Plan Review Details - Permit 15110532
Plan Review Stops For Permit 15110532
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-01-25 Cont ID  
Sent By jwitmer Date 2016-01-25 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-01-25 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-08 Cont ID  
Sent By jwitmer Date 2016-01-08 Time 13:48 Rev Time 0.00
Received By jwitmer Date 2016-01-08 Time 06:27 Sent To  
Notes
2016-01-08 13:48:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110532
 ADD: 2302 PRESIDENTIAL WAY
 CONT: HEDRICK BROTHERS
 TEL: 561-689-8880
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: FRIDAY JAN. 08/ 2016
 ACTION: DENIED
  
 1) SEMI-COMPLIED. SITE PLAN SUBMITTED.
 1A) NEW COMMENT. THE SUBMITTED (2) SITE PLANS SHOW
 EITHER THE DELETION OR ADDITION OF PROPERTY LINES.
 THE SITE PLAN DATED 6/12/2012 SHOWS THE MODULAR
 BUILDING BEING SET WITHIN 5-0? OF THE PROPERTY LINE
 WHEREAS THE SITE PLAN DATED 8/15/2013 IT APPEARS THERE
 WAS EITHER A UNITY OF PROPERTY OR A REPLAT OF THIS
 AREA. PLEASE PROVIDE ADDITIONAL INFORMATION, IS THE
 INTERNAL ROAD TO THE SITE GOING TO HAVE ITS OWN NAME
 AND ADDRESS. BEFORE PERMIT ISSUANCE THE CITY WILL NEED
 TO ASSIGN ADDRESSES TO THE SITE. THE CITY CONTACT IS
 MIKE ORIO
 TEL: 561-494-1080
 E-MAIL: [email protected]
  
 1B) BOTH SITE PLANS LIST THE CLUBHOUSE STRUCTURE AS
 TEMPORARY, PLEASE PROVIDE THE DATES THIS STRUCTURE WILL
 BE OCCUPIED FOR USE. 108.1 GENERAL. THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR TEMPORARY
 STRUCTURES AND TEMPORARY USES. SUCH PERMITS SHALL BE
 LIMITED AS TO TIME OF SERVICE, BUT SHALL NOT BE
 PERMITTED FOR MORE THAN 6MONTHS. THE BUILDING OFFICIAL
 IS AUTHORIZED TO GRANT EXTENSIONS FOR DEMONSTRATED
 CAUSE.
 105.1 TIME LIMITATION. THE BUILDING OFFICIAL IS
 AUTHORIZED TO GRANT ONE OR MORE (2) EXTENSIONS OF TIME
 FOR ADDITIONAL PERIODS NOT EXCEEDING THREE MONTHS EACH.
 THE EXTENSION SHALL BE REQUESTED IN WRITING PRIOR TO
 THE ABANDONMENT DATE AND JUSTIFIABLE CAUSE
 DEMONSTRATED.
  
 2) THE MOD SPACE PLANS DO NOT HAVE A DCA STATE APPROVAL
 . SUBMITTED ARE LETTERS CONFIRMING THAT MODSPACE-MIAMI
 HAS BEEN ACCEPTED INTO THE MODULAR PROGRAM AND ARE
 CURRENT. LOST PLANS CAN BE SUBMITTED ?AS BUILT?
 PREPARED, SIGNED & SEALED BY A ARCHITECT.
  
 2A) THE ?AS BUILT? PLANS SHOW A OCCUPANCY OF A BUSINESS
 OCCUPANCY. PLEASE NOTE THE (2) SITE PLANS INDICATE THE
 USE OF THIS STRUCTURE IS LABELED AS A CLUBHOUSE, FOR
 THE SQUARE FEET OF THE BUILDING AND PROPOSED OCCUPANT
 LOAD OF AN A3 ASSEMBLY BUILDING THE MODULAR PLANS WOULD
 NEED TO BE RE-DESIGNED FOR OCCUPANT LOAD, FLOOR
 LOADING, ACCESSIBLE EGRESS PATH, ENERGY CALCULATIONS,
 PLUMBING AND MECHANICAL SYSTEMS. DISCREPANCY IN PLANS.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 2B) PLEASE PROVIDE A WRITTEN DOCUMENT WHO THE ARCHITECT
 OF RECORD WILL BE SINCE THE SUBMITTED SET OF PLANS HAS
 (3) DIFFERENT ARCHITECTURAL SHEETS WITHIN THE SET OF
 PLANS, AND WHO WILL BE TAKING RESPONSIBILITY OF
 COORDINATING THE PLANS AND NARRATIVE RESPONSES.
 61G1-23.015 RESPONSIBLE SUPERVISING CONTROL OVER
 ARCHITECTURAL PRACTICE OUTSIDE OF THE ARCHITECTS?
 OFFICE.
  
 2C) PLEASE SEE THE RANDALL STOFFTS SHEETS A001 & A101
 INDICATE THE PROPOSED CLUBHOUSE AS AN EXISTING
 STRUCTURE PLEASE CORRECT, UNDER THIS PERMIT BOTH THE
 PROPOSED WORK, CLUBHOUSE, LANDING, RAMP, STAIR HAND
 RAIL & GUARD RAIL WILL BE UNDER THIS PERMIT.
  
 2D) THE PLANS DESIGNED UNDER MODSPACE WILL NEED
 RE-EVALUATING IF THE A-3 ASSEMBLY (CLUBHOUSE/ COMMUNITY
 HALL) SINCE THE FLOOR LOADS WOULD NEED TO COMPLY WITH
 2014 FBC-B TABLE 1607.1(4) ASSEMBLY AREAS FOOTNOTE M.
  
 2E) DISCREPANCY IN PLANS. MODSPACE PLANS SHOWS 3 SETS
 OF DOORS WHEREAS RANDELL STOFFT PLANS ONLY SHOW 2
 DOORWAYS. DISCREPANCY IN PLANS.
  
 2F) IF THIS PROJECT IS TO BE CONSIDERED AN A3 OCCUPANCY
 AND THE OCCUPANT LOAD WOULD BE GREATER THAN 50 THERE
 WILL BE THE NEED FOR 2 ACCESSIBLE EXITS ? THE OVERALL
 DIAGONAL DISTANCE APART (NON-SPRINKLERED).
 PLEASE SEE 2014 FBC-ACCESSIBILITY CODE 207.1 ACCESSIBLE
 MEANS OF EGRESS SHALL COMPLY WITH THE 2003 IBC SECTION
 1007. 2003 IBC-B 1007.1. WHERE 2 OR MORE MEANS OF
 EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE PORTION OF THE SPACE SHALL BE SERVED BY NOT
 LESS THAN TWO ACCESSIBLE MEANS OF EGRESS.
  
 2G) MODSPACE COVERSHEET UNDER THE HEADING OF STRUCTURAL
 LOAD LIMITATION/ WIND DESIGN CRITERIA HAS THE VASD &
 VULT REVERSED. 146VULT/ 188 VASD MPH 107.2.1.3
 DISCREPANCY IN PLANS, CORRECT.
  
  
 3-5) COMPLIED. STORM SHUTTERS PERMIT # 15120406.
  
 6) DESIGN DOCUMENTS BY RANDELL STOIFT ARCHITECT FOR
 ACCESSIBLE STAIRS, RAMP AND LANDING:
  
 6A) COMPLIED
  
 6B) COMPLIED.
  
 6C) SEMI-COMPLIED. SHEET A101.THE MID-LANDING SET AT A
 HEIGHT OF 15.5 INCHES DOES NOT SHOW COMPLIANCE WITH
 2014 FBC-ACCESSIBILITY CODE 405.8 HANDRAILS. RAMP RUNS
 WITH A RISE GREATER THAN 6 INCHES (150 MM) SHALL HAVE
 HANDRAILS COMPLYING WITH 505.
  
 505.3 CONTINUITY.
 HANDRAILS SHALL BE CONTINUOUS WITHIN THE FULL LENGTH OF
 EACH STAIR FLIGHT OR RAMP RUN. INSIDE HANDRAILS ON
 SWITCHBACK OR DOGLEG STAIRS AND RAMPS SHALL BE
 CONTINUOUS BETWEEN FLIGHTS OR RUNS.
  
