATION FOR THE WINDOWS
 OVERHANG DEPTH AND SEPARATION ON PAGE 3 OF 4. SEE
 PLANS. SEC. R101.5.1.1.2 OF FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 REPEAT COMMENT. RESPONSE LETTER STATES THERE IS NOT
 OVERHANG FOR THIS BUILDING. NEVERTHELESS, THERE IS AN
 OVERHANG SEPARATION. THERE IS NOT INFORMATION GIVEN FOR
 THE OVERHANG SEPARATION. SEE PLANS AND REVISE AS
 REQUIRED.
  
 C) PROVIDE COMPLETE INFORMATION IN THE ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 REPEAT COMMENT. NEED BUILDER'S SIGNATURE AND DATE.
  
 D) BUNKER ENGINEERING AND CONSTRUCTION IS NOT THE
 BUILDER. REVISE AS REQUIRED. PROVIDE THE CORRECT
 BUILDER'S NAME. SEC. R101.5.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE
 U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS
 ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By jgomez Date 2015-12-22 Time 16:53 Rev Time 0.00
Received By jgomez Date 2015-12-22 Time 14:48 Sent To  
Notes
2015-12-22 15:52:35RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014)
  
 1- EXISTING ENCLOSED PORCH AREA IS ALTERED TO EXPAND
 THE LIVING AREA. BRING PLANS TO PALM BEACH COUNTY (2300
 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) THERE IS A PERMIT APPLICATION FOR ROOFING
 SUB-PERMIT. PROVIDE PRODUCT APPROVAL FOR ROOF MATERIAL
 TO BE INSTALLED. AND, CLEARLY IDENTIFY APPROVED
 ASSEMBLY TO BE INSTALLED. ALSO, PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS IF SELECTED ASSEMBLY
 DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 B) WINDOW MULLIONS AS SHOWN ON PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 SUBMITTED. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 D) OUTSWING ENTRY DOOR AS SHOWN ON PLANS. DRAWINGS
 SUBMITTED WITH FLORIDA PRODUCT APPROVAL FL11136-R3 ARE
 FOR "INSWING" DOORS. NEED DRAWINGS FOR "OUTSWING" DOOR.
  
 E) OUTSWING KITCHEN DOOR THAT MEETS THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER ON SHEET S.1.
 DESIGN PRESSURES FOR DOOR SUBMITTED WITH FLORIDA
 PRODUCT APPROVAL FL15474-R1 DON'T MEET THE CALCULATED
 DESIGN PRESSURES. PRODUCT APPROVAL NEED TO MEET OR
 EXCEED THE CALCULATED DESIGN PRESSURES.
  
 F) HURRICANE SHUTTERS FOR WINDOWS AND DOORS WITHOUT
 IMPACT RATED GLAZING . AND, PROVIDE COMPLETE
 INSTALLATION SCHEDULE. SEE INSTALLATION SCHEDULE CITY
 SAMPLE OR PROVIDE COMPLETE INSTALLATION SCHEDULE IN ANY
 OTHER FORMAT THAT HAS ALL THE REQUIRED INFORMATION.
  
 3- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 4- WINDOW AND DOOR SCHEDULE SHOWN ON SHEET S.1 CALL FOR
 WINDOWS AND DOORS WITH IMPACT GLAZING. PRODUCT
 APPROVALS SUBMITTED DON'T HAVE IMPACT GLAZING. REVISE
 AS REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 5- ENERGY CALCULATIONS SUBMITTED:
 A) ENGINEER WHO SIGNED AND SEALED THE ENERGY
 CALCULATIONS TO PROVIDE ALL HIS INFORMATION AS REQUIRED
 BY F.A.C. SEC. 61G15-23.002 AND F.S. 471.
  
 B) ENGINEER WHO SIGNED AND SEALED THE ENERGY
 CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY F.A.C. SEC. 61G15-23.002. AND F.S. 471.
  
 C) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) ITEM #11: PROVIDE DOCUMENTATION SHOWING HOW
 OBTAINING THE R-8 VALUE FOR DUCT. SEC. R405.4.3 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: SEE MECHANICAL NOTES ON MECHANICAL PLAN M.1.
  
 E) CLIMATE ZONE SHOWN ON PAGE 2 OF 4 IS INCORRECT. SEE
 TABLE R301.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014) AND REVISE AS REQUIRED.
  
 F) PROVIDE COMPLETE INFORMATION FOR THE WINDOWS
 OVERHANG DEPTH AND SEPARATION. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 G) PROVIDE COMPLETE INFORMATION THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 IMPORTANT: LABEL FOR WINDOWS AND DOORS SHOWING THE
 U-FACTOR AND SHGC FACTOR SPECIFIED ON THE ENERGY
 CALCULATIONS WILL BE REQUIRED WHEN ENERGY CALCULATIONS
 ARE NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 6- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. REVISE VALUATION AS REQUIRED. INCLUDE THE
 ROOFING SCOPE OF WORK.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-04-21 Cont ID  
Sent By mvaldes Date 2016-04-21 Time 17:51 Rev Time 0.00
Received By mvaldes Date 2016-04-21 Time 17:51 Sent To  
Notes
2016-04-21 17:51:33ROUTED TO JULIO GOMEZ

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-18 Cont ID  
Sent By mvaldes Date 2016-02-18 Time 19:00 Rev Time 0.00
Received By mvaldes Date 2016-02-18 Time 19:00 Sent To  
Notes
2016-02-18 19:05:36ROUTED TO JULIO GOMEZ

Review Stop E ELECTRICAL
Rev No 1 Status P Date   Cont ID  
Sent By jgomez Date 2015-12-23 Time 10:39 Rev Time 0.00
Received By mvaldes Date 2015-12-23 Time 15:27 Sent To  
Notes
2015-12-23 15:32:141ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 PROVISO
  
 (C) BOXES AT CEILING-SUSPENDED (PADDLE) FAN OUTLETS.
 OUTLET BOXES OR OUTLET BOX SYSTEMS USED AS THE SOLE
 SUPPORT
 OF A CEILING-SUSPENDED (PADDLE) FAN SHALL BE LISTED,
 SHALL BE
 MARKED BY THEIR MANUFACTURER AS SUITABLE FOR THIS
 PURPOSE,
 AND SHALL NOT SUPPORT CEILING-SUSPENDED (PADDLE) FANS
 THAT
 WEIGH MORE THAN 32 KG (70 LB). FOR OUTLET BOXES OR
 OUTLET BOX
 SYSTEMS DESIGNED TO SUPPORT CEILING-SUSPENDED (PADDLE)
 FANS
 THAT WEIGH MORE THAN 16 KG (35 LB), THE REQUIRED
 MARKING SHALL
 INCLUDE THE MAXIMUM WEIGHT TO BE SUPPORTED.
  
 R404.1 LIGHTING EQUIPMENT (MANDATORY).
 A MINIMUM OF 75 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS OR A MINIMUM OF 75 PERCENT OF THE PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL CONTAIN ONLY HIGH
 EFFICACY LAMPS.
  
 R315.1 CARBON MONOXIDE PROTECTION.
 EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-04-18 Cont ID  
Sent By jgomez Date 2016-04-18 Time 09:17 Rev Time 0.00
Received By jgomez Date 2016-04-18 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-14 Cont ID  
Sent By jgomez Date 2016-04-14 Time 16:17 Rev Time 0.00
Received By jgomez Date 2016-04-14 Time 14:17 Sent To  
Notes
2016-04-14 17:17:4304/14/16 RECEIVED E-MAIL FROM MECHANICAL ENGINEER
 MICHAEL BASSFORD REGARDING THE EQUIPMENT CALCULATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-02 Cont ID  
Sent By jgomez Date 2016-03-02 Time 15:29 Rev Time 0.00
Received By jgomez Date 2016-02-18 Time 13:54 Sent To  
Notes
2016-02-18 13:54:51RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-18 Cont ID  
Sent By lmarchan Date 2016-02-18 Time 13:52 Rev Time 0.00
Received By lmarchan Date 2015-11-17 Time 10:35 Sent To  
Notes
2015-11-18 10:38:06R08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2016-03-29 Cont ID  
Sent By jgomez Date 2016-03-29 Time 12:04 Rev Time 0.00
Received By jgomez Date 2016-03-29 Time 12:04 Sent To  
Notes
2016-03-29 12:05:07$1101.25 PAID. MU-2016-6730.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-03-02 Cont ID  
Sent By jgomez Date 2016-03-02 Time 14:46 Rev Time 0.00
Received By jgomez Date 2016-03-02 Time 14:46 Sent To  
Notes
2016-03-02 14:46:481- EXISTING ENCLOSED PORCH AREA IS ALTERED TO EXPAND
 THE LIVING AREA. BRING PLANS TO PALM BEACH COUNTY (2300
 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By jgomez Date 2015-12-22 Time 17:00 Rev Time 0.00
Received By jgomez Date 2015-12-22 Time 16:53 Sent To  
Notes
2015-12-22 17:00:491- EXISTING ENCLOSED PORCH AREA IS ALTERED TO EXPAND
 THE LIVING AREA. BRING PLANS TO PALM BEACH COUNTY (2300
 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. COUNTY IMPACT FEE ORDINANCE OF THE UNIFIED
 LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2016-04-21 Cont ID  
Sent By jgomez Date 2016-04-21 Time 18:52 Rev Time 0.00
Received By jgomez Date 2016-04-21 Time 18:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2016-04-18 Cont ID  
Sent By jgomez Date 2016-04-18 Time 09:18 Rev Time 0.00
Received By jgomez Date 2016-04-18 Time 09:17 Sent To  
Notes
2016-04-18 09:35:15RESIDENTIAL (R3) ALTERATION FIFTH MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
 1- PREVIOUS MECHANICAL REVIEWS WERE DENIED BECAUSE THE
 A/C UNIT MAY HAVE BEING OVERSIZED. ENGINEER WAS
 INFORMED VIA PHONE CONVERSATION THAT THE CALCULATIONS
 NEED TO BE DONE BASED ON THE INTERIOR DESIGN
 TEMPERATURES. THE CODE REQUIRES THE A/C SIZING
 CALCULATIONS TO BE DONE BASED ON THE INTERIOR DESIGN
 TEMPERATURES OF 75 DEGREES MINIMUM FOR COOLING AND 72
 DEGREES MAXIMUM FOR HEATING AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). THE CALCULATIONS SUBMITTED DON'T SEEM TO COMPLY
 WITH THIS INTERIOR DESIGN TEMPERATURES. PAGE 1 OF 1 OF
 AIR SYSTEM SIZING SUMMARY FOR FAMILY-BEDROOMS AHU-1
 SHOWS DESIGN SUPPLY TEMP..........58.0 DEGREES.
 THEREFORE, IT DOESN'T SEEM TO COMPLY. REVISE AS
 REQUIRED.
  
 2- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1.
 EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY ITEMS #1 ABOVE. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: THE DESIGN PROFESSIONAL MAY BE CHARGED FOUR TIMES
 THE PLAN REVIEW FEE IF REVIEW IS DENIED AGAIN AS
 REQUIRED BY FLORIDA STATUTE 553.80(2)(B).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2016-04-14 Cont ID  
Sent By jgomez Date 2016-04-14 Time 14:17 Rev Time 0.00
Received By jgomez Date 2016-04-14 Time 14:17 Sent To  
Notes
2016-04-14 14:19:4604/14/16 RECEIVED AND RESPONDED E-MAIL TO MICHAEL
 BASSFORD P.E. REGARDING THE CALCULATIONS FOR THE
 EQUIPMENT SIZING.
  
