Plan Review Details - Permit 15110637
Plan Review Stops For Permit 15110637
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-24 Cont ID  
Sent By jwitmer Date 2015-11-24 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2015-11-24 Time 07:54 Sent To  
Notes
2015-11-24 09:08:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110637
 ADD: 325 CLEMATIS ST. 1ST & 2ND FLOOR ALTERATIONS.
 CONT: MAC ENTERPRISES
 TEL: 561-236-3627
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: TUES. NOV. 24/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET T.1 :
 1A) THE COVERSHEET NOR DOES THE LIFE SAFETY PLAN
 INDICATE TO WHAT CODES THIS PROJECT WAS DESIGNED TOO?
 THE 2014 FBC FAMILY OF CODES WAS ADOPTED STATEWIDE ON
 JUNE 30/ 2015.
  
 1B) UNDER THE 2014 FL. EXISITING BUILDING CODE THE
 DESIGNER OF RECORD HAS NOT DECLARED UNDER WHICH
 COMPLIANCE METHOD THE PLANS WERE DEVELOPED. 2014 FL.
 EXISTING BUILDING CODE 301.1.
  
 1C) THE COVERSHEET INDICATES UNDER A NOTE SPRINKLERS
 NOT APPLICABLE, I TAKE IT THIS BUILDING IS NOT FIRE
 SPRINKLERED NOR IS IT PLANNED TO BE IN THIS SCOPE OF
 WORK.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 1D) THE COVERSHEET INDICATES THE 1ST FLOOR A TO BE A
 FUTURE 1ST FLOOR BUSINESS AND 2ND FLOOR FUTURE ASSEMBLY
 OCCUPANCY. TYPE OF ASSEMBLY OCCUPANCY A1, A2 OR A3 IS
 UNKNOWN. PLEASE REVIEW THE 2014 FBC-B TABLE 503 WILL
 NOT ALLOW ANY ASSEMBLY OCCUPANCY ON THE 2ND FLOOR IN A
 BUILDING TYPE VB-UNSPRINKLERED. THE OTHER ISSUE IS THE
 ALLOWABLE AREA FOR AN ASSEMBLY OCCUPANCY IN A TYPE VB
 UNSPRINKLERED BUILDING IS OVER THE ALLOWABLE AREA,
 AGAIN SEE TABLE 503.FBC-B .
  
 1E) THE COVERSHEET VERSES THE LIFE SAFETY SHEET LS.1.
 THE QUESTION IS THE BUSINESS AND ASSEMBLY OCCUPANCIES
 ON THE COVER SHEET REVERSED TO WHAT FLOOR THEY ARE
 LOCATED? LS.1 APPEARS ON THE 1ST FLOOR TO HAVE A FRONT
 THAT OPENS ONTO CLEMATIS ST. THAT WOULD BE MORE SUITED
 FOR THE ASSEMBLY OCCUPANCY. IF SO PLEASE PROVIDE THE
 LEASABLE SQUARE FOOT AREA FOR THE TENANT SPACE. THE
 OTHER ISSUE THAT NEEDS ADDITIONAL INFORMATION IS THE
 MEZZANINE, THE PLANS SHEET A1 INDICATE THAT THE
 MEZZANINE IS USED FOR MECHANICAL ROOM OR IS THE
 MECHANICAL ROOM LOCATED ABOVE THE MEZZANINE ROOM? AND
 DOES THE MECHANICAL SYSTEM OPERATE FOR THE WHOLE
 BUILDING?
  
 1F) DISCREPANCY IN PLANS THE COVERSHEET INDICATES THE
 2ND FLOOR AS AN ASSEMBLY OCCUPANCY WHEREAS SHEET S-1.1
 THE 2ND FLOOR STRUCTURAL SHEET INDICATES THE 2ND FLOOR
 LIVE LOAD AS 80 LBS. FBC-B TABLE 1607.1 LIVE LOADS FOR
 ASSEMBLY MOVABLE SEATS IS 100 LBS. WHEREAS OFFICE
 CORRIDORS IS 80 LBS./ PSF.
  
 1G) THE COVERSHEET T.1 DOES NOT INDICATE IF THE 2
 FLOORS ARE GOING TO BE UNDER THE CONTROL OF A SINGLE
 TENANT OR IF THERE ARE GOING TO BE (2) SEPERATE TENANTS
 THAT WILL SHARE BACK OF HOUSE RESTROOMS AND OTHER
 COMMON ELEMENTS? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED FOR A THOROUGH REVIEW.
  
