2015-11-19 06:40:38 | 1) SHOW THE EHD NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. WPB AMENDMENTS |
| TO FBC SEC. 107.2.1. |
| 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE |
| FBC-2014 FUEL GAS CODE SEC. 304. |
| 3) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND |
| TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE |
| SEC. 502 THRU 505. |
| 4) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2, AND |
| 301.3. GAS APPLIANCES SHALL BE LISTED AND LABELED PER |
| SEC.301.3 OF 2014 FUEL GAS CODE |
| 5) THE 1/2 " GALVANIZED DROP TO THE SUMMER KITCHEN |
| SHALL BE 3/4". TABLE 402.4(2) FGC. |
| 6) THE 1/2" CSST TO THE SUMMER KITCHEN SHALL BE 3/4". |
| TABLE 402.4(15) FGC. |
| 7) THE 3/4" CSST DOWNSTREAM OF THE 1" GALVANIZED SHALL |
| BE 1". TABLE 402.4(15) FGC. |
| 8) THE PE TO THE POOL HEATER SHALL BE 1 1/2 ". TABLE |
| 402.4 (21) FGC. |
| 9) THE PLANS REFER TO TABLE 402.4 (2) FOR PE PIPE. THIS |
| TABLE IS FOR SCH. 40 METALLIC PIPE. INDICATE THE |
| CORRECT SIZING TABLES FOR ALL THE DIFFERENT TYPE OF |
| PIPE MATERIAL ON THE PLANS. |
| 10) IF ANY MP REGULATORS ARE GOING TO BE INSTALLED, |
| SHOW THE LOCATION ON THE PLANS AND LIST THE CORRECT |
| SIZING TABLE FOR THE SYSTEM. |
| 11) THE BTU LOAD OF THE APPLIANCES LISTED ON THE GAS |
| TABLE DOES NOT CORRELATE WITH THE BTU LOAD SHOWN ON THE |
| GAS RISER. CLARIFY. |
| |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |