2015-11-17 05:55:32 | 1) SUBMIT THE SIZING TABLE FROM THE 2014 FBC- FUEL GAS |
| FOR THE PE PIPE.WPB AMEND. TO FBC SEC. 107.3.5.3. |
| 2) INDICATE THE TYPE OF PIPE AND THE SIZE OF THE BRANCH |
| LINE TO THE TANKLESS WATER HEATER BY THE KITCHEN AND |
| ALSO FOR THE POOL HEATER. WPB AMEND. TO FBC SEC. |
| 107.3.5.3. |
| 3) INDICATE THE LENGTH OF THE SECTION OF PE PIPE TO THE |
| TANKLESS WATER HEATER BY THE KITCHEN. WPB AMEND. TO FBC |
| SEC. 107.3.5.3. |
| 4) SHOW THE CORRESPONDING EHD FOR THE PIPE SIZES OF THE |
| CSST.REFER TO TABLE 402.4 (15) OF THE 2014 FGC. |
| 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL |
| GAS EQUIPMENT SHOWING IT IS LISTED AND LABELED PER 2014 |
| FGC SEC. 301.3. |
| 6) 2014 FBC-ENERGY ? SEC. R403.9.1.1 ? ALL GAS AND SPA |
| HEATERS SHALL HAVE A MINIMUM THERMAL EFFICIENCY OF 82 % |
| FOR HEATERS MANUFACTURED ON OR AFTER APRIL 16, 2013 |
| WHEN TESTED IN ACCORDANCE WITH ANSI Z 21.56. POOL |
| HEATERS FIRED BY NATURAL OR LP GAS SHALL NOT HAVE |
| CONTINUOUSLY BURNING PILOT LIGHTS. THE SUBMITTED |
| SPECIFICATIONS SHALL SHOW PROOF OF COMPLIANCE. |
| 7) THE DEVELOPED LENGTH FO THE 2 PSI SYSTEM IS 127 |
| FEET, NOT 122 FEET WHICH MEANS THE NEXT ROW FOR THE |
| LENGTH TO BE USED FOR SIZING THIS LINE IS 150 FT. THE 5 |
| FEET FROM THE METER DOES NOT APPEAR TO HAVE BEEN |
| INCLUDED. THIS MEANS THE 3/4 " PE PIPE UP TO THE FIRST |
| BRANCH TO THE TWH, COOKTOP & DRYER IS UNDRSIZED AND |
| NEEDS TO BE 1 INCH IN SIZE. PER TABLE 402.4 (22) THE |
| MAXIMUM BTU LOAD ON 3/4" PIPE AT 150 FEET IS 860 BTU'S |
| AND THE TOTAL ON THIS LINE IS 871 BTU'S. |
| 8) THE MANUFACTURER'S INSTALLATION INSTRUCTIONS SHALL |
| BE AVAILABLE ON THE JOBSITE AT THE TIME OF INSPECTION. |
| 2014 FBC-FUEL GAS SEC.305.1. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |
| |
| |
2015-11-16 15:57:30 | ROUTED TO PLUMB <5K |