Plan Review Details - Permit 15110346
Plan Review Stops For Permit 15110346
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-29 Cont ID  
Sent By rmcdouga Date 2016-02-29 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2016-02-29 Time 16:59 Sent To  
Notes
2016-02-29 16:59:28APPROVED WITH EXCEPTION. SEE RED-LINED NOTES ON THE
 PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-24 Cont ID  
Sent By rmcdouga Date 2016-02-24 Time 07:33 Rev Time 0.00
Received By rmcdouga Date 2016-02-24 Time 07:21 Sent To  
Notes
2016-02-24 07:21:33PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO SECTION
 2413.6.1 OF THE 2014 FBC. THIS SECTION IS ONLY
 APPLICABLE TO STRUCTURES LOCATED IN THE HIGH VELOCITY
 HURRICANE ZONE ( DADE AND BROWARD COUNTIES ). THIS
 SECTION REQUIRES SHUTTERS USED TO PROTECT OPENINGS
 ABOVE THE FIRST FLOOR TO BE PERMANENTLY INSTALLED AND
 CLOSABLE FROM THE INSIDE OF THE BUILDING. THIS SECTION
 DOES NOT APPLY IN PALM BEACH COUNTY AND THE STORM
 PANELS YOU ARE USING DO NOT COMPLY. PLEASE REMOVE THIS
 NOTE FROM THE PLANS.
  
 2) SECTION 2411.3.1.6 THAT IS CITED IN THE GENERAL
 NOTES ON SEVERAL PLAN SHEETS ALSO DOES NOT APPLY
 OUTSIDE OF THE HIGH VELOCITY HURRICANE ZONE ( DADE AND
 BROWARD COUNTIES ).
  
 3) THE CORRECT SECTION FOR STRUCTURAL INDEPENDENCE OF
 THE ADJACENT UNIT IS FBC R302.2.4 AND NOT R317.2.4.
  
 4) FBC 1208.2 IS FROM THE 2014 FBC AND NOT THE
 FBC-RRESIDENTIAL. THE RESIDENTIAL CODE APPLIES TO
 TOWNHOUSES SUCH AS THIS PROJECT. THIS SECTION OF CODE
 IS LOCATED IN R305.1.
  
 5) FBC R302.11 IS THE SECTION FOR FIREBLOCKING AND NOT
 R4302.11. SEE SHEET D1.
  
 6) THE CORRECT SECTION FOR INSULATION FLAME SPREAD AND
 SMOKE DEVELOPED IS FBC R302.10.1.
  
 7) THE 2014 FBCR REFERENCES THE 2011 EDITIONS OF ACI
 530.1, ASCE 6-11 AND TMS 602. SEE CLOUDED AREA ON PLANS
 WHERE THE WRONG EDITIONS ARE CITED.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-21 Cont ID  
Sent By rmcdouga Date 2015-12-21 Time 09:35 Rev Time 0.00
Received By rmcdouga Date 2015-12-21 Time 09:35 Sent To  
Notes
2015-12-18 18:36:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE 2010 FBC.
 THE FBC FIFTH EDITION (2014) WENT INTO EFFECT ON JUNE
 30, 2015. ALL NEW PERMITS APPLIED FOR ON OR AFTER THAT
 DATE ARE REQUIRED TO COMPLY WITH AND REFERENCE THE FBC
 FIFTH EDITION.
  
 2) THE ENERGY CALCULATION FORMS SPECIFY IECC ZONE 2.
 THE CITY OF WEST PALM IS IN PALM BEACH COUNTY WHICH IS
 IN CLIMATE ZONE 1A. FBC ENERGY CONSERVATION TABLE
 R301.1
  
 3) THE STORM PANEL SCHEDULES REFERENCE THE 2010 FBC.
 PLEASE CHANGE TO THE 2014 FBC.
  
 4) THE NOTES ON SECTION 2 SHEET D-1 AT THE PARTY WALL
 SHOULD REFERENCE 2014 FBC R302.2 AND NOT R317.2.
  
 5) THE CORRECT SECTION FOR STRUCTURAL INDEPENDENCE OF
 THE ADJACENT UNIT IS FBC R302.2.4 AND NOT R317.2.4.
  
 6) FBC R 4409.13.3.2.3 THAT IS SPECIFIED ON THE PLANS
 ONLY APPLIES TO THE HVHZ ( HIGH VELOCITY HURRICANE ZONE
 ) AND DOES NOT APPLY IN PALM BEACH COUNTY. THE CORRECT
 SECTION FOR THIS JURISDICTION IS FBC R 806.1 WHICH
 ALLOWS THE MAXIMUM SCREEN MESH OPENINGS TO BE 1/4 INCH.
  
