Plan Review Details - Permit 15110042
Plan Review Stops For Permit 15110042
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 10:50 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 10:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By skennedy Date 2015-11-05 Time 06:52 Rev Time 0.00
Received By skennedy Date 2015-11-05 Time 06:52 Sent To  
Notes
2015-11-05 17:34:451ST REVIEW: FBC 2014 5TH ED.
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW. YOU MAY CHOOSE TO SEND ME RESPONSES TO THESE
 COMMENTS VIA E-MAIL.
  
 PER THE MINIMUM PLAN REVIEW REQUIREMENTS FOUND IN FBC
 107, YOU MUST DECLARE THE CODE REFERENCE AND LEVEL OF
 WORK. FOR YOUR CONVENIENCE, THE APPLICABLE CODE IS: THE
 FBC 2014 5TH ED EXISTING BUILDING. IT SEEMS THE LEVEL
 OF WORK IS EITHER A REPAIR OR MORE LIKELY AN ALTERATION
 LEVEL I. PLEASE SEE SECTIONS 502 & 503 BELOW SO YOU MAY
 MAKE A DETERMINATION.
 SECTION 502 REPAIRS
  
 502.1 SCOPE.
 REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE PATCHING
 OR RESTORATION OR REPLACEMENT OF DAMAGED MATERIALS,
 ELEMENTS, EQUIPMENT OR FIXTURES FOR THE PURPOSE OF
 MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND CONDITION
 WITH RESPECT TO EXISTING LOADS OR PERFORMANCE
 REQUIREMENTS.
  
 502.2 APPLICATION.
 REPAIRS SHALL COMPLY WITH THE PROVISIONS OF CHAPTER 6.
  
 502.3 RELATED WORK.
 WORK ON NONDAMAGED COMPONENTS THAT IS NECESSARY FOR THE
 REQUIRED REPAIR OF DAMAGED COMPONENTS SHALL BE
 CONSIDERED PART OF THE REPAIR AND SHALL NOT BE SUBJECT
 TO THE PROVISIONS OF CHAPTER 7, 8, 9, 10 OR 11.
  
 SECTION 503 ALTERATION?LEVEL 1
  
 503.1 SCOPE.
 LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT
 OR THE COVERING OF EXISTING MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS,
 EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE.
  
 503.2 APPLICATION.
 LEVEL 1 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF
 CHAPTER 7.
  
 PLEASE ALSO INDICATE THE OCCUPANCY CLASSIFICATION AND
 TYPE OF CONSTRUCTION OF THE BUILDING AS DEFINED IN FBC
 CHAPTERS 3 & 6. FOR YOUR CONVENIENCE, THE OCCUPANCY
 CLASSIFICATION IS R-3 AND I BELIEVE THE CONSTRUCTION
 TYPE IS II-B. ALSO INDICATE THE BUILDING AS HAVING A
 FIRE SPRINKLER SYSTEM.
  
 ADDITIONALLY, YOU MUST PRINT YOUR NAME AND LICENSE
 NUMBER ON THE PLAN AND SIGN THE DRAWING PER FBC 107.2.1
 PLEASE ALSO PROVIDE A MORE COMPREHENSIVE SCOPE OF WORK.
 A COPY OF YOUR CONTRACT OR CONTRACTS MAY BE HELPFUL IF
 THEY CONTAIN A SCOPE OF WORK. ACCORDINGLY, IF YOU ARE
 REPLACING WALLS THAT AFFECT THE FIRE RATING PLEASE
 SPECIFY AND IF SUCH WALLS ARE THE RESPONSIBILITY OF THE
 HARBOR TOWERS CONDOMINIUM ASSOCIATION, PLEASE SPECIFY
 AND POTENTIALLY PROVIDE A SEPARATE PERMIT APPLICATION
 FOR THAT WORK IF YOU ARE CONTRACTED BY THEM. ALSO, IF
 ELECTRICAL FIXTURES, PLUMBING FIXTURES AND CABINETRY &
 TOPS ARE BEING REPLACED, INDICATE TO WHAT EXTENT AND IF
 THE LAYOUT IS TO BE ALTERED OR NOT. PLEASE IDENTIFY THE
 MATERIALS TO BE USED TO ASSURE COMPLIANCE WITH THE
 DESIGN PARAMETERS. ADDITIONALLY, IF INSTALLING A HARD
 FLOORING SURFACE, PROVIDE INFORMATION ON THE FLOORING
 AND SOUND INSULATION TO DEMONSTRATE COMPLIANCE WITH THE
 CRITERIA OF FBC SECTIONS BELOW:
  
 FBC 603.1 FLAME SPREAD
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 IF YOU HAVE ANY QUESTIONS, FEEL FREE TO CONTACT ME.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 10:50 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By skennedy Date 2015-11-06 Time 07:34 Rev Time 0.00
Received By skennedy Date 2015-11-06 Time 07:34 Sent To  
Notes
2015-11-06 07:36:301ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 PLEASE SEE BUILDING REVIEW COMMENTS. PLEASE PROVIDE A
 MORE COMPREHENSIVE SCOPE OF WORK OR ELECTRICAL PLAN.
 FBC 107
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 10:49 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 10:50 Rev Time 0.00
Received By skennedy Date 2015-11-02 Time 06:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 10:50 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 10:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By skennedy Date 2015-11-06 Time 07:34 Rev Time 0.00
Received By skennedy Date 2015-11-06 Time 07:34 Sent To FIRE
Notes
2015-11-06 07:37:431ST REVIEW: FBC 2014 5TH ED.
  
 PLEASE SEE BUILDING REVIEW COMMENTS. PLEASE PROVIDE A
 MORE COMPREHENSIVE SCOPE OF WORK OR MECHANICAL PLAN.
 FBC 107
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 10:50 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 10:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By skennedy Date 2015-11-06 Time 07:34 Rev Time 0.00
Received By skennedy Date 2015-11-06 Time 07:34 Sent To  
Notes
2015-11-06 07:37:181ST REVIEW: FBC 2014 5TH ED.
  
 PLEASE SEE BUILDING REVIEW COMMENTS. PLEASE PROVIDE A
 MORE COMPREHENSIVE SCOPE OF WORK OR PLUMBING PLAN. FBC
 107
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]