Plan Review Details - Permit 15100875
Plan Review Stops For Permit 15100875
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-28 Cont ID  
Sent By ccole Date 2015-10-28 Time 17:40 Rev Time 0.00
Received By ccole Date 2015-10-28 Time 14:52 Sent To  
Notes
2015-10-28 14:52:43RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-27 Cont ID  
Sent By ccole Date 2015-10-27 Time 13:34 Rev Time 0.00
Received By ccole Date 2015-10-23 Time 16:16 Sent To  
Notes
2015-10-23 16:16:30ROUTED TO MECHANICAL $5000 & UNDER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-10-28 Cont ID  
Sent By ccole Date 2015-10-28 Time 17:40 Rev Time 0.00
Received By ccole Date 2015-10-28 Time 17:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-27 Cont ID  
Sent By ccole Date 2015-10-27 Time 13:34 Rev Time 0.00
Received By ccole Date 2015-10-27 Time 13:34 Sent To  
Notes
2015-10-27 13:37:111ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100875
 10/27/15
  
 1) THE DESIGN PROFESSIONAL OF RECORD HAS NOT PROVIDED
 COMPLETE WIND LOAD DESIGN CRITERIA, OR COMPLETE DETAILS
 FOR INSTALLATION OF THE EXTERIOR EXHAUST FAN. REFER TO
 SECTION R301.2.1, FBC-14 RESIDENTIAL AND REVISE THE
 PLAN TO BE IN COMPLIANCE. PROVIDE THE FOLLOWING: A)
 BASIC WIND SPEED, EXPOSURE CATEGORY, HEIGHT AND
 ADJUSTMENT ADJUSTMENT COEEFICIENTS, DESIGN PRESSURES
 ETC.
 B) INDICATE THE TYPE, SIZE, AND QUANTITIES OF ANCHORS
 FOR MOUNTING THE EXHAUST FAN TO THE WALL.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE HOOD,
 THE CHARBROILER, AND THE EXHAUST FAN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  