 405.9 EDGE PROTECTION. EDGE PROTECTION COMPLYING WITH
 405.9.1 OR 405.9.2 SHALL BE PROVIDED ON EACH SIDE OF
 RAMP RUNS AND AT EACH SIDE OF RAMP LANDINGS.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-25 Cont ID  
Sent By jwitmer Date 2015-11-25 Time 14:48 Rev Time 0.00
Received By jwitmer Date 2015-11-25 Time 13:26 Sent To  
Notes
2015-11-25 14:48:02BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110532
 ADD: 2302 PRESIDENTIAL WAY
 CONT: HEDRICK BROTHERS
 TEL: 561-689-8880
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. NOV. 25/ 2015
 ACTION: DENIED
  
 1) PLEASE SUBMIT A SITE PLANS MISSING FROM THE 1ST
 REVIEW. 2014 FLORIDA BUILDING CODE W 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS. 107.3.5.1.1 COMMERCIAL BUILDINGS (1.)
 SITE PLAN REQUIREMENTS:
 LOCATION OF JOBSITE.
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF SPECIFIC TANKS, WATER LINES AND SEWER LINES
 FLOOD HAZARD AREAS, FLOOD ZONES, AND DESIGN FLOOD
 ELEVATIONS
  
 2) THE MOD SPACE PLANS DO NOT HAVE A DCA STATE APPROVAL
 BY A 3RD PARTY AGENCY. THE PLANS ARE THE EQUIVALENT TO
 A SITE BUILT STRUCTURE. CAN INSPECTION AFFADAVITS FROM
 THE MANUFACTURER PLANT BE OBTAINED, IF NOT THE
 STRUCTURE HAS TO BE OPENED UP FOR THE CITY STAFF TO BE
 ABLE TO VERIFY CODE COMPLIANCE.
  
 3) THIS STRUCTURE IS GOING TO BE USED AS TEMPORARY GOLF
 FACILITY. THE TERM TEMPORARY IS LESS THAN 180 DAYS. THE
 USE WILL REQUIRE COMPLIANCE WITH EITHER LARGE MISSILE
 IMPACT WINDOWS OR STORM SHUTTERS FOR ALL GLAZED
 OPENINGS. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (E) SHUTTERS
  
 4) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) STORM SHUTTERS. PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.2.
 FL BLD CODE 2010 SECTION 107.2.5., 1609.1.2, 1715.8 A
 COMPLETE INSTALLATION SCHEDULE SUMMARIZING &
 IDENTIFYING OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR.
  
 6) DESIGN DOCUMENTS BY RANDELL STOIFT ARCHITECT FOR
 ACCESSIBLE STAIRS, RAMP AND LANDING:
  
 6A) SHEET A001 DESIGN PARAMETERS INDICATE BUILDING
 CLASSIFICATION AS A R-3 OCCUPANCY, BUT THE PLANS STATE
 TEMPORARY GOFL FACILITY. PLEASE CORRECT OCCUPANCY
 PROUP. 2010 FBC-B 304.1.
  
