Plan Review Details - Permit 15110501
Plan Review Stops For Permit 15110501 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2016-01-29 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-29 |
Time |
12:48 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-29 |
Time |
12:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2016-01-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-25 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-22 |
Time |
19:07 |
Sent To |
|
|
Notes |
2016-01-25 14:18:41 | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | SECT. 103.1.1.2 CODE COMPLIANCE CERTIFICATION. | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-01-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-05 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-12-31 |
Time |
16:07 |
Sent To |
|
|
Notes |
2016-01-05 10:00:19 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | SECT. 103.1.1.2 CODE COMPLIANCE CERTIFICATION. | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION. | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SUBMIT TWO COPIES OF FL OR NOA | | NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM | | DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING | | MATERIALS THAT ARE SPECIFIED ON THE PLANS. (BUR AND | | CONCRETE BARREL TILE) NOTE: THE PRODUCT APPROVALS FOR | | ROOF COVERING MATERIAL FOR FLAT ROOF TYPICALLY HAVE THE | | FASTENER SPACING AND DESIGN PRESSURES FOR ROOF ZONE 1 | | AND REQUIRE RAS 117 CALULATIONS FOR ROOF ZONES 2 AND 3. | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-12-11 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-12-11 |
Time |
13:38 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-12-08 |
Time |
18:42 |
Sent To |
|
|
Notes |
2015-12-11 09:09:53 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE DRAWING INDEX ON SHEET T1 DOES NOT MATCH THE | | DRAWINGS THAT WERE SUBMITTED. SHEETS T2, A1.3A, A4 AND | | P3 ARE MISSING. | | | | 2) SHEETS T1, D1 AND D2 REFERENCE THE 2008 NEC AND THE | | 2011 NEC IS THE CURRENT EDITION. | | | | 3) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | 402 OR 405. | | FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE | | COMPLIANCE CERTIFICATION. | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION. | | | | 4) SPECIFY THE WIND DESIGN DATA ON THE PLANS. THIS | | PROJECT HAS A V ULTIMATE WIND SPEED OF 170 MPH AND THE | | EXPOSURE CATEGORY IS D. FBC-R301.2.1 | | | | 5) SHOW COMPLIANCE WITH FBC-R317.1 PROTECTION OF WOOD | | AND WOOD BASED PRODUCTS FROM DECAY SHALL BE PROVIDED IN | | THE FOLLOWING LOCATIONS BY THE USE OF NATURALLY DURABLE | | WOOD OR WOOD THAT IS PRESERVATIVE-TREATED IN ACCORDANCE | | WITH AWPA U1 FOR THE SPECIES, PRODUCT, PRESERVATIVE AND | | END USE. PRESERVATIVES SHALL BE LISTED IN SECTION 4 OF | | AWPA U1. | | 1. WOOD JOISTS OR THE BOTTOM OF A WOOD STRUCTURAL FLOOR | | WHEN CLOSER THAN 18 INCHES (457 MM) OR WOOD GIRDERS | | WHEN CLOSER THAN 12 INCHES (305 MM) TO THE EXPOSED | | GROUND IN CRAWL SPACES OR UNEXCAVATED AREA LOCATED | | WITHIN THE PERIPHERY OF THE BUILDING FOUNDATION. | | | | 6) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED. | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | ENTRANCE OF RAIN OR SNOW. VENTILATION OPENINGS SHALL | | HAVE A LEAST DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM | | AND 1/4 INCH (6.4 MM) MAXIMUM. VENTILATION OPENINGS | | HAVING A LEAST DIMENSION LARGER THAN 1/4 INCH (6.4 MM) | | SHALL BE PROVIDED WITH CORROSION-RESISTANT WIRE CLOTH | | SCREENING, HARDWARE CLOTH, OR SIMILAR MATERIAL WITH | | OPENINGS HAVING A LEAST DIMENSION OF 1/16 INCH (1.6 MM) | | MINIMUM AND 1/4 INCH (6.4 MM) MAXIMUM. OPENINGS IN ROOF | | FRAMING MEMBERS SHALL CONFORM TO THE REQUIREMENTS OF | | SECTION R802.1.8. REQUIRED VENTILATION OPENINGS SHALL | | OPEN DIRECTLY TO THE OUTSIDE AIR. | | | | 7) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. | | | | 8) PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR | | NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND | | MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT | | ROOFING MATERIALS. (BUR AND CONCRETE BARREL TILE) | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-01-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-05 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-05 |
Time |
14:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-12-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-12-15 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-12-11 |
Time |
16:52 |
Sent To |
|
|
Notes |
