Plan Review Details - Permit 15110567
Plan Review Stops For Permit 15110567
Review Stop E ELECTRICAL
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mvaldes Date 2015-11-23 Time 11:12 Sent To  
Notes
2015-11-23 11:13:561ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 PHIL PETTY
 561-805-6742
 [email protected]
  
  
  
 (1) READILY ACCESSIBLE LOCATION. THE SERVICE
 DISCONNECTING
 MEANS SHALL BE INSTALLED AT A READILY ACCESSIBLE
 LOCATION
 EITHER OUTSIDE OF A BUILDING OR STRUCTURE OR INSIDE
 NEAREST THE
 POINT OF ENTRANCE OF THE SERVICE CONDUCTORS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2015-11-19 15:29:291ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6700
 [email protected]
  
  
  
 PLEASE SHOW DISCONNECTING MEANS ACCORDING TO NEC 230
 PLEASE SHOW INTERSYSTEM BONDING AND WATER BONDING PER
 NEC 250
 FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE
 LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.
 NEC 240.24 (A) & (B) PANELS SHALL BE LOCATED SUCH THAT
 OVER CURRENT DEVICES ARE ACCESSIBLE AND THAT OCCUPANTS
 SHALL HAVE ACCESS TO OCP DEVICES.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-23 Cont ID  
Sent By mvaldes Date 2015-11-23 Time 16:16 Rev Time 0.00
Received By mvaldes Date 2015-11-20 Time 10:46 Sent To  
Notes
2015-11-23 10:47:04RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-23 Cont ID  
Sent By mvaldes Date 2015-11-19 Time 15:26 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 15:21 Sent To  
Notes
2015-11-13 15:21:21ELEC -$5000