 1H) NEITHER THE COVERSHEET T.1 NOR LS.1 SHOW PROPOSED
 OCCUPANT LOADS FOR EACH FLOOR NOR DOES THE STAIRWELLS
 AND DOORS SHOW THE OCCUPANT LOAD ALLOWABLE OCCUPANT
 LOAD PER FBC-B 1005.3.1 STAIRWAYS A FACTOR OF 0.3 AND
 1005.3.2 OTHER EGRESS COMPONENTS A FACTOR OF 0.2.
  
 1I) THE COVERSHEET T.1 NOR THE LS.1 INDICATE COMPLIANCE
 WITH HORIZONTAL OCCUPANCY SEPARATION 2014 FBC-B
 707.3.10 & TABLE 707.3.10.
  
 2) SHEET A.1 BACK OF HOUSE WHAT APPEARS TO BE COMMON
 AREAS TO BOTH TENANTS. PLEASE PROVIDE A CUT SECTION
 THROUGH THE MEZZANINE AREA NORTH TO SOUTH THERE ARE A
 LOT OF QUESTIONS IN REGARDS TO THIS AREA.
  
 2A) THE REAR STAIRS, IT IS HARD TO TELL IF THIS STAIR
 IS BEING DESIGNED AS A ENCLOSED STAIR OR IF THE
 DESIGNER IS TRYING TO VIEW THIS STAIR AS A EXIT ACCESS
 STAIRWELL (FBC-B 1009.3 & 1016.3.1) OR AS A RATED EXIT
 STAIR ( 1022.2). IF DESIGNED AS A EXIT ACCESS STAIR
 TRAVEL DISTANCE NEEDS TO BE IN CONFORMANCE WITH FBC-B
 1016.3.
  
 2B) THE REAR STAIR WALL RATING IS CLEARLY SHOWN ON THE
 2ND FLOOR AS DARKER AROUND THE 2ND FLOOR CORRIDOR AND
 LIGHTER IN THE SOUTH WALL OF THE STAIRWELL. ON THE 1ST
 FLOOR THERE APPEARS TO BE NO RATING THAT WOULD SEPARATE
 THE STAIRWELL FROM THE 1ST FLOOR TENANT. FBC-B 1022.2).
  
 2C) !ST FLOOR BACK OF HOUSE, IF THE REAR STAIR IS TO BE
 CONSIDERED A EXIT STAIR (1 HOUR RATED) THEN 3 THINGS
 NEED TO HAPPEN:
  
 2C)(1) THE REAR EXIT WILL LEAD INTO A EXIT PASSAGE WAY
 AND TO THE EXIT DOOR. BETWEEN THE EXIT STAIR WELL AND
 EXIT PASSAGE WAY SECTION FBC-B 1022.3.1 EXTENSION. THE
 FIRE-RESISTANCE RATING SHALL BE AT LEAST EQUAL TO THAT
 REQUIRED FOR THE INTERIOR EXIT STAIRWAY AND RAMP. A
 FIRE DOOR ASSEMBLY COMPLYING WITH SECTION 716.5 SHALL
 BE INSTALLED IN THE FIRE BARRIER TO PROVIDE A MEANS OF
 EGRESS FROM THE INTERIOR EXIT STAIRWAY AND RAMP TO THE
 EXIT PASSAGEWAY. OPENINGS IN THE FIRE BARRIER OTHER
 THAN THE FIRE DOOR ASSEMBLY ARE PROHIBITED.
 PENETRATIONS OF THE FIRE BARRIER ARE PROHIBITED.
  
 2C)(2) THE EXIT PASSAGEWAY WILL NEED TO BE SEPARATED
 FROM THE ELEVATOR AND REMOVAL OF THE HOUSE PANELS.
 1023.5 OPENINGS AND PENETRATIONS.
 EXIT PASSAGEWAY OPENING PROTECTIVES SHALL BE IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 716. EXCEPT
 AS PERMITTED IN SECTION 402.8.7, OPENINGS IN EXIT
 PASSAGEWAYS OTHER THAN EXTERIOR OPENINGS SHALL BE
 LIMITED TO THOSE NECESSARY FOR EXIT ACCESS TO THE EXIT
 PASSAGEWAY FROM NORMALLY OCCUPIED SPACES AND FOR EGRESS
 FROM THE EXIT PASSAGEWAY. WHERE AN INTERIOR EXIT
 STAIRWAY OR RAMP IS EXTENDED TO AN EXIT DISCHARGE OR A
 PUBLIC WAY BY AN EXIT PASSAGEWAY, THE EXIT PASSAGEWAY
 SHALL ALSO COMPLY WITH SECTION 1022.3.1. ELEVATORS
 SHALL NOT OPEN INTO AN EXIT PASSAGEWAY.
  