 7) FBC R702.2.2 IS THE SECTION FOR MINIMUM STUCCO
 FINISH ON CONCRETE BLOCK AND NOT 4411.31.
  
 8) FBC R302.11 IS THE SECTION FOR FIREBLOCKING AND NOT
 R4409.7.1.
  
 9) THE CORRECT SECTION FOR INSULATION FLAME SPREAD AND
 SMOKE DEVELOPED IS FBC R302.10.1.
  
 10) FBC R302.2.2 IS THE SECTION THAT REQUIRES
 FIRE-RESISTANT PLYWOOD FOR 4 FEET ON EACH SIDE OF THE 2
 HOUR FIRE RATED PARTY WALL.
  
 11) THE 2014 FBCR REFERENCES THE 2011 EDITIONS OF ACI
 530.1, ASCE 6-11 AND TMS 602.
  
 12) THE ROOF SHEATHING FASTENING DETAIL DIAGRAM ON
 SHEET S-3 DOES NOT SHOW ROOF ZONE 3 FOR THE GABLE ROOF
 AREAS ON THE FRONT OF THE BUILDING. SEE FBC R803.2.3.1
  
 13) THE UPLIFT PRESSURES FOR THE ROOF COMPONENTS AND
 CLADDING ON SHEET S-6 ARE NOT CORRECT. ROOF ZONE 1 IS
 SPECIFIED AS -31.31 PSF AND ZONE 2 AND 3 ARE SPECIFIED
 AS -49.66 PSF. FBC-R 301.2.1
  
 14) THE ANCHOR SPACING IS BLANK ON THE STORM PANEL
 SCHEDULE FOR THE END A UNIT. FBC 107.2.1
  
 15) THE MAXIMUM NEGATIVE DESIGN PRESSURE LISTED IN THE
 PRODUCT APPROVAL FOR THE ENTRY DOOR IS -50 PSF. THE
 WIND PRESSURE FOR THE ENTRY DOOR IN THE EXTERIOR WALL
 ZONE IS SPECIFIED AS -55.08 PSF IN THE SCHEDULE ON THE
 PLANS. FBC-R301.1
  
 16) THE VALUATIONS FOR THE TOWNHOUSES ARE LOW BASED ON
 ICC VALUATION DATE AND WILL BE ADJUSTED AS FOLLOWS. THE
 1441 UNIT A IS $164,673.00. THE 1545 UNIT B IS
 $175,294.00. THE 1669 UNIT C IS $191,515.23.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-02-25 Cont ID  
Sent By albarran Date 2016-02-25 Time 15:38 Rev Time 0.00
Received By albarran Date 2016-02-25 Time 15:37 Sent To  
Notes
2016-02-25 15:38:17ALL PREVIOUSLY MENTIONED COMMENTS HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-22 Cont ID  
Sent By albarran Date 2016-02-22 Time 17:38 Rev Time 0.00
Received By albarran Date 2016-02-22 Time 15:00 Sent To  
Notes
2016-02-22 17:38:292ND ELECTRICAL REVIEW NOTES FOR PERMIT #: 15110245,
 15110318, 15110330, 15110346, 15110351, 15110356 &
 15110362
 REVIEWED FOR COMPLIANCE WITH: FBC 5TH EDITION 2014 &
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 SHEET A-E 1 COMMENT #9: I MENTIONED THE NEED FOR A
 SECOND WALL SWITCH FOR THE LOCATIONS WHERE YOU INTEND
 TO HANG A PADDLE FAN. YOUR RESPONSE ONLY CONFIRMS THAT
 THERE WILL BE A PADDLE FAN W/A LIGHT KIT. NEC
 210.70(A)(1) MANDATES THAT BE AT LEAST ONE WALL SWITCH
 CONTROLLED LUMINAIRE IN EVERY HABITABLE ROOM, THEREFORE
 IF YOU WILL NOT BE ADDING THE SECOND SWITCH, YOU SHALL
 MAKE SURE THAT THE SWITCH CONTROLS THE LUMINAIRE AND
 NOT THE FAN.
  
 SHEET B-E 1 COMMENT #10: SAME AS ABOVE.
  
