Plan Review Details - Permit 15110501
Plan Review Stops For Permit 15110501
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-01-29 Cont ID  
Sent By rmcdouga Date 2016-01-29 Time 12:48 Rev Time 0.00
Received By rmcdouga Date 2016-01-29 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-01-25 Cont ID  
Sent By rmcdouga Date 2016-01-25 Time 14:18 Rev Time 0.00
Received By rmcdouga Date 2016-01-22 Time 19:07 Sent To  
Notes
2016-01-25 14:18:41PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECT. 103.1.1.2 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-05 Cont ID  
Sent By rmcdouga Date 2016-01-05 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2015-12-31 Time 16:07 Sent To  
Notes
2016-01-05 10:00:19PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECT. 103.1.1.2 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SUBMIT TWO COPIES OF FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING
 MATERIALS THAT ARE SPECIFIED ON THE PLANS. (BUR AND
 CONCRETE BARREL TILE) NOTE: THE PRODUCT APPROVALS FOR
 ROOF COVERING MATERIAL FOR FLAT ROOF TYPICALLY HAVE THE
 FASTENER SPACING AND DESIGN PRESSURES FOR ROOF ZONE 1
 AND REQUIRE RAS 117 CALULATIONS FOR ROOF ZONES 2 AND 3.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-11 Cont ID  
Sent By rmcdouga Date 2015-12-11 Time 13:38 Rev Time 0.00
Received By rmcdouga Date 2015-12-08 Time 18:42 Sent To  
Notes
2015-12-11 09:09:53PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DRAWING INDEX ON SHEET T1 DOES NOT MATCH THE
 DRAWINGS THAT WERE SUBMITTED. SHEETS T2, A1.3A, A4 AND
 P3 ARE MISSING.
  
 2) SHEETS T1, D1 AND D2 REFERENCE THE 2008 NEC AND THE
 2011 NEC IS THE CURRENT EDITION.
  
 3) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
 FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE
 COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 4) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THIS
 PROJECT HAS A V ULTIMATE WIND SPEED OF 170 MPH AND THE
 EXPOSURE CATEGORY IS D. FBC-R301.2.1
  
 5) SHOW COMPLIANCE WITH FBC-R317.1 PROTECTION OF WOOD
 AND WOOD BASED PRODUCTS FROM DECAY SHALL BE PROVIDED IN
 THE FOLLOWING LOCATIONS BY THE USE OF NATURALLY DURABLE
 WOOD OR WOOD THAT IS PRESERVATIVE-TREATED IN ACCORDANCE
 WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND
 END USE. PRESERVATIVES SHALL BE LISTED IN SECTION 4 OF
 AWPA U1.
 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR
 WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS
 WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED
 GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED
 WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION.
  
 6) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL
 HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM
 AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS
 HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM)
 SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH
 SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH
 OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM)
 MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF
 FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF
 SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL
 OPEN DIRECTLY TO THE OUTSIDE AIR.
  
 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 8) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR
 NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND
 MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS. (BUR AND CONCRETE BARREL TILE)
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-05 Cont ID  
Sent By rmcdouga Date 2016-01-05 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2016-01-05 Time 14:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By rmcdouga Date 2015-12-15 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2015-12-11 Time 16:52 Sent To  
Notes
2015-12-11 17:43:27PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ELECTRICAL PLANS REFERENCE THE 2008 NEC. THE
 2011 NEC IS THE EDITION OF NEC THAT IS CURRENTLY
 REFERENCED BY THE 2014 FBC.
  
 2) THE ELECTRICAL PROVISIONS OF THE 2014
 FBC-RESIDENTIAL WILL APPLY TO THIS PROJECT.
  
 3) SHOW COMPLIANCE WITH FBCR-E3901.12 FOR REQUIRED HVAC
 SERVICE OUTLET RECEPTACLES.
  
 4) SHOW COMPLIANCE WITH FBCR-E3901.7 FOR REQUIRED
 RECEPTACLE OUTLETS AT FRONT AND REAR OF DWELLING.
  