 1023.6 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 PASSAGEWAY ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT PASSAGEWAY AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010M2). SUCH PENETRATIONS SHALL BE PROTECTED
 IN ACCORDANCE WITH SECTION 714. THERE SHALL BE NO
 PENETRATIONS OR COMMUNICATING OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT PASSAGEWAYS.
  
 2C)(3) THE 3RD ISSUE IS THERE IS A COLUMN LOCATED IN
 THE EXIT PASSAGE WAY OR EXIT ACCESS STAIRWELL AND
 MEZZANINE ABOVE. PLEASE PROVIDE THE CLEAR HEIGHT FROM
 THE BOTTOM OF THE MEZZANINE LEVEL TO THE TOP OF THE 1ST
 FLOOR FINISH FLOOR. SEE FBC-B 1003.2 & 1003.3.1
 HEADROOM.
  
 3) THE MEZZANINE LEVEL IS NOT CLEAR AS TO WHERE THE
 WALL LINE IS FOR THE MEZZANINE NONE ARE SHOWN. THE
 OTHER ISSUE THAT IS UNCLEAR ON THE 2ND FLOOR PLAN
 VIEWING THE MEZZANINE LEVEL THE WORDS STATE, INDICATES
 MEZZANINE ABOVE, IS THERE 2 MEZZANINES ONE ON THE 1ST
 FLOOR AND 1 ON THE 2ND FLOOR? 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THIS AREA MAYNOT BE AN ACTUAL
 MEZZANINE BY DEFINITION BUT A 505.3 EQUIPMENT
 PLATFORMS.
  
 EQUIPMENT PLATFORMS IN BUILDINGS SHALL NOT BE
 CONSIDERED AS A PORTION OF THE FLOOR BELOW. SUCH
 EQUIPMENT PLATFORMS SHALL NOT CONTRIBUTE TO EITHER THE
 BUILDING AREA OR THE NUMBER OF STORIES AS REGULATED BY
 SECTION 503.1. THE AREA OF THE EQUIPMENT PLATFORM SHALL
 NOT BE INCLUDED IN DETERMINING THE FIRE AREA IN
 ACCORDANCE WITH SECTION 903. EQUIPMENT PLATFORMS SHALL
 NOT BE A PART OF ANY MEZZANINE AND SUCH PLATFORMS AND
 THE WALKWAYS, STAIRS, ALTERNATING TREAD DEVICES AND
 LADDERS PROVIDING ACCESS TO AN EQUIPMENT PLATFORM SHALL
 NOT SERVE AS A PART OF THE MEANS OF EGRESS FROM THE
 BUILDING.
  
 505.3.1 AREA LIMITATION.
 THE AGGREGATE AREA OF ALL EQUIPMENT PLATFORMS WITHIN A
 ROOM SHALL BE NOT GREATER THAN TWO-THIRDS OF THE AREA
 OF THE ROOM IN WHICH THEY ARE LOCATED. WHERE AN
 EQUIPMENT PLATFORM IS LOCATED IN THE SAME ROOM AS A
 MEZZANINE, THE AREA OF THE MEZZANINE SHALL BE
 DETERMINED BY SECTION 505.2.1 AND THE COMBINED
 AGGREGATE AREA OF THE EQUIPMENT PLATFORMS AND
 MEZZANINES SHALL BE NOT GREATER THAN TWO-THIRDS OF THE
 ROOM IN WHICH THEY ARE LOCATED.
  
 4) THE STRUCTURAL SHEETS SHOW A SCOPE OF WORK THAT WILL
 REQUIRE A RESIDENT INSPECTOR ON THIS PROJECT. 2014
 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.9 OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109. HE/SHE MAY ACCEPT REPORTS OF INSPECTORS
 OF RECOGNIZED INSPECTION SERVICES, PROVIDED THAT AFTER
 INVESTIGATION HE/SHE IS SATISFIED AS TO THEIR
 QUALIFICATIONS AND RELIABILITY. A CERTIFICATE CALLED
 FOR BY ANY PROVISION OF THE TECHNICAL CODES SHALL NOT
 BE BASED ON SUCH REPORTS UNLESS THE SAME ARE IN WRITING
 AND CERTIFIED BY A RESPONSIBLE OFFICER OF SUCH SERVICE.
 THE BUILDING OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY
 AN INSPECTION SERVICE IN THE FOLLOWING INSTANCES:
  
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F ?C) IN EXCESS OF 3000
 POUNDS PER SQUARE INCH
 4. FOR HELICAL PILE
 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE
 FOOT
 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT
 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR
 METHODS OF CONSTRUCTION
  
 4A) RESIDENT INSPECTOR FORMS MUST BE SIGNED BY ALL
 PARTIES NOTARIZED AND RETURNED TO THE BUILDING
 DEPARTMENT.
 FORMS WERE E-MAILED TO: [email protected]
 TUES. NOV. 24/ 2015 02:40 PM.
  
