Plan Review Details - Permit 15110125
Plan Review Stops For Permit 15110125
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-02-11 Cont ID  
Sent By jwitmer Date 2016-02-11 Time 06:28 Rev Time 0.00
Received By jwitmer Date 2016-02-11 Time 06:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-02-02 Cont ID  
Sent By jwitmer Date 2016-02-02 Time 10:45 Rev Time 0.00
Received By jwitmer Date 2016-02-02 Time 10:04 Sent To  
Notes
2016-02-02 10:45:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110125
 ADD: 114 S. OLIVE AVE.
 CONT: HOOD DEPOT
 TEL: 954-570-9860
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: WED. DEC. 30/2015
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
 1) COMPLILED. WIND DESIGN CRITERIA ON THE PLANS.
  
  
 2A)(1) 3RD REQUEST. SEMI COMPLIED. PRECISION ALUMINUM
 PRODUCTS/ A/C STANDS SUBMITTED ENGINEERING FROM FRANK
 BENNARDO NO COVERE SHEETS WERE PROVIDED INDICATING THIS
 IS A FLORIDA APPROVAL OR A MIAMI-DADE NOA.
  
 2A)(2) SHEET 3 OF 7 SHOWS 3 ROOF TOP CONDENING UNITS
 AND ROOF TOP STAND AND ROOF TOP CURBS INTAKE AND
 EXHAUST FANS PLEASE PROVIDE EITHER A FLORIDA APPROVAL
 OR MIAMI-DADE NOA. . PLEASE SHOW COMPLIANCE WITH:
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOF TOP CURBS, ROOF TOP INTAKE & EXHAUST FANS
 -NO PRODUCT APPROVALS WERE SUBMITTED!!!!
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 2B) 3RD REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) 3RD REQUEST.THE ENGINEER OF RECORD (STRUCTURAL) HAS
 NOT REVIEWED THESE PLANS FOR CODE COMPLIANCE, NOR
 AFFIXED THERE SHOP DRAWING STAMPED REVIEWED AND
 APPROVED. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-30 Cont ID  
Sent By jwitmer Date 2015-12-30 Time 09:30 Rev Time 0.00
Received By jwitmer Date 2015-12-30 Time   Sent To  
Notes
2015-12-30 09:12:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110125
 ADD: 114 S. OLIVE AVE.
 CONT: HOOD DEPOT
 TEL: 954-570-9860
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: WED. DEC. 30/2015
 ACTION: DENIED
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
 1) 2ND REQUEST. THE (7) MECHANICAL SHEETS SUBMITTED BY
 HOOD DEPOT DO NOT HAVE THE WIND DESIGN CRITERIA ON THE
 PLANS,
  
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2A) 2ND REQUEST. SHEET 3 OF 7 SHOWS 3 ROOF TOP
 CONDENING UNITS AND ROOF TOP STAND AND ROOF TOP CURBS
 INTAKE AND EXHAUST FANS PLEASE PROVIDE EITHER A FLORIDA
 APPROVAL OR MIAMI-DADE NOA. . PLEASE SHOW COMPLIANCE
 WITH: FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOF TOP CURBS, ROOF TOP INTAKE & EXHAUST FANS
 (31)(G) PRE-ENGINEERED A/C STANDS
  
 2B) 2ND REQUEST. 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 3) 2ND REQUEST. SHEET 6 & 7 SHOWS THE AIR COMPRESSOR
 BEING HUNG FROM THE SIDE OF THE THRESHOLD BUILDING. ALL
 THRESHOLD INSPECTIONS ARE TO BE PREFORMED BY THE
 THRESHOLD INSPECTOR. NO INSPECTIONS OF THIS SYSTEM HAS
 OCCURRED. THE SECOND ISSUE IS THE ENGINEER OF RECORD
 (STRUCTURAL) HAS NOT REVIEWED THESE PLANS FOR CODE
 COMPLIANCE, NOR AFFIXED THERE SHOP DRAWING STAMPED
 REVIEWED AND APPROVED. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-14 Cont ID  
Sent By jwitmer Date 2015-12-14 Time 14:49 Rev Time 0.00
Received By jwitmer Date 2015-12-14 Time 13:40 Sent To Z
Notes
2015-12-14 13:55:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15110125
 ADD: 114 S. OLIVE AVE.
 CONT: HOOD DEPOT
 TEL: 954-570-9860
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: MON. DEC. 21/2015
 ACTION: DENIED
  
 1) THE (7) MECHANICAL SHEETS SUBMITTED BY HOOD DEPOT DO
 NOT HAVE THE WIND DESIGN CRITERIA ON THE PLANS,
  
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 1.2. RISK CATEGORY.
  