 5) FBCR-E 3901.2.1 OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL SPACE EXCEED 6' FROM AN OUTLET.
  
 6) NOTE S ON SHEET E3 STATES THAT BEDROOM OUTLETS ARE
 TO BE AFCI PROTECTED. THE CURRENT ELECTRICAL CODE
 REQUIRES AFCI PROTECTION FOR RECEPTACLE OUTLETS LOCATED
 IN OTHER ROOMS AS WELL. SEE FBCR-E3902.12 FOR LIST OF
 ROOMS THAT REQUIRE AFCI PROTECTION.
  
 7) GARAGE AND OUTDOOR RECEPTACLES ARE REQUIRED TO BE
 GFCI PROTECTED. FBCR-E 3902
  
 8) SHOW COMPLIANCE WITH FBCR-E3609.3 FOR REQUIRED
 INTERSYSTEM BONDING TERMINATION.
  
 9) THE ELECTRICAL RISER DIAGRAM ON SHEET E3 HAS
 TRANSFER SWITCH ON PANEL B. IS THERE GOING TO BE A
 FUTURE GENERATOR WITH A TRANSFER SWITCH (SEPARATE
 PERMIT REQUIRED) INSTALLED TO FEED THIS PANEL FOR
 EMERGENCY POWER. PLEASE CLARIFY. FBC 107.2.1
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-12-28 Cont ID  
Sent By gjohnson Date 2015-12-28 Time 15:48 Rev Time 0.00
Received By gjohnson Date 2015-12-28 Time 15:48 Sent To  
Notes
2015-12-28 15:52:28GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
  
  
 SEPERATE PERMIT EQUIRED FOR GAS
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-11-12 Cont ID  
Sent By fmittner Date 2015-11-12 Time 14:17 Rev Time 0.00
Received By fmittner Date 2015-11-12 Time 14:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-01-29 Cont ID  
Sent By rmcdouga Date 2016-01-29 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2016-01-26 Time 13:07 Sent To  
Notes
2016-01-26 13:08:00RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-01-25 Cont ID  
Sent By rmcdouga Date 2016-01-25 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2016-01-12 Time 14:41 Sent To  
Notes
2016-01-12 14:41:37ROUTED RESUB FOR IMPACT FEES TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-05 Cont ID  
Sent By rmcdouga Date 2016-01-05 Time 15:16 Rev Time 0.00
Received By rmcdouga Date 2015-12-22 Time 13:44 Sent To  
Notes
2015-12-22 13:44:19RESUB ROUTED TO GJOHNSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-15 Cont ID  
Sent By rmcdouga Date 2015-12-15 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2015-11-12 Time 10:15 Sent To  
Notes
2015-11-13 10:19:59R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-01-25 Cont ID  
Sent By rmcdouga Date 2016-01-25 Time 07:47 Rev Time 0.00
Received By rmcdouga Date 2016-01-22 Time 19:07 Sent To  
Notes
2016-01-25 07:57:30MU 2016-734, PAID $21.91.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-08 Cont ID  
Sent By rmcdouga Date 2015-12-08 Time 18:41 Rev Time 0.00
Received By rmcdouga Date 2015-12-08 Time 18:41 Sent To  
Notes
2015-12-08 18:42:35BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-01-29 Cont ID  
Sent By rmcdouga Date 2016-01-29 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2016-01-29 Time 12:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-01-25 Cont ID  
Sent By rmcdouga Date 2016-01-25 Time 14:45 Rev Time 0.00
Received By rmcdouga Date 2016-01-25 Time 08:54 Sent To  
Notes
2016-01-25 14:45:56PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
 FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE
 COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION. (THE EQUIPMENT SPECIFIED ON THE MECHANICAL
 PLANS ARE REQUIRED TO MATCH THE ENERGY FORMS AND
 CALCULATIONS).
  