 4B) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 4C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 4D) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE
 PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR
 THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 4E) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS
  
 5) TO DATE NO SOILS REPORTS WERE SUBMITTED FOR THIS
 PROJECT. SHEET S-4.0 NOTE 4 INDICATES THE GEOTECHNICAL
 ENGINEER SHALL INSPECT AND REQUIRE TESTING AS NECESSARY
 TO ASSURE THAT THE FOUNDATION PILES ARE INSTALLED IN
 ACCORDANCE WITH THEIR SPECIFICATIONS AND REPORT ANY
 DEVIATIONS TO THE ENGINEER.
 1804.1 EXCAVATION NEAR FOUNDATIONS. EXCAVATION FOR ANY
 PURPOSE SHALL NOT REMOVE LATERAL SUPPORT FROM ANY
 FOUNDATION WITHOUT FIRST UNDERPINNING OR PROTECTING THE
 FOUNDATION AGAINST SETTLEMENT OR LATERAL TRANSLATION.
  
 6) SHEET S-1.0 SHOWS A HELICAL PIER BEING INSTALLED
 UNDER THE FOUNDATION IN A DOORWAY. THE INSTALLATION OF
 THE HELICAL PIER WILL CREATE A POINT LOAD THAT WILL
 TRANSFER UPWARDS ON A 45 DEGREE ANGLE, WILL THIS LOAD
 TRANSFER INTO THE COLUMNS OR WILL IT TRANSFER THROUGH
 THE FOUNDATION & BLOCK WORK AND CRACK THE FLOOR IN THE
 DOOR OPENING? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 7) SHEET S-1.0 IN THE SOUTHEAST CORNER OF THE BUILDING
 THERE IS A NOTE PRE-ENGINEERED STAIRS BY OTHERS, THERE
 IS NO DESIGN CRITERIA FOR LIVE LOADS (FBC-B TABLE
 1604.5) TO BE CARRIED NOR DOE THE NOTE INDICATE CLOSED
 RISERS FBC-B 1009.7.5.
  
 8) NONE OF THE STRUCTURAL SHEETS,NEITHER ARCHITECTURAL
 SHEETS NOR THE MECHANICAL SHEETS SHOW ROOF TOP ACCESS
 FOR THE MECHANICAL EQUIPMENT. PLEASE SHOW COMPLIANCE
 WITH:
 FBC-B 1509.6.4 EQUIPMENT AND APPLIANCES ON ROOFS OR
 ELEVATED STRUCTURES. WHERE EQUIPMENT AND APPLIANCES
 REQUIRING ACCESS ARE INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 MM),
 SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED
 MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM
 GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES?
 LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES (762
 MM) HIGH OR WALKING ON ROOFS HAVING A SLOPE GREATER
 THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS
  
 9A) ROOF TOP MECHANICAL EQUIPMENT MAY REQUIRE SCREENING
 AS A ZONING REQUIREMENT. ? 1509.6 MECHANICAL EQUIPMENT
 SCREENS.
 MECHANICAL EQUIPMENT SCREENS SHALL BE CONSTRUCTED OF
 THE MATERIALS SPECIFIED FOR THE EXTERIOR WALLS IN
 ACCORDANCE WITH THE TYPE OF CONSTRUCTION OF THE
 BUILDING. WHERE THE FIRE SEPARATION DISTANCE IS GREATER
 THAN 5 FEET (1524 MM), MECHANICAL EQUIPMENT SCREENS
 SHALL NOT BE REQUIRED TO COMPLY WITH THE
 FIRE-RESISTANCE RATING REQUIREMENTS.
  
 9B) IF MECHANICAL SCREENS ARE REQUIRED THEN THE
 STRUCTURAL MEMBERS WILL BE REQUIRED TO BE ATTACHED TO
 THE ROOF FRAMING TO BE PART OF THE MWFRS (MAIN WIND
 FORCE RESISTING SYSTEM).
  