 1.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 1.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 1.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 2A) SHEET 3 OF 7 SHOWS 3 ROOF TOP CONDENING UNITS AND
 ROOF TOP STAND. PLEASE SHOW COMPLIANCE WITH: FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31 (G) PRE-ENGINEERED A/C STANDS
  
 2B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 3) SHEET 5OF 7 SHOWS THE AIR COMPRESSOR BEING HUNG FROM
 THE SIDE OF THE THRESHOLD BUILDING. ALL THRESHOLD
 INSPECTIONS ARE TO BE PREFORMED BY THE THRESHOLD
 INSPECTOR. THE SECOND ISSUE IS THE ENGINEER OF RECORD
 HAS NOT REVIEWED THESE PLANS FOR CODE COMPLIANCE, NOR
 AFFIXED THERE SHOP DRAWING STAMPED REVIEWED AND
 APPROVED. FL 61G-15-30.006 (3) THE DELEGATED ENGINEER
 SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENTS TO
 THE ENGINEER OF RECORD FOR REVIEW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2016-02-03 Cont ID  
Sent By albarran Date 2016-02-03 Time 14:16 Rev Time 0.00
Received By albarran Date 2016-02-03 Time 13:59 Sent To I
Notes
2016-02-03 14:38:03HOOD DEPOT IS DEFERRING ALL THE ELECTRICAL COMMENTS AND
 REQUIRED DOCUMENTATION TO AN ELECTRICAL ENGINEER.
 THEREFORE IN AN EFFORT TO RELEASE THIS PERMIT AND NOT
 HOLD IT UP ANY LONGER, I WILL ISSUE THE PERMIT WITHOUT
 ANY ELECTRIC. AN ELECTRICAL SUB PERMIT SHALL BE
 REQUIRED TO ADDRESS ALL OF THE ELECTRICAL COMMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-01-14 Cont ID  
Sent By albarran Date 2016-01-14 Time 14:42 Rev Time 0.00
Received By albarran Date 2016-01-14 Time 12:02 Sent To Z
Notes
2016-01-14 14:42:43YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS.
  
 1. THIS TIME THE MASTER PERMIT REFERRED TO ON THE
 APPLICATION IS FOR THE COMMERCIAL REMODEL OF THE BLDG.
 BUT THE KITCHEN HOOD SYSTEM SPECIFIED ON THE MASTER
 PERMIT DIFFERS FROM THE ONE BEING PROPOSED ON THIS
 APPLICATION THEREFORE ALL ELECTRICAL REQUIREMENTS AS
 PREVIOUSLY REQUESTED SHALL BE SUBMITTED FOR REVIEW.
 2. THE SYSTEM ON THE MASTER PERMIT IS A CAPTIVE AIR AND
 THIS IS A HOOD DEPOT.
 3. YOU SHALL PROVIDE CIRCUIT DIRECTORY, WIRING DIAGRAM
 AND LOAD CALCS FOR BOTH, THE HOOD FAN MOTORS AND THE
 MUA COOLING SYSTEM.
 4. PROVIDE SHUNT TRIP BREAKER FOR ALL ELECTRICAL
 EQUIPMENT AND OUTLETS UNDER THE HOOD.
 5. YOU SHALL PROVIDE A CORRECTED CIRCUIT DIRECTORY FOR
 THE PANELS AFFECTED BY THIS MODIFICATION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE?SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE?SUBMITTAL FORM, AS WELL AS AN
 INDICATION ON THE PAGE WHERE THE CORRECTION WAS
 PERFORMED. ADDITIONALLY, PLEASE INSERT CORRECTED PAGES
 INTO THE SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARISON. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED. IF YOU HAVE FURTHER QUESTIONS,
 PLEASE DON?T HESITATE TO CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH.: 561?805?6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-11 Cont ID  
Sent By albarran Date 2015-12-11 Time 10:04 Rev Time 0.00
Received By albarran Date 2015-12-11 Time 09:26 Sent To B
Notes
2015-12-11 10:54:16THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE MASTER PERMIT REFERRED TO ON THIS APPLICATION IS
 FOR A FIRE SPRINKLER SYSTEM AND HAS NOTHING TO DO WITH
 THE INSTALLATION OF KITCHEN HOODS. THEREFORE A COMPLETE
 ELECTRICAL DRAWING SHALL BE PROVIDED.
 2. THE FAN SCHEDULE AND CONTROL PANEL INPUT VOLTAGES DO
 NOT MATCH ON THE SUBMITTED DRAWINGS. REVISE DRAWINGS TO
 ADDRESS THIS ISSUE.
 3. YOU SHALL PROVIDE CIRCUIT DIRECTORY, WIRING DIAGRAM
 AND LOAD CALCS FOR THIS ADDED LOAD.
 4. PROVIDE SHUNT TRIP BREAKER FOR ALL ELECTRICAL
 EQUIPMENT AND OUTLETS UNDER THE HOOD.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-01-26 Cont ID  
Sent By pleduc Date 2016-01-26 Time   Rev Time 0.00
Received By pleduc Date 2016-01-26 Time 14:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-23 Cont ID  
Sent By pleduc Date 2015-12-23 Time   Rev Time 0.00
Received By pleduc Date 2015-12-23 Time 10:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-16 Cont ID  
Sent By lmarchan Date 2015-12-18 Time 16:15 Rev Time 0.00
Received By pleduc Date 2015-11-16 Time 11:13 Sent To M
Notes
2015-11-16 12:05:32THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE GREATER DETAIL OF THE LOCATION OF THE
 HOOD SYSTEM AS IT APPEARS TO BE IN AN ALLEY.
  
