Plan Review Details - Permit 15110034
Plan Review Stops For Permit 15110034
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 15:40 Rev Time 0.00
Received By albarran Date 2015-12-28 Time 12:04 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 14:14 Rev Time 0.00
Received By albarran Date 2015-11-24 Time 14:07 Sent To I
Notes
2015-11-24 14:16:38SEE COMMENTS FOR THE PREVIOUS REVIEW WHICH HAVE NOT
 BEEN ADDRESSED.
 PURSUANT TO FL ?553.80, THE 4TH SUBMITTAL FOR A PERMIT
 WHICH REFLECTS FAILURE TO CORRECT A DEFICIENCY
 PREVIOUSLY SPECIFICALLY AND CONSISTENTLY IDENTIFIED ON
 ALL PRIOR SUBMITTALS MUST RESULT IN THE ASSESSMENT OF A
 PENALTY OF 3 TIMES THE PLAN REVIEW FEE IN ADDITION TO
 THE NORMAL FEE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By albarran Date 2015-11-05 Time 12:40 Rev Time 0.00
Received By albarran Date 2015-11-05 Time 12:35 Sent To I
Notes
2015-11-05 12:46:42THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE 2011 EDITION
 OF THE NEC, (NATIONAL ELECTRICAL CODE); THE 5TH EDITION
 OF THE 2014 FBC, (FLORIDA BUILDING CODE) AS APPLICABLE
 AND BELOW ARE THE DEFICIENCIES NOTED.
  
 1. THESE DRAWINGS BEING THAT THEY ARE FOR THE ACTUAL
 INSTALLATION OF THE HOOD SYSTEM AND THE ASSOCIATED FAN
 MOTORS WILL REQUIRE IN ADDITION TO THE A SITE SPECIFIC
 WIRING DIAGRAM YOU WILL HAVE TO SUBMIT SPECS FOR BOTH,
 THE EXHAUST AND MAKE UP AIR BLOWER MOTORS.
 2. YOU WILL PROVIDE A CIRCUIT DIRECTORY OF THE PANEL
 WHERE THESE MOTORS ARE BEING SERVED FROM.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-11-19 Cont ID  
Sent By scaldero Date 2015-11-19 Time 09:49 Rev Time 0.00
Received By scaldero Date 2015-11-19 Time 09:48 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-11-03 Cont ID  
Sent By albarran Date 2015-11-05 Time 12:48 Rev Time 0.00
Received By scaldero Date 2015-11-03 Time 15:15 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 15:42 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-12-28 15:43:5012/28/15 THIS PERMIT PASSED ALL REVIEWS AND IS READY
 FOR ISSUANCE. LORI NOTIFIED VIA EMAIL. SENT TO SMALL
 READY BIN "H". MA

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 15:12 Rev Time 0.00
Received By albarran Date 2015-12-23 Time 15:03 Sent To  
Notes
2015-12-28 15:14:1012/28/15 CONTACTED CG TO ADVISE THAT THIS HAD ONCE
 AGAIN FAILED MULTIPLE REVIEWS. GC IS OUT OF TOWN AND
 WILL ADDRESS THIS AFTER THE HOLIDAYS. SENT TO SMALL
 DENIED BIN "P". MA

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-11-24 Cont ID  
Sent By albarran Date 2015-11-24 Time 14:19 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-11-24 14:19:0611/24/15 FAILED THE ELECTRICAL REVIEW. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "H". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-19 Cont ID  
Sent By ccole Date 2015-11-19 Time 16:38 Rev Time 0.00
Received By ccole Date 2015-11-16 Time 15:36 Sent To  
Notes
2015-11-16 15:36:10RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-05 Cont ID  
Sent By albarran Date 2015-11-05 Time 12:46 Rev Time 0.00
Received By albarran Date 2015-11-02 Time 14:56 Sent To  
Notes
2015-11-05 12:47:5811/5/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "H". MA

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-12-28 Cont ID  
Sent By albarran Date 2015-12-28 Time 15:14 Rev Time 0.00
Received By ccole Date 2015-12-28 Time 08:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-19 Cont ID  
Sent By ccole Date 2015-11-19 Time 16:36 Rev Time 0.00
Received By ccole Date 2015-11-19 Time 16:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By ccole Date 2015-11-05 Time 09:16 Rev Time 0.00
Received By ccole Date 2015-11-05 Time 09:16 Sent To  
Notes
2015-11-05 09:37:511ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15110034
 11/5/2015
  
 1) PROVIDE AN AIR VELOCITY CALCULATION FOR THE NEW
 GREASE DUCT- SECTION 506.3.4.
 2) SHOW COMPLIANCE WITH SECTION 508.1.1 MAKEUP AIR
 TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10?F
 (6?C) EXCEPT WHERE THE ADDED HEATING AND COOLING LOADS
 OF THE MAKEUP AIR DO NOT EXCEED THE CAPACITY OF THE
 HVAC SYSTEM.
 3) SHOW COMPLIANCE WITH SECTION 507.9 CLEARANCES FOR
 TYPE I HOOD.
 A TYPE I HOOD SHALL BE INSTALLED WITH A CLEARANCE TO
 COMBUSTIBLES OF NOT LESS THAN 18 INCHES (457 MM).
 EXCEPTION: CLEARANCE SHALL NOT BE REQUIRED FROM GYPSUM
 WALLBOARD OR 1/2-INCH (12.7 MM) OR THICKER CEMENTITIOUS
 WALLBOARD ATTACHED TO NONCOMBUSTIBLE STRUCTURES
 PROVIDED THAT A SMOOTH, CLEANABLE, NONABSORBENT AND
 NONCOMBUSTIBLE MATERIAL IS INSTALLED BETWEEN THE HOOD
 AND THE GYPSUM OR CEMENTITIOUS WALLBOARD OVER AN AREA
 EXTENDING NOT LESS THAN 18 INCHES (457 MM) IN ALL
 DIRECTIONS FROM THE HOOD.
 4) PROVIDE A SUBMITTAL FOR THE DUCT WRAP WITH A REVIEW
 AND APPROVAL STAMP FROM THE DESIGN PROFESSIONAL OF
 RECORD.
 5) SHEET 5: PROVIDE THE CLEARANCE DISTANCE MEASURES
 FROM THE GREASE DUCT TERMINATION CAP TO ADJACENT
 BUILDINGS, ADJACENT PROPERTY LINES, AND PARTS OF THE
 SAME OR CONTIGUOUS BUILDING- SECTION 506.3.13.3
 6) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 TIE DOWN OF THE NEW ROOFTOP EXHAUST AND SUPPLY FANS AND
 CURB ADAPTERS- SECTION 301.15. THE ENGINEER OF RECORD
 SHALL PROVIDE WIND DESIGN CRITERIA, DESIGN PRESSURES,
 AND COMPLETE DETAILS FOR INSTALLATION, INCLUDING
 REVIEWED AND APPROVED SUBMITTALS FOR THE CURB ADAPTERS,
 AND REVIEWED AND APPROVED NOA'S FOR THE FANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  