 10) ROOF TOP MECHANICAL EQUIPMENT WILL NEED TO SHOW
 COMPLIANCE WITH: 2014 FBC- ? M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 11) NOTE DEPENDING ON THE 2ND FLOOR EXITING IS TO BE
 DEFINED IF IT IS A EXIT ACCESS STAIR OR AS A VERTICAL
 EXIT AND EXIT PASSAGE WAY FBC-B 1022.5 PENETRATIONS
 ONLY ALLOWS IN EXITS EQUIPMENT, DUCTWORK NECESSARY FOR
 INDEPENDENT VENTILATION OR PRESSURIZATION.
  
 12) SHEET S-4.0 PROVIDES THE WIND DESIGN CRITERIA, THE
 MEAN ROOF HEIGHT IS NOT PROVIDED NEITHER IS THE
 PRESSURES FOR COMPONENTS AND CLADDING.
 FBC-B 2014 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR
 HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 FBC-B 2014 FBC-B 1603.1.4 WIND DESIGN DATA. (5) VASD
 POSITIVE AND NEGATIVE PRESSURES.
  
 13) PRODUCT APPROVALS: COMPONENTS & CLADDING. 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 14) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 15) EITHER THE CONTRACTOR OR THE DESIGNER OF RECORD MAY
 REQUEST THE PRODUCT APPROVALS FOR COMPONENTS AND
 CLADDING TO BE DEFERRED. 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 16) CHANGE OF OCCUPANCY ASSEMBLY: IMPACT FEES BEFORE A
 PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-23 Cont ID  
Sent By mvaldes Date 2015-12-23 Time 10:03 Rev Time 0.00
Received By mvaldes Date 2015-12-23 Time 10:03 Sent To  
Notes
2015-12-23 10:25:151ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 PLEASE FOLLOW UP ON BUILDING AND FIRE COMMENTS IN ORDER
 TO COMPLY WITH THE ELECTRICAL REVIEW.
 PROVIDE EXISTING INFORMATION OF RISER DIAGRAM AND LOAD
 CALCS , WIRE SIZES , INSULATION TYPE , CONDUIT SIZES ,
 AND ETC.
 PROVIDE A NARRATIVE DETAILED SCOPE OF WORK. WPB FBC
 107.2.1
 AIC CALCULATIONS REQUIRED FOR 400 AMP DISCONNECT TO
 HOUSE PANELS. ( CURRENT LIMITING FUSES ? )
  
 110.10 CIRCUIT IMPEDANCE, SHORT-CIRCUIT CURRENT
 RATINGS,
 AND OTHER CHARACTERISTICS. THE OVERCURRENT PROTECTIVE
 DEVICES, THE TOTAL IMPEDANCE, THE EQUIPMENT
 SHORTCIRCUIT
 CURRENT RATINGS, AND OTHER CHARACTERISTICS OF THE
 CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND
 COORDINATED TO
 PERMIT THE CIRCUIT PROTECTIVE DEVICES USED TO CLEAR A
 FAULT TO
 DO SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL
 EQUIPMENT
 OF THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE
 EITHER BETWEEN
 TWO OR MORE OF THE CIRCUIT CONDUCTORS OR BETWEEN ANY
 CIRCUIT CONDUCTOR AND THE EQUIPMENT GROUNDING
 CONDUCTOR(
 S) PERMITTED IN 250.118. LISTED EQUIPMENT APPLIED IN
 ACCORDANCE WITH THEIR LISTING SHALL BE CONSIDERED TO
 MEET THE
 REQUIREMENTS OF THIS SECTION.
  
 110.15 HIGH-LEG MARKING. ON A 4-WIRE, DELTA-CONNECTED
 SYSTEM WHERE THE MIDPOINT OF ONE PHASE WINDING IS
 GROUNDED, ONLY THE CONDUCTOR OR BUSBAR HAVING THE
 HIGHER
 PHASE VOLTAGE TO GROUND SHALL BE DURABLY AND
 PERMANENTLY
 MARKED BY AN OUTER FINISH THAT IS ORANGE IN COLOR OR BY
 OTHER
 EFFECTIVE MEANS. SUCH IDENTIFICATION SHALL BE PLACED AT
 EACH
 POINT ON THE SYSTEM WHERE A CONNECTION IS MADE IF THE
 GROUNDED CONDUCTOR IS ALSO PRESENT.
  