 2. THE HEIGHT OF THE CLEARENCE FROM THE GROUND, WITHIN
 THE ALLEY, SHALL BE A MINIMUM OF 13'6".
  
 3. THE LOCATION OF THE 2ND HOOD EXHAUST APPEARS TO BE
 TOO CLOSE TO THE ROOF A/C. PROVIDE GREATER DETAIL.
  
 4. PROVIDE A FIRE RATED LISTING FOR PENETRATING THE
 EXTERIOR WALL.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2016-02-11 Cont ID  
Sent By jwitmer Date 2016-02-11 Time 08:52 Rev Time 0.00
Received By jwitmer Date 2016-02-09 Time 09:54 Sent To  
Notes
2016-02-10 09:54:56B22

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-10 Cont ID  
Sent By lmarchan Date 2016-02-10 Time 09:54 Rev Time 0.00
Received By lmarchan Date 2015-12-18 Time 13:47 Sent To  
Notes
2016-01-20 12:21:31B22 - RESUBMITTED ON 1/19/16
2015-12-21 13:47:29B22 *COULD NOT LOCATE ORIGINAL SUBMITTAL IN DENIED
 DRAWERS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-18 Cont ID  
Sent By lmarchan Date 2015-12-15 Time 16:15 Rev Time 0.00
Received By lmarchan Date 2015-11-04 Time 09:09 Sent To FIRE
Notes
2015-12-15 18:40:00TO SHIRLEY.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-02-10 Cont ID  
Sent By ccole Date 2016-02-10 Time 16:29 Rev Time 0.00
Received By ccole Date 2016-02-10 Time 16:29 Sent To  
Notes
2016-02-10 16:34:41MECHANICAL PROVISOS
 PERMIT #15110125
 2/10/16
  
 1) A REVISION TO THE PLAN IS REQUIRED FOR GUARD RAILS
 AT ROOF EDGES WHERE SERVICEABLE EQUIPMENT IS WITHIN 10'
 OF THE EDGE.
 2) PROVIDE AT INSPECTION UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLIES REQUIRED FOR SEALING THE SUPPLY
 AND EXHAUST DUCT PENETRATIONS THROUGH THE FIRE-RATED
 EXTERIOR WALL BY ALLEYWAY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-02-01 Cont ID  
Sent By ccole Date 2016-02-01 Time 09:24 Rev Time 0.00
Received By ccole Date 2016-02-01 Time 09:24 Sent To  
Notes
2016-02-01 09:53:253RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110125
 2/1/2016
  
 1) THE ENGINEERING AND INSTALLATION DETAILS FOR THE
 SUBMITTED ROOF STAND PRODUCT APPROVAL HAVE BEEN UPDATED
 BY THE CERIFIYING ENGINEER FRANK BENNARDO P.E. PLEASE
 PROVIDE THE 2014 APPROVED FLORIDA PRODUCT APPROVAL FOR
 THE ALUMIMNUM ROOF STAND (INCLUDING THE COVER SHEET)
 WITH AN APPROVAL SIGNATURE ON THE DOCUMENT FROM THE
 ENGINEER OF RECORD ALLEN WEIDER P.E.
 2) AS PREVIOUSLY NOTED GUARDS ARE REQUIRED FOR THE
 MECHANICAL EQUIPMENT WITHIN 10' OF THE ROOF EDGE.
 PLEASE PROVIDE ENGINEERED PLANS AND SPECIFICATIONS FOR
 REVIEW.
 3) THE LETTER FROM EMERALD ENGINEERING MUST HAVE AN
 ORIGINAL SIGNATURE AND SEAL- COPIES OF THE ORIGINAL
 LETTER HAVE BEEN SUBMITTED. PLEASE NOTE THAT BY THE
 CONTENT OF THE LETTER, REVISIONS TO THE MAIN PLAN ARE
 REQUIRED BECAUSE OF THE RE-DESIGN OF THE KITCHEN HOOD
 AND EXHAUST SYSTEM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-04 Cont ID  
Sent By ccole Date 2015-12-29 Time 09:33 Rev Time 0.00
Received By ccole Date 2015-12-29 Time 09:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-09 Cont ID  
Sent By ccole Date 2015-12-09 Time 08:10 Rev Time 0.00
Received By ccole Date 2015-12-09 Time 06:57 Sent To  
Notes
2015-12-09 10:04:291ST REVIEW 2014 MECHANICAL
 PERMIT #15110125
 12/9/15
  