2015-12-11 17:43:27 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE ELECTRICAL PLANS REFERENCE THE 2008 NEC. THE | | 2011 NEC IS THE EDITION OF NEC THAT IS CURRENTLY | | REFERENCED BY THE 2014 FBC. | | | | 2) THE ELECTRICAL PROVISIONS OF THE 2014 | | FBC-RESIDENTIAL WILL APPLY TO THIS PROJECT. | | | | 3) SHOW COMPLIANCE WITH FBCR-E3901.12 FOR REQUIRED HVAC | | SERVICE OUTLET RECEPTACLES. | | | | 4) SHOW COMPLIANCE WITH FBCR-E3901.7 FOR REQUIRED | | RECEPTACLE OUTLETS AT FRONT AND REAR OF DWELLING. | | | | 5) FBCR-E 3901.2.1 OUTLET SPACING, IT APPEARS SOME | | POINTS ALONG THE WALL SPACE EXCEED 6' FROM AN OUTLET. | | | | 6) NOTE S ON SHEET E3 STATES THAT BEDROOM OUTLETS ARE | | TO BE AFCI PROTECTED. THE CURRENT ELECTRICAL CODE | | REQUIRES AFCI PROTECTION FOR RECEPTACLE OUTLETS LOCATED | | IN OTHER ROOMS AS WELL. SEE FBCR-E3902.12 FOR LIST OF | | ROOMS THAT REQUIRE AFCI PROTECTION. | | | | 7) GARAGE AND OUTDOOR RECEPTACLES ARE REQUIRED TO BE | | GFCI PROTECTED. FBCR-E 3902 | | | | 8) SHOW COMPLIANCE WITH FBCR-E3609.3 FOR REQUIRED | | INTERSYSTEM BONDING TERMINATION. | | | | 9) THE ELECTRICAL RISER DIAGRAM ON SHEET E3 HAS | | TRANSFER SWITCH ON PANEL B. IS THERE GOING TO BE A | | FUTURE GENERATOR WITH A TRANSFER SWITCH (SEPARATE | | PERMIT REQUIRED) INSTALLED TO FEED THIS PANEL FOR | | EMERGENCY POWER. PLEASE CLARIFY. FBC 107.2.1 | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2015-12-28 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2015-12-28 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2015-12-28 |
Time |
15:48 |
Sent To |
|
|
Notes |
2015-12-28 15:52:28 | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | GAS PLAN REVIEW | | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT | | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE | | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. | | 107.2.1. | | | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | FBC-R, SEC. G2404.3. | | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL | | GAS SEC. 301.3. | | | | | | | | SEPERATE PERMIT EQUIRED FOR GAS | | GAS PERMIT APPLICATION REQUIREMENTS | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | IN THE CITY OF WEST PALM BEACH: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | SEC. 402.4.1. | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | PSI. | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | SEC. 502 THRU 505. | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | PER NFPA 58, TABLE 3-2.2.2. | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF | | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | PER NFPA 58 SECTION 3-2.2.7(H). |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2015-11-12 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2015-11-12 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2015-11-12 |
Time |
14:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2016-01-29 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-29 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-26 |
Time |
13:07 |
Sent To |
|
|
Notes |
2016-01-26 13:08:00 | RESUB ROUTED TO RMCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-01-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-25 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-12 |
Time |
14:41 |
Sent To |
|
|
Notes |
2016-01-12 14:41:37 | ROUTED RESUB FOR IMPACT FEES TO RMCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-01-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-05 |
Time |
15:16 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-12-22 |
Time |
13:44 |
Sent To |
|
|
Notes |
2015-12-22 13:44:19 | RESUB ROUTED TO GJOHNSON |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-12-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-12-15 |
Time |
10:00 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-11-12 |
Time |
10:15 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2016-01-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-25 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-22 |
Time |
19:07 |
Sent To |
|
|
Notes |
2016-01-25 07:57:30 | MU 2016-734, PAID $21.91. |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2015-12-08 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-12-08 |
Time |
18:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-12-08 |
Time |
18:41 |
Sent To |
|
|
Notes |
2015-12-08 18:42:35 | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2016-01-29 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-29 |
Time |
13:20 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-29 |
Time |
12:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2016-01-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-25 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-25 |
Time |
08:54 |
Sent To |
|
|
Notes |
2016-01-25 14:45:56 | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | 402 OR 405. | | FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE | | COMPLIANCE CERTIFICATION. | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION. (THE EQUIPMENT SPECIFIED ON THE MECHANICAL | | PLANS ARE REQUIRED TO MATCH THE ENERGY FORMS AND | | CALCULATIONS). | | | | 2) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2016-01-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-05 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-05 |
Time |
10:03 |
Sent To |
|
|
Notes |
2016-01-05 10:04:12 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | 402 OR 405. | | FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE | | COMPLIANCE CERTIFICATION. | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION. | | | | 2) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL | | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS | | PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. FBC | | -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW CRITERIA: | | SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, KITCHEN | | EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | | | 3) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-12-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-12-09 |
Time |
08:24 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-12-09 |
Time |
08:24 |
Sent To |
|
|
Notes |
2015-12-09 08:35:31 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW COMPLIANCE WITH 2014 FBC ENERGY CONSERVATION | | SECT. 101.5.1 & 103.1 BY SUBMITTING THE PROPER | | CONSTRUCTION DOCUMENTS. SEE RESIDENTIAL BUILDING FORMS | | 402 OR 405. | | FBC ENERGY CONSERVATION - SECT. 103.1.1.2 CODE | | COMPLIANCE CERTIFICATION. | | THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER | | AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL | | CERTIFY THAT THE BUILDING IS IN COMPLIANCE WITH THE | | CODE, AS PER SECTION 553.907, FLORIDA STATUTES, PRIOR | | TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION OR | | RENOVATION. | | | | 2) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL | | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS | | PER FBC-R M16 & BATH EXHAUST PER FBC-R M15. FBC | | -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW CRITERIA: | | SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, KITCHEN | | EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | | | 3) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2015-12-28 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2015-12-28 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2015-12-28 |
Time |
15:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-11-16 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2015-11-16 |
Time |
15:33 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2015-11-16 |
Time |
15:33 |
Sent To |
|
|
Notes |
2015-11-16 16:18:14 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1.PLEASE PROVIDE CALCULATIONS FOR ROOF SCUPPERS AND | | DOWN SPOUTS. | | PER WPB AMEND.TO FBC 107.2.1 | | 2.EMERGENCY OVERFLOW SCUPPERS ARE REQUIRED. | | PER.FBC P SEC 1108.1 | | (A) EMERGENCY OVERFLOW SCUPPERS SHALL COMPY WITH FBC | | SEC.1503.4.2.1 OVERFLOW SCUPPERS. | | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT | | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR | | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 | | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND | | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED | | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET | | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. | | 3. SHEET P2 RISER DIAGRAM WASHING MACHINE IS NOT | | VENTED. | | PER FBCP SEC. 901.2.1 | | 4.SHEET P2 RISER DIAGRAM DOUBLE LAVS IN BATHROOM 1 NOT | | VENTED. | | PER FBCP SEC 901.2.1 | | 5. DRAIN LINES FROM KITCHEN MASTER BATHROOM AND LAUNDRY | | MUST CONNECT TO BUILDING DRAIN SEPARATELY THEY CANNOT | | CONNECT TO POWDER ROOM SANITARY PIPING. | | PER FBC SEC 912.1 | | 6. PROVIDE MANUFACTURE INSTALLATION INSTRUCTIONS FOR | | TANKLESS WATER HEATER. | | PER WPB AMEND.TO FBC 107.2.1 | | 7. SEPERATE PERMIT EQUIRED FOR GAS | | GAS PERMIT APPLICATION REQUIREMENTS | | | | EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL | | BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING | | IN THE CITY OF WEST PALM BEACH: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON | | THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | SEC. 402.4.1. | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014 | | FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2 | | PSI. | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | SEC. 502 THRU 505. | | | | 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | 10. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP | | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF | | THE TANK FROM THE BUILDING AND ADJACENT PROPERTY LINES | | THE DISTANCE OF THE TANK FROM ALL SOURCES OF IGNITION, | | OTHER CONTAINERS, BUILDINGS, AND THE LOCATION OF ANY | | BUILDING OPENINGS BELOW THE RELIEF VALVE OF THE TANK | | PER NFPA 58, TABLE 3-2.2.2. | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS | | ABOVE OR BELOW GROUND, AND SHOW REQUIRED PROTECTION OF | | THE TANK AND APPURTENANCES PER NFPA 58. IF THE TANK IS | | BELOW GROUND THE CONTAINER SHALL BE SECURELY ANCHORED | | PER NFPA 58 SECTION 3-2.2.7(H). | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2016-01-25 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-25 |
Time |
08:16 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-25 |
Time |
08:15 |
Sent To |
|
|
Notes |
2016-01-25 08:53:57 | 1) FL 16709 CERTAINTEED, MODIFIED BITUMEN ROOFING | | SYSTEM # W-5 | | 2) SANTAFE SPANISH 'S' CLAY ROOF TILE, NOA NO. | | 12-0210.01 | | 3) 3M AH-160 ROOF TILE ADHESIVE, NOA NO. 14-0805.01 |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2016-01-05 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-05 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-05 |
Time |
08:58 |
Sent To |
|
|
Notes |
2016-01-05 08:59:45 | NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF COVERING | | MATERIALS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2015-11-12 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2015-11-12 |
Time |
14:17 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2015-11-12 |
Time |
14:17 |
Sent To |
|
|
Notes |
|
|
|