Plan Review Details - Permit 15110526
Plan Review Stops For Permit 15110526
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-03 Cont ID  
Sent By cthroop Date 2016-02-03 Time 14:49 Rev Time 0.00
Received By cthroop Date 2016-02-03 Time 14:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-01-04 Cont ID  
Sent By cthroop Date 2016-01-04 Time 08:30 Rev Time 0.00
Received By cthroop Date 2016-01-04 Time 08:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By cthroop Date 2015-11-20 Time 11:35 Rev Time 0.00
Received By cthroop Date 2015-11-20 Time 11:35 Sent To  
Notes
2015-11-20 12:01:05CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1ST REVIEW: FBC 2014 5TH ED.
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW. FOR YOUR CONVIENENCE I HAVE REFERENCED THE
 APPROPRIATE CODE SECTIONS:
  
 PLANS TO BE LEGIBLE.
 PROVIDE DETAILS FOR FOOTINGS.
 PROVIDE DETAILS FOR CONNECTION TO FOOTINGS.
 PROVIDE SITE PLAN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION.
  
 1807.3 EMBEDDED POSTS AND POLES.
 DESIGNS TO RESIST BOTH AXIAL AND LATERAL LOADS
 EMPLOYING POSTS OR POLES AS COLUMNS EMBEDDED IN EARTH
 OR IN CONCRETE FOOTINGS IN EARTH SHALL BE IN ACCORDANCE
 WITH SECTIONS 1807.3.1 THROUGH 1807.3.3.
 1808.8 CONCRETE FOUNDATIONS.
 THE DESIGN, MATERIALS AND CONSTRUCTION OF CONCRETE
 FOUNDATIONS SHALL COMPLY WITH SECTIONS 1808.8.1 THROUGH
 1808.8.6 AND THE PROVISIONS OF CHAPTER 19.
 1809.12 TIMBER FOOTINGS.
 TIMBER FOOTINGS SHALL BE PERMITTED FOR BUILDINGS OF
 TYPE V CONSTRUCTION AND AS OTHERWISE APPROVED BY THE
 BUILDING OFFICIAL. SUCH FOOTINGS SHALL BE TREATED IN
 ACCORDANCE WITH AWPA U1 (COMMODITY SPECIFICATION A, USE
 CATEGORY 4B). TREATED TIMBERS ARE NOT REQUIRED WHERE
 PLACED ENTIRELY BELOW PERMANENT WATER LEVEL, OR WHERE
 USED AS CAPPING FOR WOOD PILES THAT PROJECT ABOVE THE
 WATER LEVEL OVER SUBMERGED OR MARSH LANDS. THE
 COMPRESSIVE STRESSES PERPENDICULAR TO GRAIN IN
 UNTREATED TIMBER FOOTINGS SUPPORTED UPON TREATED PILES
 SHALL NOT EXCEED 70 PERCENT OF THE ALLOWABLE STRESSES
 FOR THE SPECIES AND GRADE OF TIMBER AS SPECIFIED IN THE
 AF&PA NDS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-03 Cont ID  
Sent By cthroop Date 2016-02-03 Time 14:49 Rev Time 0.00
Received By cthroop Date 2016-01-20 Time 09:37 Sent To  
Notes
2016-01-21 09:37:29ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-04 Cont ID  
Sent By cthroop Date 2016-01-04 Time 08:30 Rev Time 0.00
Received By cthroop Date 2015-12-22 Time 11:52 Sent To  
Notes
2015-12-28 07:45:0112/28 TO CT DESK
  
  
2015-12-22 11:53:04ROUTED TO SGRAHAM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-20 Cont ID  
Sent By cthroop Date 2015-11-20 Time 12:01 Rev Time 0.00
Received By cthroop Date 2015-11-13 Time 15:30 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2016-01-22 Cont ID  
Sent By sgraham Date 2016-01-22 Time 15:30 Rev Time 0.00
Received By sgraham Date 2016-01-22 Time 15:30 Sent To AD
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2015-12-22 Cont ID  
Sent By sgraham Date 2015-12-22 Time 15:12 Rev Time 0.00
Received By sgraham Date 2015-12-22 Time 15:12 Sent To B
Notes
2015-12-22 15:13:1312/22/15 ZONING FAILED 2ND CHECKLIST
  
 1. SUBMIT TWO CERIFIED UP TO DATE SURVEYS SHOWING THE
 LOCATION OF THE AWNING.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-11-16 Cont ID  
Sent By cthroop Date 2015-11-20 Time 12:02 Rev Time 0.00
Received By sgraham Date 2015-11-16 Time 10:38 Sent To B
Notes
2015-11-16 10:39:4811/16/15 ZONING FAILED
  
 1. SUBMIT TWO COPIES OF UP TO DATE SURVEYS SHOWING THW
 LOCATION OF THE AWNING.