Plan Review Details - Permit 15110039
Plan Review Stops For Permit 15110039
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-11 Cont ID  
Sent By jgomez Date 2015-12-11 Time 08:50 Rev Time 0.00
Received By jgomez Date 2015-12-11 Time 08:41 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-11-24 Cont ID  
Sent By jgomez Date 2015-11-24 Time 10:21 Rev Time 0.00
Received By jgomez Date 2015-11-24 Time 09:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-14 Cont ID  
Sent By mvaldes Date 2015-12-14 Time 08:31 Rev Time 0.00
Received By mvaldes Date 2015-12-14 Time 08:31 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-11 Cont ID  
Sent By skennedy Date 2015-12-11 Time 08:58 Rev Time 0.00
Received By skennedy Date 2015-12-11 Time 08:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-11-05 Cont ID  
Sent By ppetty Date 2015-11-05 Time 15:14 Rev Time 0.00
Received By ppetty Date 2015-11-05 Time 15:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-11 Cont ID  
Sent By skennedy Date 2015-12-11 Time 08:59 Rev Time 0.00
Received By skennedy Date 2015-11-25 Time 15:07 Sent To  
Notes
2015-11-25 15:08:04R11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-24 Cont ID  
Sent By jgomez Date 2015-11-24 Time 10:22 Rev Time 0.00
Received By jgomez Date 2015-11-02 Time 15:36 Sent To  
Notes
2015-11-02 15:36:52R11

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-03 Cont ID  
Sent By gjohnson Date 2015-12-03 Time 13:58 Rev Time 0.00
Received By gjohnson Date 2015-12-03 Time 13:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-04 Cont ID  
Sent By tklarge Date 2015-11-04 Time 05:24 Rev Time 0.00
Received By tklarge Date 2015-11-04 Time 04:49 Sent To  
Notes
2015-11-04 05:23:401) SUBMIT AN EXISTING FLOOR PLAN FOR THE 1ST & 2ND
 FLOORS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) NOTE #13 ON SHT. A.03 REFERS TO THE INSTALLATION OF
 A BACKFLOW PREVENTION DEVICE BUT NOTHING IS SHOWN.
 CLARIFY.
 3) NOTE #15 ON A.03 REFERS TO A 1 INCH STUB OUT FOR A
 FUTURE POOL BUT NOTHING IS SHOWN ON THE PLANS. CLARIFY.
 4)NOTE #18 ON A.03 REFERS TO GAS PIPING/GAS METER BUT
 THERE IS NO GAS PIPNG SHOWN. WILL ANY WORK BE DONE ON
 THE GAS SYSTEM? CLARIFY.
 5) NOTE #25 ON A.03 REFERS TO THE INSTALLATION OF TWO
 TANKLESS WATER HEATERS BUT NOTHING IS SHOWN ON THE
 PLANS. IF THE TANKLESS WATER HEATERS ARE BEING
 INSTALLED, SUBMIT MANUF. SPECIFICATIONS FOR THE WATER
 HEATERS AND RELATED PLUMBING/GAS DRAWINGS. SHOW THE
 LOCATION ON THE PLANS. CLARIFY.
 6) NOTE # 26 ON A.03 REFERS TO A RECIRCULATING PUMP.
 NOTHING IS ON THE PLANS. CLARIFY.
 7) NOTE # 27 REFERS TO DRAIN PAN & VACUUM RELIEF VALVE
 FOR WATER HEATER. IF NEW TANKLESS HEATERS ARE BEING
 INSTALLED THIS IS NOT REQD. SHOW THE LOCATION OF THE
 EXISTING WATER HEATER ON THE PLANS.
 8) THE SANITARY RISER ON A.03 IS NOT CLOSE TO BEING
 CODE COMPLIANT.IF NO CHANGES ARE BEING MADE TO THE
 SANITARY SYSTEM, DELETE THE RISER DIAGRAM FROM THE
 DRAWING.
 9) INDICATE ON THE PLAN IF ANY OF THE PLUMBING
 FIXTURES/GAS APPLIANCES ARE BEING RELOCATED FROM THEIR
 PRESENT LOCATION OR ARE BEING REPLACED IN THEIR PRESENT
 LOCATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  