 PLEASE PROVIDE ADEQUATE WIRE GUTTER SIZES ACCORDING TO
 NEC
  
 (A) DEFLECTED INSULATED CONDUCTORS. WHERE INSULATED
 CONDUCTORS
 ARE DEFLECTED WITHIN AN AUXILIARY GUTTER, EITHER AT THE
 ENDS OR WHERE CONDUITS, FITTINGS, OR OTHER RACEWAYS OR
 CABLES
 ENTER OR LEAVE THE GUTTER, OR WHERE THE DIRECTION OF
 THE GUTTER IS
 DEFLECTED GREATER THAN 30 DEGREES, DIMENSIONS
 CORRESPONDING
 TO ONE WIRE PER TERMINAL IN TABLE 312.6(A) SHALL APPLY.
 (B) AUXILIARY GUTTERS USED AS PULL BOXES. WHERE
 INSULATED
 CONDUCTORS 4 AWG OR LARGER ARE PULLED THROUGH AN
 AUXILIARY
 GUTTER, THE DISTANCE BETWEEN RACEWAY AND CABLE ENTRIES
 ENCLOSING THE SAME CONDUCTOR SHALL NOT BE LESS THAN
 THAT REQUIRED
 IN 314.28(A)(1) FOR STRAIGHT PULLS AND 314.28(A)(2) FOR
 ANGLE PULLS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-19 Cont ID  
Sent By pleduc Date 2015-11-20 Time   Rev Time 0.00
Received By pleduc Date 2015-11-19 Time 07:54 Sent To  
Notes
2015-11-19 16:59:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FORLLOWING COMMENTS:
  
 1. SHEET T 1 - PROJECT DATA INDICATES A PROPOSED
 BUSINESS AND ASSEMBLY OCCUPANCY. IS THE PROPOSED A
 SINGLE 2 STORY OCCUPANCY OR TWO INDIVIDUAL OCCUPANCIES?
 IF SO IT IS A MIXED OCCUPANCY OR SEPARATED OCCUPANCY.
  
 2. SHEET LS 1 - NO OCCUPANCY LOADS ARE INDICATED.
  
 BASED ON THIS REVIEW A FIRE SPRINKLER SYSTEM IS
 REQUIRED.
  
 3. SHEET LS 1 - THE INDICATED EXIT SEPARATION ON THE
 2ND FLOOR IS NOT CODE COMPLAINT. PER NFPA 101, CHAPTER
 7, 7.5.1.3.2, WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE REQUIRED, THEY SHALL BE LOCATED AT A
 DISTANCE FROM ONE ANOTHER NOT LESS THAN ONE-HALF THE
 LENGTH OF THE MAXIMUM OVERALL DIAGONAL DIMENSION OF THE
 BUILDING OR AREA TO BE SERVED, MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESSES, OR EXIT DISCHARGES.
  
 4. SHEETS A 1 - A 2 - NO DETAIL OF THE MEZZANINE IS
 PROVIDED.
  
 NFPA 101 CHAPTER 8, 8.6.10.2.1 THE AGGREGATE AREA OF
 MEZZANINES LOCATED WITHIN A ROOM, OTHER THAN THOSE
 LOCATED IN SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES,
 SHALL NOT EXCEED ONE-THIRD THE OPEN AREA OF THE ROOM IN
 WHICH THE MEZZANINES ARE LOCATED. ENCLOSED SPACE SHALL
 NOT BE INCLUDED IN A DETERMINATION OF THE SIZE OF THE
 ROOM IN WHICH THE MEZZANINE IS LOCATED.
 8.6.10.2.3 FOR PURPOSES OF DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AGGREGATE AREA OF THE MEZZANINE
 SHALL NOT BE INCLUDED IN THE AREA OF THE ROOM.
  
 THE PROPOSED MEZZANINE IS NOT APPROVED.
  
 5. FIRE FIGHTER'S EMERGENCY OPERATIONS. ALL NEW
 ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER'S EMERGENCY
 OPERATIONS REQUIREMENTS OF ASME A17.1/CSA B44, SAFETY
 CODE FOR ELEVATORS.
  
 6. SHEET LS 1 - THE EXIT WIDTH AT THE FRONT DOOR IS NOT
 ADAQUATE FOR THE OCCUPANCY LOADS.
  
 7. SHEET A 1 - THERE APPEARS TO BE A COLUMN SUPPORTING
 THE MEZZANINE IN THE EXIT PATH FROM THE 2ND FLOOR
 STAIRWAY. NO DETAIL IS PROVIDED FOR THIS COLUMN, AND/OR
 HEADROOM DIMENSIONS AND/OR FIRE RATING.
  
 8. SHEET E 3 - SHOULD THE PROPOSED USE BE SEPARATE INTO
 TWO OCCUPANCIES, THE FIRE ALARMS SHALL BE SEPARATED.
  
 9. SHEET LS 1 - THE EXIT ARROW INDICATORS AT THE FIRST
 FLOOR ELEVATOR LOBBY POINT TO INCORRECT DIRECTION;
 TOWARDS THE UP STAIRWAY, PLEASE CORRECT.
  
 10. SHEET A 1 - NO DETAIL IS INDICATED FOR THE 1ST
 FLOOR FIRE RATED WALL AS IT INTERACTS WITH THE
 MEZZANINE. IS THERE A FIRE RATING FOR THE EXPOSED AREAS
 OF THE STRUCTURE OF THE MEZZANINE?
  
 11. SHEET A 5 - DOORS 103 AND 202 REQUIRE PANIC
 HARDWARE.
  
 12. SHEET A 1 - THE ELEVATOR LOBBY SHALL BE SEPARATED
 FROM THE EXIT COORIDOR ON BOTH FLOOR LEVEL.
  
 13. SHEET A 3 - NO DETAIL IS PROVIDED FOR THE REAR EXIT
 STAIRWAY.
  
 14. SHEET A 1 - NOR FIRE RATING IS INDICATED FOR THE
 THE FLOORING.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-23 Cont ID  
Sent By cpuell Date 2015-12-23 Time 12:01 Rev Time 0.00
Received By cpuell Date 2015-11-16 Time 13:24 Sent To  
Notes
2015-11-16 13:26:40C02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By ccole Date 2015-11-23 Time 16:24 Rev Time 0.00
Received By ccole Date 2015-11-20 Time 16:23 Sent To  
Notes
2015-11-23 07:44:421ST REVIEW 2014 MECHANICAL
 PERMIT #15110637
 11/23/15
  
