2015-10-24 03:01:14 | 1) THE NOTES ON THE PLAN STATE THIS IS A 2 PSI SYSTEM |
| BUT THE TABLE YOU ARE REFERENCING FROM THE 2014 |
| FBC-RES. ON THE PLANS IS FOR LESS THAN 2 PSI WITH A |
| PRESSURE DROP OF 3.0 IN. W.C.. CLARIFY. |
| 2) IF IT IS A 2 PSI SYSTEM, INDICATE THE CORRECT SIZING |
| TABLE FOR THE SYSTEM ON THE PLAN.2014 FBC-FUEL GAS. |
| SEC.402.2. |
| 3) SIZE ALL SECTIONS OF THE PIPE ON THE RISER DIAGRAM. |
| THE ONLY PIPE THAT IS SIZED IS THE 3/4" CSST TO THE |
| RANGE, 2014 FGC SEC. 402.2. |
| 4) SUBMIT MANUF. SPECS FOR THE DRYER AND RANGE. |
| APPLIANCES SHALL BE LISTED AND LABELED. SEC. 301.3. |
| 5) IF THE DRYER IS LOCATED IN A CLOSET, MAKEUP AIR |
| SHALL BE PROVIDED. AN OPENING HAVING AN AREA OF NOT |
| LESS THAN 100 SQUARE INCHES FOR MAKEUP AIR SHALL BE |
| PROVIDED IN THE CLOSET ENCLOSURE OR MAKEUP AIR SHALL BE |
| PROVIDED BY OTHER APPROVED MEANS. 2014 FGC SEC.304.1, |
| 614.5. SHOW THE LOCATION OF THE DRYER ON THE FLOOR |
| PLANS. |
| 6) SHOW THE LOCATION OF ALL STEP-DOWN REGULATORS IF IT |
| IS A 2 PSI SYSTEM. SHOW THE LOCATION OF THE REGULATOR |
| VENTS AND THE SIZES.COMPLY W/ 2014 FGC SEC.410.2. & |
| 410.3. |
| 7) IF THE TANKLESS WATER HEATER IS REPLACING AN |
| EXISTING STORAGE TANK TYPE, INDICATE SUCH ON THE PLANS. |
| IF THE TANKLESS IS IN ADDITION TO AN EXISTING WATER |
| HEATER, SUBMIT A WATER RISER DIAGRAM SHOWING WHERE THE |
| COLD WATER SUPPLY IS COMING FROM.MINIMUM COLD WATER |
| SUPPLY SHALL BE 3/4". |
| 8) A SEPARATE PERMIT IS REQUIRED FOR ANY RELATED |
| ELECTRICAL WORK THAT WILL BE DONE. |
| |