Plan Review Details - Permit 15100819
Plan Review Stops For Permit 15100819
Review Stop G GAS REVIEW
Rev No 3 Status F Date 2015-12-06 Cont ID  
Sent By tklarge Date 2015-12-06 Time 05:58 Rev Time 0.00
Received By tklarge Date 2015-12-06 Time 05:30 Sent To  
Notes
2015-12-06 05:30:151) THE GAS HEATER SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82%.THE SUBMITTED SPECIFICATION SHEET
 DOES NOT SHOW THIS REQUIREMENT. SUBMIT POOL HEATER
 SPECS THAT SHOW COMPLIANCE. 2014 FBC-ENERGY CODE
 SEC.R403.9.1.1.2ND REQUEST
 2) GAS POOL HEATERS SHALL NOT HAVE CONTINUOUSLY BURNING
 PILOT LIGHTS.2014 FBC-ENERGY CODE SEC.R403.9.1.1.
 SUBMIT SPECIFICATIONS THAT SHOW COMPLIANCE. 2ND
 REQUEST.
 3) IDENTIFY THE MODEL OF THE POOL HEATER TO BE
 INSTALLED ON THE MANUF. SPECIFICATIONS.2ND REQUEST
 4) THE SUBMITTED GAS DRAWING SHOWS 3 HEATERS: 2
 "HEATERS" @ 400,000 BTU'S AND ONE POOL HEATER AT
 250,000 BTU'S. WHAT ARE THE TWO "HEATERS"? IF THEY ARE
 POOL HEATERS IDENTIFY THEM AS SUCH AND WHY ARE THERE 3
 HEATERS WHEN THE POOL PLANS CALL OUT ONE.
 5) THE GAS PLAN DOES NOT SHOW THE RANGE AND BBQ AS
 EXISTING IF THAT IS WHAT THEY ARE. IDENTIFY ON THE PLAN
 IF THEY ARE NEW AND TO BE INSTALLED UNDER THIS GAS
 PERMIT OR IF THEY ARE EXISTING. WPB AMEND. TO FBC SEC.
 107.2.1.
 6) IDENTIFY THE BBQ OUTLET ON THE GAS RISER. WPB AMEND.
 TO FBC SEC. 107.2.1.
 7) SHOW THE BTU LOAD OF EACH APPLIANCE AT THE GAS
 OUTLET. THE PROPER SIZING FOR THE INDIVIDUAL SECTIONS
 OF PIPE CANNOT BE DETERMINED TO BE COMPLIANT WITHOUT
 THIS INFORMATION.WPB AMEND. TO FBC SEC. 107.2.1.
 8) THE SUBMITTED GAS PLAN SHOWS ONE POOL HEATER AS
 250,000 BTU'S AND TWO OTHER " HEATERS " AS 400,000
 BTU'S BUT THE POOL PLANS CALL OUT A 125,000 BTU GAS
 POOL HEATER AND ONE HEAT PUMP. AT THIS POINT, I HAVE
 ABSOLUTELY NO IDEA WHAT IS BEING INSTALLED ON THIS
 POOL. THE CONTRACTOR NEEDS TO COME IN AND STRAIGHTEN
 OUT THIS CONVOLUTED SUBMISSION AND SUBMIT TWO COPIES OF
 DOCUMENTS THAT SATISFY THE GAS REVIEW COMMENTS.
  
 ALSO, SEE PERMIT APPLICATION #15100811
  
  
 ** NOTE: DO NOT SUBMIT CORRECTIONS FOR THE GAS UNLESS
 ALL ITEMS ARE CORRECTED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-11-16 Cont ID  
Sent By tklarge Date 2015-11-16 Time 06:05 Rev Time 0.00
Received By tklarge Date 2015-11-13 Time 06:54 Sent To  
Notes
2015-11-13 12:53:241) INDICATE ON THE GAS PLAN THE SPECIFIC GAS SIZING
 TABLES THAT WERE USED IN THE SIZING OF THE GAS SYSTEM.
 SUBMIT COPIES OF THE TABLES USED IF DIFFERENT THAN IN
 THE 2014 FBC-FUEL GAS. 2ND REQUEST.
 2) IS THE POOL HEATER THE ONLY GAS APPLIANCE BEING
 INSTALLED UNDER THIS PERMIT OR ARE ALL THESE APPLIANCES
 BEING INSTALLED UNDER THIS GAS APPLICATION? IF THE POOL
 HEATER IS THE ONLY NEW APPLIANCE, MARK ALL THE OTHER
 APPLIANCES AS "EXISTING". ALSO, THE BBQ IS SHOWN ON THE
 LIST BUT NOT ON THE GAS DRAWING. CLARIFY.2ND REQUEST.
 3) SIZE THE BRANCH LINE TO THE RANGE AND ALSO FOR THE
 HEATER BY THE METER.2ND REQUEST.
 4) IF ALL APPLIANCES ARE BEING INSTALLED AT THIS TIME,
 SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL APPLIANCES.
 APPLIANCES SHALL BE LISTED AND LABELELD 2014 FBC-RES.
 SEC.G2404.3.2ND REQUEST.
 5) SIZE THE BRANCH LINE TO THE RANGE AND ALSO FOR THE
 HEATER BY THE METER.2ND REQUEST.
  
  
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-11-12 Cont ID  
Sent By tklarge Date 2015-10-27 Time   Rev Time  
Received By tklarge Date 2015-10-27 Time   Sent To  
Notes
2015-10-27 09:02:341) SIZE ALL SECTIONS OF THE GAS PIPING DIAGRAM AND
 CLEARLY SHOW THE TYPE OF PIPE BEING INSTALLED.WPB
 AMEND. TO FBC SEC. 107.2.1.
 2) THE GAS DRAWING IS ILLEGIBLE.SUBMIT A GAS RISER THAT
 IS CLEAR IN DETAIL AND SHOWS ALL PIPE SIZES, PIPE
 MATERIALS AND BTU LOAD OF EACH APPLIANCE. WPB AMEND. TO
 FBC SEC. 107.2.1.
 3) THE GAS HEATER SHALL HAVE A MINIMUM THERMAL
 EFFICIENCY OF 82%.THE SUBMITTED SPECIFICATION SHEET
 DOES NOT SHOW THIS REQUIREMENT. SUBMIT POOL HEATER
 SPECS THAT SHOW COMPLIANCE. 2014 FBC-ENERGY CODE
 SEC.R403.9.1.1.
 4) GAS POOL HEATERS SHALL NOT HAVE CONTINUOUSLY BURNING
 PILOT LIGHTS.2014 FBC-ENERGY CODE SEC.R403.9.1.1.
 SUBMIT SPECIFICATIONS THAT SHOW COMPLIANCE.
 5) IDENTIFY THE MODEL OF THE POOL HEATER ON THE MANUF.
 SPECIFICATIONS THAT IS TO BE INSTALLED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-16 Cont ID  
Sent By tklarge Date 2015-11-16 Time 06:05 Rev Time 0.00
Received By tklarge Date 2015-11-12 Time 17:21 Sent To G
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved