Plan Review Details - Permit 15101054
Plan Review Stops For Permit 15101054
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-23 Cont ID  
Sent By skennedy Date 2015-11-23 Time 09:08 Rev Time 0.00
Received By skennedy Date 2015-11-23 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By cthroop Date 2015-11-03 Time 13:52 Rev Time 0.00
Received By cthroop Date 2015-11-03 Time 13:52 Sent To  
Notes
2015-11-03 13:54:58CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 WHEN INSTALLING A HARD FLOORING SURFACE, PROVIDE
 INFORMATION ON THE FLOORING AND SOUND INSULATION TO
 DEMONSTRATE COMPLIANCE WITH THE CRITERIA OF FBC
 SECTIONS BELOW:
  
 FBC 603.1 FLAME SPREAD
  
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-11-21 Cont ID  
Sent By skennedy Date 2015-11-21 Time 10:02 Rev Time 0.00
Received By skennedy Date 2015-11-21 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By skennedy Date 2015-11-03 Time 13:54 Rev Time 0.00
Received By skennedy Date 2015-11-03 Time 13:54 Sent To  
Notes
2015-11-03 14:12:541ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 FBC 107 PROVIDE MINIMUM INFORMATION AS SPECIFIED BELOW:
  
 PLEASE SPECIFY WHICH MODEL OF THE INSTANT HOT WATER
 HEATER IS PROPOSED AND VERIFY THAT THE EXISTING
 CONDUCTORS AND OCP ARE ADEQUATELY SIZED. THIS MATTER
 CAN BE HANDELED BY AN EMAIL TRANSMITTAL OR YOU MAY
 ELECT TO ALLOW THE ELECTRICIAN OF RECORD TO ADDRESS THE
 MATTER PRIOR TO OR DURING THE INSPECTIOM.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-23 Cont ID  
Sent By skennedy Date 2015-11-23 Time 09:08 Rev Time 0.00
Received By skennedy Date 2015-11-21 Time 10:02 Sent To  
Notes
2015-11-21 10:03:16RESPONSE SUBMITTED VIA EMAIL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-03 Cont ID  
Sent By cthroop Date 2015-11-03 Time 13:53 Rev Time 0.00
Received By cthroop Date 2015-10-29 Time 15:09 Sent To P
Notes
2015-10-30 15:10:13GJOHNSON DESK

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-23 Cont ID  
Sent By skennedy Date 2015-11-23 Time 09:09 Rev Time 0.00
Received By skennedy Date 2015-11-23 Time 09:09 Sent To  
Notes
2015-11-23 09:10:01A PERMIT IS REQUIRED FOR THE WATWER HEATER REPLACEMENT.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-11-02 Cont ID  
Sent By cthroop Date 2015-11-03 Time 13:53 Rev Time 0.00
Received By gjohnson Date 2015-11-02 Time 13:34 Sent To  
Notes
***NONE***