 SHEET C-E 1 DIDN?T HAVE THE ABOVE COMMENT MENTIONED BUT
 THE REQUIREMENT APPLIES AS WELL.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-22 Cont ID  
Sent By albarran Date 2015-12-22 Time 08:40 Rev Time 0.00
Received By albarran Date 2015-12-22 Time 08:40 Sent To  
Notes
2015-12-22 08:41:05THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 (PLANS APPEAR UNDER PERMIT #15110245)
 ELEC. APP.
 1. ADJUST VALUATION TO A REASONABLE AMOUNT GREATER THAN
 $4,000.00
 PG. A-E.1
 1. IN THE INTEREST OF ENERGY CONSERVATION, LIFE SAFETY
 AND CONVENIENCE, A 3 WAY SWITCH SHOULD CONTROL THE
 FOYER LUMINAIRE.
 2. CORRECT NOTE 14 TO INCLUDE ?AND BE RATED ?WR?
 WEATHER RESISTANT AS PER NEC 406.9(B).
 3. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 4. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS.
 5. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IF THIS LUMINAIRE IS INSIDE THE ATTIC, NEC 410.11
 LUMINAIRES NEAR COMBUSTIBLE MATERIAL APPLIES.
 LUMINAIRES SHALL BE EQUIPPED WITH A SHADE OR GUARD SO
 THAT COMBUSTIBLE MATERIAL IS NOT SUBJECTED TO EXCESSIVE
 TEMPERATURES.
 8. THE ROUTING OF THE SERVICES MAY REQUIRE THAT AN
 EASEMENT BE RECORDED PER UNIT. IF SO, THESE WILL HAVE
 TO BE FILED AND RECORDED PRIOR TO FINAL INSPECTIONS.
 THIS WILL BE DETERMINED AND NOTED ON THE ELECTRICAL
 SITE PLAN.
 9. WITHOUT A SWITCHED RECEPTACLE IN THE ROOM, A SECOND
 SWITCH FOR LIGHTING IS ADVISABLE IF YOU INTEND TO HANG
 A CEILING FAN FROM THIS OUTLET.
 10. IN THE INTEREST OF ENERGY CONSERVATION, LIFE SAFETY
 AND CONVENIENCE, A 3 WAY SWITCH OR AN AUTOMATIC
 OCCUPANCY SENSOR SHOULD CONTROL THE UPSTAIRS CORRIDOR
 LUMINAIRE.
  
 PG. B-E.1
 1. NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT.
 OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE.
 2. CORRECT NOTE 14 TO INCLUDE ?AND BE RATED ?WR?
 WEATHER RESISTANT AS PER NEC 406.9(B).
 3. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 4. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS.
 5. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IF THIS LUMINAIRE IS INSIDE THE ATTIC, NEC 410.11
 LUMINAIRES NEAR COMBUSTIBLE MATERIAL APPLIES.
 LUMINAIRES SHALL BE EQUIPPED WITH A SHADE OR GUARD SO
 THAT COMBUSTIBLE MATERIAL IS NOT SUBJECTED TO EXCESSIVE
 TEMPERATURES.
 8. THE ROUTING OF THE SERVICES MAY REQUIRE THAT AN
 EASEMENT BE RECORDED PER UNIT. IF SO, THESE WILL HAVE
 TO BE FILED AND RECORDED PRIOR TO FINAL INSPECTIONS.
 THIS WILL BE DETERMINED AND NOTED ON THE ELECTRICAL
 SITE PLAN.
 9. IN THE INTEREST OF ENERGY CONSERVATION, LIFE SAFETY
 AND CONVENIENCE, A 3 WAY SWITCH SHOULD CONTROL THE
 LIVING ROOM LUMINAIRE.
 10. WITHOUT A SWITCHED RECEPTACLE IN THE ROOM, A SECOND
 SWITCH FOR LIGHTING IS ADVISABLE IF YOU INTEND TO HANG
 A CEILING FAN FROM THIS OUTLET.
 11. SPACE KITCHEN COUNTER RECEPTACLES SO THAT THERE IS
 NO POINT FURTHER THAN 2 FT. MEASURED ALONG THE COUNTER
 FROM AN OUTLET.
 PG. C-E.1
 1. IN THE INTEREST OF ENERGY CONSERVATION, LIFE SAFETY
 AND CONVENIENCE, A 3 WAY SWITCH SHOULD CONTROL THE
 LIVING ROOM LUMINAIRE.
 2. CORRECT NOTE 14 TO INCLUDE ?AND BE RATED ?WR?
 WEATHER RESISTANT AS PER NEC 406.9(B).
 3. THE WORD ?ROMEX? AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 4. NEC 110.26(D) ILLUMINATION. ILLUMINATION SHALL BE
 PROVIDED FOR ALL WORKING SPACES ABOUT SERVICE
 EQUIPMENT, SWITCHBOARDS, AND PANELBOARDS.
 5. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 6. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 7. IF THIS LUMINAIRE IS INSIDE THE ATTIC, NEC 410.11
 LUMINAIRES NEAR COMBUSTIBLE MATERIAL APPLIES.
 LUMINAIRES SHALL BE EQUIPPED WITH A SHADE OR GUARD SO
 THAT COMBUSTIBLE MATERIAL IS NOT SUBJECTED TO EXCESSIVE
 TEMPERATURES.
 8. THE ROUTING OF THE SERVICES MAY REQUIRE THAT AN
 EASEMENT BE RECORDED PER UNIT. IF SO, THESE WILL HAVE
 TO BE FILED AND RECORDED PRIOR TO FINAL INSPECTIONS.
 THIS WILL BE DETERMINED AND NOTED ON THE ELECTRICAL
 SITE PLAN.
 9. SPACE KITCHEN COUNTER RECEPTACLES SO THAT THERE IS
 NO POINT FURTHER THAN 2 FT. MEASURED ALONG THE COUNTER
 FROM AN OUTLET.
 10. IN THE INTEREST OF ENERGY CONSERVATION, LIFE SAFETY
 AND CONVENIENCE, A 4 WAY SWITCH OR AUTOMATIC OCCUPANCY
 SENSOR SHOULD CONTROL THE LUMINAIRES IN THE UPSTAIRS
 BEDROOM CORRIDOR.
  