 6B) NO WIND DESIGN WAS PROVIDED ON ANY OF THE PLANS.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 6C) SHEET A101 & A102 ARE DETAIL SHEETS THA ARE
 INCOMPLETE. THERE ARE MANY IDENTIFICATION TAGS, BUT NO
 LEGEND AS TO WHAT THEY ARE. THERE ARE NO HEIGHT
 DIMENSIONS FOR HANDRAILS NOR GUARDRAILS. THE PLANS ARE
 BASICALLY INCOMPLETE IN FOR THE SCOPE OF WORK OUTLINED.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 6D) NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-01-27 Cont ID  
Sent By mvaldes Date 2016-01-27 Time 15:23 Rev Time 0.00
Received By mvaldes Date 2016-01-27 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-12-21 Cont ID  
Sent By mvaldes Date 2015-12-21 Time 15:23 Rev Time 0.00
Received By mvaldes Date 2015-12-21 Time 15:23 Sent To  
Notes
2015-12-21 15:34:301ST REVIEW: FBC 2014 5TH ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 FAILED TO ADRESS COMMENTS 5 AND 6.
 1006.1 ILLUMINATION REQUIRED.
 THE MEANS OF EGRESS, INCLUDING THE EXIT DISCHARGE,
 SHALL BE ILLUMINATED AT ALL TIMES THE BUILDING SPACE
 SERVED BY THE MEANS OF EGRESS IS OCCUPIED.
 EXTERIOR EGRESS COMPONENTS AT OTHER THAN THEIR LEVELS
 OF EXIT DISCHARGE UNTIL EXIT DISCHARGE IS ACCOMPLISHED
 FOR BUILDINGS REQUIRED TO HAVE TWO OR MORE EXITS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-04 Cont ID  
Sent By albarran Date 2015-12-04 Time 12:38 Rev Time  
Received By albarran Date   Time   Sent To P
Notes
2015-12-04 12:37:54THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF THE VARIOUS COMPONENTS OF THIS
 INSTALLATION.
 A) INDICATE ON PLAN THE PROPOSED ROUTE OF ALL FEEDERS;
 WHETHER AERIAL OR UNDERGROUND. (ALL TRENCHING SHALL
 REMAIN OPEN FOR INSPECTION. NO SITE TUBES WILL BE
 ALLOWED)
 B) INDICATE THE DISTANCE FOR EACH FEEDER FOR VOLTAGE
 DROP CALCULATIONS.
 2. NEC 215.5 YOU SHALL PROVIDE A FEEDER DIAGRAM
 INDICATING IN ADDITION TO THE ABOVE, THE LOAD CALCS AND
 CONDUCTOR SIZING AND INSULATION.
 3. NEC 408.4 PROVIDE A CIRCUIT DIRECTORY AND MARK EVERY
 PANELBOARD WITH THE LOCATION OF THE SOURCE DISCONNECT.
 4. NEC 110.16 ALL EQUIPMENT SHALL BE MARKED WITH THE
 ARC-FLASH WARNING HAZARD LABEL.
 5. IN ADDITION TO THE ELECTRICAL SERVICE FOR THESE
 UNITS, FBC SECTION 1006 REQUIRES THAT THE MEANS OF
 EGRESS BY PROPERLY ILLUMINATED DURING THE TIME OF
 OCCUPANCY. THE DRAWINGS DO NOT REFLECT ADEQUATE
 ILLUMINATION.
 6. FBC FURTHER REQUIRES THAT THESE AREAS BE PROVIDED
 WITH EMERGENCY LIGHTING.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-18 Cont ID  
Sent By GJT Date 2015-12-18 Time   Rev Time 0.00
Received By   Date 2015-12-18 Time   Sent To  
Notes
2015-12-18 09:50:1612/18/15 - PASSED WITH THE FOLLOWING PROVISO: SPRINKLER
 INSTALLATION PENDING VERIFICATION OF 83' BUILDING
 SEPARATION EXISTING OR NEW BLDG. FIRE INSPECTOR WILL
 VERIFY ON INSPECTION. GJT

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-12-02 Cont ID  
Sent By GJT Date 2015-12-02 Time   Rev Time  
Received By   Date 2015-12-02 Time   Sent To  
Notes
2015-12-02 09:41:442302 PRESIDENTIAL WAY - CONSTRUCTION TRAILERS
 PERMIT #15110532
 REVIEW COMMENTS - FIRE DEPARTMENT
 STATUS ? FAILED BY FIRE DEPARTMENT. SUBMIT REVISION
 ADDRESSING PLAN REVIEW COMMENTS:
  
 **A #131 FIRE FINAL INSPECTION IS NEEDED BEFORE
 OCCUPANCY OF THE STRUCTURE IS PERMITTED**
  
 PROVIDE A PLAN SHOWING THE CONFIGURATIONS AND LOCATIONS
 OF THE TRAILERS IN CORRELATION TO OTHER STRUCTURES.
 SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES. PLEASE IDENTIFY AND SHOW
 CLOSET FIRE HYDRANT TO THE PROPOSED TRAILER.
  
 NO PLAN DETAILS SUBMITTED FOR STAIRS, HANDRAILS OR
 GUARDRAILS. HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE
 STAIR. HANDRAILS SHALL BE LOCATED NOT LESS THAN 34
 INCHES AND NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF
 THE TREAD, MEASURED VERTICALLY TO THE TOP OF THE RAIL
 FROM THE LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL
 BE RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT
 NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A
 DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN
 2 INCHES. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE
 PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS,
 MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR.
 OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH
 DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE
 TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND
 BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE
 PASSAGE OF A 6-INCH DIAMETER SPHERE. STAIR RISERS SHALL
 BE BETWEEN 4 INCHES AND 7 INCHES IN HEIGHT. STAIRS
 SHALL BE SLIP RESISTANT AND HAVE A MINIMUM TREAD DEPTH
 OF 11 INCHES AND PREVENT THE ACCUMULATION OF WATER. NO
 PLATFORM / RAMP DETAILS ARE SHOWN FOR REAR EXIT / ENTRY
 DOUBLE DOORS.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF
 DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA
 ADMINISTRATIVE CODE 69A-60.0081.
  
 NOTE: PER NFPA 241, 4.2 TEMPORARY OFFICES AND SHEDS;
 TABLE 4.2.1 SEPARATION DISTANCES, FIRE SPRINKLERS ARE
 REQUIRED IN EACH TRAILER. ALL TRAILERS GREATER THAN A
 ?DOUBLE WIDE? IN THE CITY OF WEST PALM BEACH IS
 REQUIRED TO BE SPRINKLED. PLEASE PROVIDE PLANS FOR A
 MONITORED SPRINKLER AS A SEPARATE/SUB PERMIT.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-27 Cont ID  
Sent By ndaniels Date 2016-01-27 Time 15:30 Rev Time 0.00
Received By ndaniels Date 2016-01-20 Time 14:49 Sent To  
Notes
2016-01-21 14:50:00C23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-11 Cont ID  
Sent By ccole Date 2016-01-11 Time 10:57 Rev Time 0.00
Received By ccole Date 2015-12-11 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-11 Cont ID  
Sent By skennedy Date 2015-12-11 Time 11:18 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 11:44 Sent To  
Notes
2015-11-24 10:11:52NEW DOCUMENTS ADDED TO C01 ON 11/23
2015-11-16 11:45:17C01

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2016-01-26 Cont ID  
Sent By ccole Date 2016-01-26 Time 14:07 Rev Time 0.00
Received By ccole Date 2016-01-26 Time 14:06 Sent To  
Notes
2016-01-26 14:10:19A SEPARATE PERMIT AND PLAN SUBMITTAL WILL BE REQUIRED
 FOR ANY HVAC ALTERATIONS TO BE PERFORMED ON-SITE.
 1/26/16
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-26 Cont ID  
Sent By ccole Date 2016-01-26 Time 10:43 Rev Time 0.00
Received By ccole Date 2016-01-26 Time 10:43 Sent To  
Notes
2016-01-26 11:02:072ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110532
 1/26/16
  
 1) THERE ARE NO MECHANICAL PLANS IN THE RE-SUBMITTED
 PLAN SETS, AND NO RESPONSE NARRATIVE WAS PROVIDED TO
 ADDRESS THE 1ST REVIEW MECHANICAL COMMENTS: PLEASE
 PROVIDE.
 2) BASED ON THE RE-SUBMITTED FLOOR PLANS, IT APPEARS
 THAT ON-SITE DUCT WORK WILL HAVE TO BE PERFORMED-
 PROVIDE AC LAYOUT PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-11 Cont ID  
Sent By ccole Date 2016-01-11 Time 09:42 Rev Time 0.00
Received By ccole Date 2016-01-11 Time 09:42 Sent To  
Notes
2016-01-11 10:53:001ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110532
 01/11/16
  
 1) PLEASE CLARIFY THE OCCUPANCY CLASSIFCATION OF THE
 PROPOSED TEMPORARY CLUBHOUSE AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS IN ACCORDANCE WITH TABLE 403.3
 FBC-14 MECHANICAL. INDICATE THE REQUIRED AND PROVIDED
 AMOUNTS OF OUTDOOR AIR CFM'S ON THE PLAN.
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 3-TON AC SYSTEMS- REFER TO SECTION C403.2.1 FBC-14
 ENERGY CONSERVATION.
 3) PROVIDE DOCUMENTATION OF ENERGY EFFICIENCY
 COMPLIANCE USING EITHER THE PRESCRIPTIVE OR PERFORMANCE
 COMPLIANCE PATH- REFER TO SECTION C101.5.1 FBC-14
 ENERGY CONSERVATION.
 4) PROVIDE AN AC LAYOUT PLAN AND AIR DISTRIBUTION
 SCHEDULE. INCLUDE THE SUPPLY AND RETURN DUCT RUNS, DUCT
 TYPES AND SIZES, CFM CAPACITIES AT EACH SUPPLY DIFFUSER
 OR RETURN GRILL.
 5) THE PLANS INDICATE THREE 3-TON SYSTEMS COMMUNICATING
 WITH EACH OTHER AND EXCEEDING 2000 CFM'S: SEE SECTION
 606.2.2 AND PROVIDE DUCT SMOKE DETECTORS IN THE RETURN
 AIR SYSTEM(S). SHOW THE LOCATIONS OF THE DEVICES ON THE
 LAYOUT PLAN AND INDICATE CONTROLS OPERATION AND THE
 MEANS OF SUPERVISION- SECTIONS 606.4 & 606.4.1.
 6) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE AC
 UNITS ON THE EXTERIOR WALL OF THE MODULAR STRUCTURE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-01-23 Cont ID  
Sent By tklarge Date 2016-01-23 Time 06:34 Rev Time 0.00
Received By tklarge Date 2016-01-23 Time 05:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-12-19 Cont ID  
Sent By tklarge Date 2015-12-19 Time 08:55 Rev Time 0.00
Received By tklarge Date 2015-12-19 Time 08:29 Sent To  
Notes
2015-12-19 08:55:391) SHT. A001 - THE OCCUPANCY CLASSIFICATION SHOWN ON
 THE PLAN IS R-3.THIS IS NOT CORRECT. THE CORRECT
 OCCUPANCY SHALL BE PLACED ON THE PLAN IN ACCORDANCE
 WITH 2014 FBC SEC. 302.
 2) CLEARLY SHOW THE TYPE AND LOCATION OF THE BACKFLOW
 PREVENTION DEVICE REQUIRED ON THE WATER SERVICE. THE
 DEVICE SHALL BE LOCATED AT THE METER.THE BACKFLOW
 PREVENTION DEVICE SHALL BE LEAD FREE. SUBMIT
 SPECIFICATIONS ON THE DEVICE TO BE INSTALLED. WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) INDICATE ON THE PLANS ( BOTH SETS ) THAT A WATER
 COOLER TOWER AND BOTTLED WATER WILL BE PROVIDED IN THE
 MODULAR STRUCTURE. FLAT BOTTOM CUPS SHALL BE PROVIDED
 AND A CUP DISPENSER MOUNTED IN COMPLIANCE WITH SEC. 308
 OF THE 2014 FBC - ACCESSIBILITY SHALL BE PROVIDED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-04 Cont ID  
Sent By gjohnson Date 2015-11-18 Time 17:02 Rev Time 0.00
Received By gjohnson Date 2015-12-04 Time 13:18 Sent To  
Notes
2015-12-04 13:35:101ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1.A WATER FOUNTAIN IS REQUIRED PER FBCP SEC SECTION 403
 MINIMUM PLUMBING FACILITIES TABLE 403.1 AND SHALL
 COMPLY WITH FBC ACC. SEC.602.4 AND 602.7 AND 307.MUST
 BE SHOWN ON PLAN WITH DEMINTIONS.PER WPB AMEND TO FBC
 SEC 107.2.1
 2. A MOP SINK IS REQUIRED PER FBCP SEC SECTION 403
 MINIMUM PLUMBING FACILITIES TABLE 403.1 .MUST BE SHOWN
 ON PLAN WITH DEMINTIONS.PER WPB AMEND TO FBC SEC
 107.2.1
 3.PLEASE PROVIDE SITE PLAN SHOWING SEWER AND WATER
 SERVICE WITH LOCATION OF BACKFLOW. PER. WPB AMEND TO
 FBC SEC 107.2.1

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-07 Cont ID  
Sent By jroach Date 2016-01-07 Time 15:19 Rev Time 0.00
Received By jroach Date 2015-12-28 Time 10:24 Sent To  
Notes
2016-01-07 15:19:51PROVISO
  
 THE TEMPORARY CLUBHOUSE FACILITIES AND ASSOCIATED
 IMPROVEMENTS INDICATED HEREIN SHALL BE DEEMED
 ?TEMPORARY? AND SHALL BE REMOVED WITHIN 36 MONTHS OF
 THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY / COMPLETION
 FOR SUCH IMPROVEMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  