 GOOD AFTERNOON MR. BASSFORD,
 DO YOU REMEMBER THAT I TOLD YOU THAT HE CODE REQUIRES
 THE CALCULATIONS TO BE DONE BASED ON THE INTERIOR
 DESIGN TEMPERATURES OF 75 DEGREES MINIMUM FOR COOLING
 AND 72 DEGREES MAXIMUM FOR HEATING AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). THE CALCULATIONS THAT YOU SUBMITTED DON'T SEEM
 TO COMPLY WITH THIS INTERIOR DESIGN TEMPERATURES.
  
 SINCERELY,
 JULIO GOMEZ
  
  
 ORIGINAL COMMENTS BELOW:
  
 RESIDENTIAL (R3) ALTERATION THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
 1- EQUIPMENT CAPACITY CAN NOT BE MORE THAN 1.15 TIMES
 THE CALCULATED LOAD. SEC. R403.6.1.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS
 SUBMITTED SHOW A TOTAL CONDITIONING LOAD OF 21454
 BTU/HR. FRONT PAGE OF CALCULATIONS SUBMITTED CALL FOR
 2.5 TONS. THIS IS NOT ALLOWED. REVISED AS REQUIRED.
 REPEAT COMMENT. 2.5 TON UNIT IS MORE THAN 1.15 TIMES
 THE CALCULATED LOAD.
  
 2- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1.
 EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY ITEMS #2 ABOVE. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 REPEAT COMMENT.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-04-22 Cont ID  
Sent By jgomez Date 2016-03-29 Time 14:16 Rev Time 0.00
Received By jgomez Date 2016-03-29 Time 14:16 Sent To  
Notes
2016-04-07 15:40:0504/07/16 CALLED MECHANICAL ENGINEER TO GO OVER SIZING
 CALCULATIONS. EQUIPMENT IS OVERSIZED. WAITING FOR
 ENGINEER RESPONSE. JG.
  
 04/08/16 DISCUSSED EQUIPMENT SIZING WITH ENGINEER. HE
 WILL E-MAIL CALCULATIONS SHOWING THE INTERIOR
 TEMPERATURE DESIGN CRITERIA REQUIRED BY CODE.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-03-29 Cont ID  
Sent By jgomez Date 2016-03-29 Time 11:39 Rev Time 0.00
Received By jgomez Date 2016-03-29 Time 11:39 Sent To  
Notes
2016-03-29 11:40:43RESIDENTIAL (R3) ALTERATION THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
 1- EQUIPMENT CAPACITY CAN NOT BE MORE THAN 1.15 TIMES
 THE CALCULATED LOAD. SEC. R403.6.1.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS
 SUBMITTED SHOW A TOTAL CONDITIONING LOAD OF 21454
 BTU/HR. FRONT PAGE OF CALCULATIONS SUBMITTED CALL FOR
 2.5 TONS. THIS IS NOT ALLOWED. REVISED AS REQUIRED.
 REPEAT COMMENT. 2.5 TON UNIT IS MORE THAN 1.15 TIMES
 THE CALCULATED LOAD.
  
 2- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1.
 EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY ITEMS #2 ABOVE. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 REPEAT COMMENT.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-02 Cont ID  
Sent By jgomez Date 2016-03-02 Time 14:48 Rev Time 0.00
Received By jgomez Date 2016-03-02 Time 14:48 Sent To  
Notes
2016-03-02 15:11:10RESIDENTIAL (R3) ALTERATION SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC-5TH EDITION (2014)
  
 1- ENGINEER WHO SIGNED AND SEALED THE EQUIPMENT SIZING
 CALCULATIONS TO LEGIBLY PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY F.A.C. SEC. 61G15-23.002(2).
 REPEAT COMMENT.
  