 1) THE HOOD 1A & 1B SUPPLY FAN AIR INLET (SF-1) SHALL
 NOT BE LOCATED IN AN ALLEY, AND NOT WITHIN THE REQUIRED
 10' CLEARANCE DISTANCE TO THE ADJACENT PROPERTY LINE-
 REFER TO SECTIONS 508.1 AND 401.4 FBC-14 MECHANICAL.
 2) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 ALL EXTERIOR FAN AND DUCT INSTALLATIONS, INCLUDING THE
 SUPPORT PLATFORMS AND BRACKET ASSEMBLIES IN THE ALLEY-
 SEE SECTION 301.5 AND PROVIDE THE WIND LOAD DESIGN
 CRITERIA ON THE PLANS AND COMPLETE DETAILS. PLEASE
 NOTE: A) SHOP DRAWINGS FOR ALL THE STRUCTURAL
 ASSEMBLIES SHALL BE REVIEWED AND APPROVED BY THE
 ENGINEER OF RECORD AND SUBMITTED TO THE BUILDING
 DEPARTMENT. B)WELDING CERTIFICATIONS SHALL BE ON-SITE
 AT TIME OF INSPECTION.
 3) PROVIDE UL TESTED AND APPROVED FIRE STOPPING
 ASSEMBLIES ON THE PLAN FOR THE DUCTS PENETRATING THE
 FIRE-RATED EXTERIOR WALL.
 4) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL APPLIANCES AND EQUIPMENT AND THE MINIMUM
 REQUIRED CLEARANCE DISTANCES FOR EXHAUST AND VENT
 OUTLETS, AND MECHANICAL AND GRAVITY AIR INTAKES- REFER
 TO SECTIONS 401.4, 501.3.1, AND 506.3.1. PLEASE NOTE A
 REVISION TO THE ORIGINAL MECHANICAL ROOF PLAN SHEET
 SUBMITTED UNDER THE PERMIT # 13060638 MAY BE REQUIRED
 FOR REVIEW AND FOR PUBLIC RECORD. SEE ALSO SECTION
 304.11: GUARDS MAY BE REQUIRED FOR EQUIPMENT WITHIN 10'
 OF A ROOF EDGE.
 5) PROVIDE AIR VELOCITY CALCULATIONS FOR THE EXHAUST
 DUCTS- SECTION 506.3.4.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status N Date 2016-02-11 Cont ID  
Sent By jwitmer Date 2016-02-11 Time 08:44 Rev Time 0.00
Received By jwitmer Date 2016-02-11 Time 08:44 Sent To  
Notes
2016-02-11 08:52:12I SPOKE WITH ANA MARIA APONTE THIS MORNING, THE ONLY
 CHANGE IN PLANS WAS AN ADDTIONAL HORIZONTAL BRACE TO
 THE EXHAUST FAN AND WIND CALCULATIONS FOR ANCHORAGE.
 SHE OK'ED ME WRITING THE SAME APPROVAL SHE WROTE ON
 01/22/2016.
 PROVISO: SCREENING SHALL BE PROVIDED ALONG THE SOUTH
 SIDE OF THE MECHANICAL EQUIPMENT THE SAME HEIGHT AS THE
 EQUIPMENT. JW 2/11/16

Review Stop Z ZONING
Rev No 2 Status P Date 2016-01-22 Cont ID  
Sent By aaponte Date 2016-01-20 Time 13:50 Rev Time 0.00
Received By aaponte Date 2016-01-20 Time 13:50 Sent To  
Notes
2016-01-20 13:51:32PROVISO: SREENING SHALL BE PROVIDED ON THE SOUTH SIDE
 OF THE MECHANICAL EQUIPMENT.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-12-15 Cont ID  
Sent By aaponte Date 2015-12-15 Time 18:38 Rev Time 0.00
Received By aaponte Date 2015-12-15 Time 18:38 Sent To  
Notes
2015-12-15 18:39:32THE MECHANICAL UNIT IS PROJECTING FROM THE ROOF LINE.
 PLEASE PROVIDE INFORMATION TO INDICATE HOW THE UNIT
 WILL BE SCREEN FROM VIEW. MECHANICAL UNIT SHALL BE
 SCREENED WITH AN ECLOSURE AS HIGH AS THE UNIT.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.