 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-05 Cont ID  
Sent By rmcdouga Date 2016-01-05 Time 10:03 Rev Time 0.00
Received By rmcdouga Date 2016-01-05 Time 10:03 Sent To  
Notes
2016-01-05 10:04:12PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
 FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE
 COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 2) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. FBC
 -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW CRITERIA:
 SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, KITCHEN
 EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS,
 EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR,
 ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION,
 COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS,
 APPLIANCES, BOILERS, REFRIGERATION, BATHROOM
 VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION.
  
 3) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By rmcdouga Date 2015-12-09 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2015-12-09 Time 08:24 Sent To  
Notes
2015-12-09 08:35:31PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION
 SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER
 CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS
 402 OR 405.
 FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE
 COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE
 CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR
 TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR
 RENOVATION.
  
 2) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL
 PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS
 PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. FBC
 -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW CRITERIA:
 SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, KITCHEN
 EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS,
 EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR,
 ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION,
 COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS,
 APPLIANCES, BOILERS, REFRIGERATION, BATHROOM
 VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION.
  
 3) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-28 Cont ID  
Sent By gjohnson Date 2015-12-28 Time 15:48 Rev Time 0.00
Received By gjohnson Date 2015-12-28 Time 15:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-16 Cont ID  
Sent By gjohnson Date 2015-11-16 Time 15:33 Rev Time 0.00
Received By gjohnson Date 2015-11-16 Time 15:33 Sent To  
Notes
2015-11-16 16:18:141ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.PLEASE PROVIDE CALCULATIONS FOR ROOF SCUPPERS AND
 DOWN SPOUTS.
 PER WPB AMEND.TO FBC 107.2.1
 2.EMERGENCY OVERFLOW SCUPPERS ARE REQUIRED.
 PER.FBC P SEC 1108.1
 (A) EMERGENCY OVERFLOW SCUPPERS SHALL COMPY WITH FBC
 SEC.1503.4.2.1 OVERFLOW SCUPPERS.
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT
 PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR
 PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4
 INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND
 SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED
 VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET
 SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING.
 3. SHEET P2 RISER DIAGRAM WASHING MACHINE IS NOT
 VENTED.
 PER FBCP SEC. 901.2.1
 4.SHEET P2 RISER DIAGRAM DOUBLE LAVS IN BATHROOM 1 NOT
 VENTED.
 PER FBCP SEC 901.2.1
 5. DRAIN LINES FROM KITCHEN MASTER BATHROOM AND LAUNDRY
 MUST CONNECT TO BUILDING DRAIN SEPARATELY THEY CANNOT
 CONNECT TO POWDER ROOM SANITARY PIPING.
 PER FBC SEC 912.1
 6. PROVIDE MANUFACTURE INSTALLATION INSTRUCTIONS FOR
 TANKLESS WATER HEATER.
 PER WPB AMEND.TO FBC 107.2.1
 7. SEPERATE PERMIT EQUIRED FOR GAS
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION,
 OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY
 BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK
 PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS
 ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF
 THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS
 BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED
 PER NFPA 58 SECTION 3-2.2.7(H).
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-01-25 Cont ID  
Sent By rmcdouga Date 2016-01-25 Time 08:16 Rev Time 0.00
Received By rmcdouga Date 2016-01-25 Time 08:15 Sent To  
Notes
2016-01-25 08:53:571) FL 16709 CERTAINTEED, MODIFIED BITUMEN ROOFING
 SYSTEM # W-5
 2) SANTAFE SPANISH 'S' CLAY ROOF TILE, NOA NO.
 12-0210.01
 3) 3M AH-160 ROOF TILE ADHESIVE, NOA NO. 14-0805.01

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-01-05 Cont ID  
Sent By rmcdouga Date 2016-01-05 Time 08:58 Rev Time 0.00
Received By rmcdouga Date 2016-01-05 Time 08:58 Sent To  
Notes
2016-01-05 08:59:45NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF COVERING
 MATERIALS.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-11-12 Cont ID  
Sent By fmittner Date 2015-11-12 Time 14:17 Rev Time 0.00
Received By fmittner Date 2015-11-12 Time 14:17 Sent To  
Notes
***NONE***