2015-11-05 17:34:45 | 1ST REVIEW: FBC 2014 5TH ED. |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. YOU MAY CHOOSE TO SEND ME RESPONSES TO THESE |
| COMMENTS VIA E-MAIL. |
| |
| PER THE MINIMUM PLAN REVIEW REQUIREMENTS FOUND IN FBC |
| 107, YOU MUST DECLARE THE CODE REFERENCE AND LEVEL OF |
| WORK. FOR YOUR CONVENIENCE, THE APPLICABLE CODE IS: THE |
| FBC 2014 5TH ED EXISTING BUILDING. IT SEEMS THE LEVEL |
| OF WORK IS EITHER A REPAIR OR MORE LIKELY AN ALTERATION |
| LEVEL I. PLEASE SEE SECTIONS 502 & 503 BELOW SO YOU MAY |
| MAKE A DETERMINATION. |
| SECTION 502 REPAIRS |
| |
| 502.1 SCOPE. |
| REPAIRS, AS DEFINED IN CHAPTER 2, INCLUDE THE PATCHING |
| OR RESTORATION OR REPLACEMENT OF DAMAGED MATERIALS, |
| ELEMENTS, EQUIPMENT OR FIXTURES FOR THE PURPOSE OF |
| MAINTAINING SUCH COMPONENTS IN GOOD OR SOUND CONDITION |
| WITH RESPECT TO EXISTING LOADS OR PERFORMANCE |
| REQUIREMENTS. |
| |
| 502.2 APPLICATION. |
| REPAIRS SHALL COMPLY WITH THE PROVISIONS OF CHAPTER 6. |
| |
| 502.3 RELATED WORK. |
| WORK ON NONDAMAGED COMPONENTS THAT IS NECESSARY FOR THE |
| REQUIRED REPAIR OF DAMAGED COMPONENTS SHALL BE |
| CONSIDERED PART OF THE REPAIR AND SHALL NOT BE SUBJECT |
| TO THE PROVISIONS OF CHAPTER 7, 8, 9, 10 OR 11. |
| |
| SECTION 503 ALTERATION?LEVEL 1 |
| |
| 503.1 SCOPE. |
| LEVEL 1 ALTERATIONS INCLUDE THE REMOVAL AND REPLACEMENT |
| OR THE COVERING OF EXISTING MATERIALS, ELEMENTS, |
| EQUIPMENT, OR FIXTURES USING NEW MATERIALS, ELEMENTS, |
| EQUIPMENT, OR FIXTURES THAT SERVE THE SAME PURPOSE. |
| |
| 503.2 APPLICATION. |
| LEVEL 1 ALTERATIONS SHALL COMPLY WITH THE PROVISIONS OF |
| CHAPTER 7. |
| |
| PLEASE ALSO INDICATE THE OCCUPANCY CLASSIFICATION AND |
| TYPE OF CONSTRUCTION OF THE BUILDING AS DEFINED IN FBC |
| CHAPTERS 3 & 6. FOR YOUR CONVENIENCE, THE OCCUPANCY |
| CLASSIFICATION IS R-3 AND I BELIEVE THE CONSTRUCTION |
| TYPE IS II-B. ALSO INDICATE THE BUILDING AS HAVING A |
| FIRE SPRINKLER SYSTEM. |
| |
| ADDITIONALLY, YOU MUST PRINT YOUR NAME AND LICENSE |
| NUMBER ON THE PLAN AND SIGN THE DRAWING PER FBC 107.2.1 |
| PLEASE ALSO PROVIDE A MORE COMPREHENSIVE SCOPE OF WORK. |
| A COPY OF YOUR CONTRACT OR CONTRACTS MAY BE HELPFUL IF |
| THEY CONTAIN A SCOPE OF WORK. ACCORDINGLY, IF YOU ARE |
| REPLACING WALLS THAT AFFECT THE FIRE RATING PLEASE |
| SPECIFY AND IF SUCH WALLS ARE THE RESPONSIBILITY OF THE |
| HARBOR TOWERS CONDOMINIUM ASSOCIATION, PLEASE SPECIFY |
| AND POTENTIALLY PROVIDE A SEPARATE PERMIT APPLICATION |
| FOR THAT WORK IF YOU ARE CONTRACTED BY THEM. ALSO, IF |
| ELECTRICAL FIXTURES, PLUMBING FIXTURES AND CABINETRY & |
| TOPS ARE BEING REPLACED, INDICATE TO WHAT EXTENT AND IF |
| THE LAYOUT IS TO BE ALTERED OR NOT. PLEASE IDENTIFY THE |
| MATERIALS TO BE USED TO ASSURE COMPLIANCE WITH THE |
| DESIGN PARAMETERS. ADDITIONALLY, IF INSTALLING A HARD |
| FLOORING SURFACE, PROVIDE INFORMATION ON THE FLOORING |
| AND SOUND INSULATION TO DEMONSTRATE COMPLIANCE WITH THE |
| CRITERIA OF FBC SECTIONS BELOW: |
| |
| FBC 603.1 FLAME SPREAD |
| |
| FBC 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| IF YOU HAVE ANY QUESTIONS, FEEL FREE TO CONTACT ME. |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |
| (561) 805-6710 |
| [email protected] |
| |
| |