 1) IN ACCORDANCE WITH SECTION 202 FBC-14 ENERGY
 CONSERVATION, THE PROPOSED PROJECT IS DEFINED AS A
 "RENOVATION" AND SHALL BE IN COMPLIANCE WITH THE
 CURRENT FL. ENERGY CODE. PLEASE SEE SECTION C101.4.3
 AND SUBMIT ENERGY CALCULATIONS PER SECTION C101.5.1.
 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE VENTILATION CALCULATIONS- SEE ASHRAE 62
 INDOOR AIR QUALITY PROCEDURE AND TABLE 403.3 FBC-14
 MECHANICAL. INDICATE ON THE PLAN THE REQUIRED CFM'S OF
 OUTSIDE AIR FOR ALL ROOMS AND SPACES, AND THE AMOUNT OF
 O/A CFM'S PROVIDED BY THE EXISTING AC SYSTEMS. PROVIDE
 DETAILS AND DRAWINGS FOR ALL REQUIRED UPGRADES IN THE
 EVENT THE EXISTING SYSTEMS ARE NOT CAPABLE OF
 SUPPORTING THE NEW OCCUPANCIES. PLEASE NOTE REFERENCE
 IS MADE TO DOCTOR'S OFFICES ON SHEET M2, HOWEVER THE
 PLANS DON'T INDICATE ANY DOCTOR'S OFFICES.
 3) PROVIDE AN EQUIPMENT SCHEDULE FOR THE EXISTING AC
 SYSTEMS ON THE PLAN, AND CLARIFY IF THEY ARE EQUIPPED
 WITH DUCT SMOKE DETECTORS. PROVIDE A SEQUENCE OF
 OPERATION FOR THE DEVICES IF APPLICABLE.
 4) INDICATE ON THE PLAN HOW ACCESS TO THE AC AIR
 HANDLERS WILL BE PROVIDED FOR SERVICE, REPAIR, OR
 REPLACEMENT- SEE SECTION 306.1 FBC-14 MECHANICAL.
 5) PROVIDE A DETAIL ON THE PLAN FOR INSTALLATION OF THE
 FIRE DAMPERS PER MANUFACTURER'S SPECIFICATIONS, AND
 SUBMIT CUT SHEETS REVIEWED AND APPROVED BY THE ENGINEER
 OF RECORD. INDICATE HOW THE DAMPERS WILL BE ACTUATED-
 SEE SECTION 607.3.3, AND CLARIFY IF THEY WILL BE LINKED
 TO A FIRE ALARM SYSTEM.
 6) INDICATE ON THE PLANS HOW ACCESS TO THE FIRE DAMPERS
 FOR SERVICE AND MAINTRENANCE WILL BE PROVIDED, AND SHOW
 ACCESS DOOR LOCATIONS.
 7) REFER TO SECTION 3006.2 FBC-14 BUILDING CODE AND
 PROVIDE INDEPENDENT VENTILATION SYSTEMS FOR THE IT
 ROOMS IF SOLID STATE EQUIPMENT FOR THE ELEVATORS IS
 BEING HOUSED IN THOSE ADJACENT ROOMS.
 8) PROVIDE SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE
 DOWN OF THE NEW AC O/A INTAKE VENTILATOR, AND THE
 TOILET ROOM EXHAUST VENTILATOR ON THE ROOF. SUBMIT CUT
 SHEETS, AND NOA'S OR FL. PRODUCT APPROVALS FOR THE
 VENTILATORS REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD.
 9) PLEASE NOTE ADDITIONAL MECHANICAL COMMENTS MAY
 FOLLOW RESPONSES TO ALL BUILDING DEPARTMENT REVIEWS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-29 Cont ID  
Sent By tklarge Date 2015-11-29 Time 06:37 Rev Time 0.00
Received By tklarge Date 2015-11-29 Time 05:52 Sent To  
Notes
2015-11-29 06:04:231) INDICATE ON THE PLANS THE TYPE OF ASSEMBLY OCCUPANCY
 IN ACCCORDANCE WITH THE 2014 FBC SEC.303.
 2) INDICATE ON THE PLANS THE OCCUPANT LOAD FOR THE
 BUSINESS OCCUPANCY IN ACCORDANCE WITH 2014 FBC SEC.1004
 & TABLE 1004.1.2.
 3) THE MINIMUM NUMBER OF REQUIRED SANITARY FACILITIES
 CANNOT BE DETERMINED FOR EACH OCCUPANCY UNTIL THE
 OCCUPANT LOAD IS SUBMITTED FOR EACH OCCUPANCY.WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) SHT. A.5 - MOUNTING DIAGRAMS - THE HEIGHT OF THE
 GRAB BARS SHALL BE MEASURED TO THE TOP OF THE GRIPPING
 SURFACE PER THE 2014 FBC-ACCESSIBILITY SEC. 609.4.
 5) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7"-9" IN
 FRONT OF THE WATER CLOSET TO THE CCENTERLINE OF THE
 DISPENSER. 2014 FBC-ACCESSIBILITY SEC.604.7.
 6) SHT. P.1- SIZE ALL SECTIONS OF THE VENT SYSTEM. WPB
 AMEND. TO FBC SEC. 107.2.1.
 7) INDICATE THE LEVEL OF ALTERATION ON THE PLAN IN
 ACCORDANCE WITH THE 2014 FBC-EXISTING BUILDING CODE.
 8) INDICATE ON THE PLANS IF BOTH FLOORS WILL BE UNDER
 THE CONTROL OF ONE TENANT OR IF THERE WILL BE SEPARATE
 TENANTS IN THIS SPACE. WPB AMEND. TO FBC SEC. 107.2.1.
  
 NOTE: A THOROUGH AND COMPREHENSIVE PLUMBING PLAN REVIEW
 CCOULD NOT BE PERFORMED DUE TO THE LACK OF INFORMATION
 ON THE PLANS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-12-07 Cont ID  
Sent By aaponte Date 2015-12-07 Time 14:53 Rev Time 0.00
Received By aaponte Date 2015-12-07 Time 14:29 Sent To  
Notes
2015-12-07 15:07:021. PLEASE PROVIDE A SURVEY OF THE PROPERTY AND INDICATE
 THE LOCATION OF THE PROPERTY LINE ON THE FLOOR PLANS.
 2. PLEASE PROVIDE A DEMOLITION PLAN.
 3. WHAT IS THE PROPOSED USE OF THE SPACE? IF THE
 PROPOSED USE IS A RESTAURANT, PLEASE INDICATE THE
 LOCATION OF THE DUMPSTER.
 4. PROPOSED OUTDOOR PATIO DOES NOT COMPLY WITH THE
 SETBACK REQUIREMENTS.
 5. PLEASE INDICATE THE LOCATION OF THE PROPERTY LINE ON
 THE ELEVATIONS TO DETERMINE IF PROPOSED CANOPY
 ENCROACHES INTO THE PUBLIC ROW. MINIMU PROJECTION FOR A
 CANOPY IS 8 FEET.
 6. CANOPY ON 2ND FLOOR COULD BE CONSIDERED AN
 ARCHITECTURAL FEATURE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  
  