 2- EQUIPMENT CAPACITY CAN NOT BE MORE THAN 1.15 TIMES
 THE CALCULATED LOAD. SEC. R403.6.1.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS
 SUBMITTED SHOW A TOTAL CONDITIONING LOAD OF 21454
 BTU/HR. FRONT PAGE OF CALCULATIONS SUBMITTED CALL FOR
 2.5 TONS. THIS IS NOT ALLOWED. REVISED AS REQUIRED.
 REPEAT COMMENT. 2.5 TON UNIT IS MORE THAN 1.15 TIMES
 THE CALCULATED LOAD.
  
 3- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1.
 EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY ITEMS #2 ABOVE. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 REPEAT COMMENT.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-23 Cont ID  
Sent By jgomez Date 2015-12-23 Time 10:31 Rev Time 0.00
Received By jgomez Date 2015-12-23 Time 10:31 Sent To E
Notes
2015-12-23 10:36:34RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014)
  
 1- ENGINEER WHO SIGNED AND SEALED THE EQUIPMENT SIZING
 CALCULATIONS TO PROVIDE ALL HIS INFORMATION AS REQUIRED
 BY F.A.C. SEC. 61G15-23.002 AND F.S. 471.
  
 2- ENGINEER WHO SIGNED AND SEALED THE EQUIPMENT SIZING
 CALCULATIONS TO PROVIDE ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY F.A.C. SEC. 61G15-23.002. AND F.S. 471.
  
 3- SEC. R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014) DOESN'T ALLOW ANY ADDITIONAL FACTORS
 THAT WILL AFFECT THE A/C EQUIPMENT SIZING. EQUIPMENT
 SIZING CALCULATIONS SUBMITTED ARE DONE BASED ON AN
 OCCUPANT LOAD OF 8 PEOPLE. 8 PEOPLE IS NOT THE TYPICAL
 NUMBER OF PEOPLE FOR A 2 BEDROOM HOUSE. ENERGY
 CALCULATIONS SUBMITTED ARE MORE REALISTIC AND SHOW 4
 OCCUPANTS. REVISE CALCULATIONS AS REQUIRED.
  
 4- EQUIPMENT CAPACITY CAN NOT BE MORE THAN 1.15 TIMES
 THE CALCULATED LOAD. SEC. R403.6.1.1 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS
 SUBMITTED SHOW A TOTAL CONDITIONING LOAD OF 21441
 BTU/HR. FRONT PAGE OF CALCULATIONS SUBMITTED CALL FOR
 2.4 TONS. THIS IS NOT ALLOWED. REVISED AS REQUIRED.
  
 5- REVISE EQUIPMENT LISTED ON THE MECHANICAL PLAN M.1.
 EQUIPMENT SIZE TO MATCH REVISED EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY ITEMS #3 AND #4 ABOVE. SEC.
 R403.6.1.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 6- SHEET M.1: TRANSFER DUCT SIZE SPECIFIED FOR BEDROOMS
 #1 AND #2 DOESN'T COMPLY WITH THE BALANCED RETURN AIR
 SEC. M 1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
 REVISE AS REQUIRED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 PLANS S WITH REVISED PLANS. SUBMIT OLD DRAWINGS FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-11-23 Cont ID  
Sent By tklarge Date 2015-11-23 Time 04:54 Rev Time 0.00
Received By tklarge Date 2015-11-23 Time 04:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2016-03-02 Cont ID  
Sent By jgomez Date 2016-03-02 Time 14:47 Rev Time 0.00
Received By jgomez Date 2016-03-02 Time 14:47 Sent To  
Notes
2016-03-02 14:47:51NO ROOFING WORK. ROOFING PERMIT APPLICATION WAS CHANGED
 TO PLUMBING. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By jgomez Date 2015-12-22 Time 17:11 Rev Time 0.00
Received By jgomez Date 2015-12-22 Time 17:08 Sent To  
Notes
2015-12-22 17:15:051- THERE IS A PERMIT APPLICATION FOR ROOFING
 SUB-PERMIT. PROVIDE PRODUCT APPROVAL FOR ROOF MATERIAL.
 CLEARLY IDENTIFY APPROVED ASSEMBLY TO BE INSTALLED.
 AND, PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).