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-01 Cont ID  
Sent By lmarchan Date 2016-03-01 Time 08:29 Rev Time 0.00
Received By lmarchan Date 2016-02-26 Time 08:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-24 Cont ID  
Sent By rmcdouga Date 2016-02-24 Time 07:33 Rev Time 0.00
Received By rmcdouga Date 2016-02-02 Time 15:04 Sent To  
Notes
2016-02-02 15:04:08PLANS UNDER 15110245

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-22 Cont ID  
Sent By lmarchan Date 2015-12-22 Time 09:09 Rev Time 0.00
Received By lmarchan Date 2015-11-17 Time 17:11 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-12-23 Cont ID  
Sent By rmcdouga Date 2015-12-23 Time 18:44 Rev Time 0.00
Received By rmcdouga Date 2015-12-23 Time 18:44 Sent To  
Notes
2015-12-23 18:44:57MU-2015-27224

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-12-23 Cont ID  
Sent By rmcdouga Date 2015-12-23 Time 18:43 Rev Time 0.00
Received By rmcdouga Date 2015-12-23 Time 18:43 Sent To  
Notes
2015-12-18 18:38:16BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-12-21 Cont ID  
Sent By hmoser Date 2015-12-21 Time 10:59 Rev Time 0.00
Received By hmoser Date 2015-12-21 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-02-06 Cont ID  
Sent By tklarge Date 2016-02-06 Time 05:37 Rev Time 0.00
Received By tklarge Date 2016-02-06 Time 05:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-20 Cont ID  
Sent By gjohnson Date 2015-11-20 Time 12:54 Rev Time 0.00
Received By gjohnson Date 2015-11-20 Time 12:54 Sent To  
Notes
2015-11-20 12:54:531ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
 1. PLEASE PROVIDE A RISER DIAGRAM FOR SANITARY AND
 WATER.
 PER WPB AMEND.TO FBC SEC 107.3.5.1.3(3,4,5,6,10,13)
 2. PLEASE PROVIDE A SITE PLAN SHOWING WATER AND SEWER
 TO EACH UNIT .
 PER WPB AMEND.TO FBC SEC 107.3.5
 3. PLEASE PROVIDE MANUFACTURE SPEC SHEETS FOR TANKLESS
 WATER HEATER.
 PER WPB AMEND.TO FBC SEC 107.2.1

Review Stop Z ZONING
Rev No 1 Status P Date 2015-11-19 Cont ID  
Sent By llouie Date 2015-11-19 Time 11:54 Rev Time 0.00
Received By llouie Date 2015-11-19 Time 11:54 Sent To  
Notes
2015-11-19 11:55:52ZONING APPROVED WITH THE FOLLOWING PROVISO:
  
 1.) PARKING STALL STRIPING SHALL CONFORM TO THE
 STANDARDS IN ZLDR S.94-485.