Plan Review Details - Permit 15100773
Plan Review Stops For Permit 15100773
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-12-22 Cont ID  
Sent By skennedy Date 2015-12-22 Time 08:09 Rev Time 0.00
Received By skennedy Date 2015-12-21 Time 17:00 Sent To  
Notes
2015-12-22 08:09:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100773
 ADD: 328 FERN ST.
 CONT: L. J. SHEEHAN, INC.
 TEL: (561)223-2750
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUESDAY. DECEMBER 22, 2015
 ACTION: APPROVED WITH CONDITIONS
  
 A REVISION IS REQUIRED TO ADDRESS REVIEW COMMENT 7
 BELOW FROM THE PREVIOUS REVIEW. BY E-MAIL RESPONSE,
 ARCHITECT OF RECORD, RICK GONZALEZ HAS AGREEDED TO THIS
 CONDITIONAL APPROVAL.
  
 7) SHEET A2.01 INDICATES A DETAIL 4 /A5.10 THE SERVICE
 COUNTER TO BE 40 INCHES TALL. PLEASE SHOW COMPLIANCE
 WITH THE 2014 ACCESSIBILITY CODE EITHER 904.4.1PARALLEL
 APPROACH OR 904.4.2 FRONTAL APPROACH.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-09 Cont ID  
Sent By jwitmer Date 2015-11-09 Time 11:30 Rev Time  
Received By jwitmer Date 2015-11-07 Time 10:30 Sent To  
Notes
2015-11-09 11:28:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100773
 ADD: 328 FERN ST.
 CONT: L. J. SHEEHAN, INC.
 TEL: (561)223-2750
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV.09/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A WRITTEN RESPONSE TO WHAT IS THE
 CORRECT ADDRESS. THE CITY OF WEST PALM BEACH AND THE P.
 B. C. PROPERTY APPRAISERS OFFICE BOTH LIST UNDER THE
 PCN 74-43-43-21-01-009-0070 AS 326 FERN ST. THE PLANS
 ALL HAVE THE ADDRESS AS 326 FERN ST. THE PERMIT
 APPLICATION HAS THE ADDRESS AS 328 FERN ST. THE CITY
 ALSO HAS A TENANT ADDRESS OF 328 FERN ST. IF THIS
 PROJECT IS GOING TO USE THE ADDRESS OF 328 FERN ST. THE
 PLANS WILL NEED TO BE REPRINTED TO THE CORRECT ADDRESS.
 IF THE 326 FERN ST. THEN A TENANT SUITE NUMBER WILL
 NEED TO BE DETERMINED. FOR A LIST OF EXISTING SUITE
 NUMBERS FOR THE 1ST FLOOR YOU WOULD NEED TO CONTACT
 SANDY WURAFTIC AT 561-805-6688.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 ELECTRONIC MEDIA DOCUMENTS SHALL BE
 SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED.
  
 2) NOTICE, NO ACTION IS REQUIRED. THIS IS A RESTAURANT,
 A BUSINESS OCCUPANCY, OCCUPANT LOAD OF LESS THAN 50, NO
 IMPACT FEES ARE DUE, P. B. C. IMPACT FEES OFFICE.
 IMPACT FEES WERE PAID FOR RETAIL (MERCANTILE
 OCCUPANCY). TRACKING NUMBER MU-2013-023597-0000.
  
 3) SHEET S-1 PROVIDES THE WIND DESIGN CRITERIA TO BE
 UNDER THE 2014 FBC-B, 5TH EDITION BUT THE PRESSURES
 SEEM A LITTLE LOW FOR A MEAN ROOF HEIGHT OF 87 FEET.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS & MULLIONS.
  
 5) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 6) SHEET A-0.00 SHOWS DOOR TO RESTROOMS 106 & 107.
 SHEET A-6.01 THE DOOR SCHEDULE INDICATES THESE DOORS TO
 BE 2'-10" IN WIDTH. A 3'-0" DOOR WIDTH IS REQUIRED TO
 OBTAIN A 32 INCH CLEAR OPENING. 2014 FBC-B 1008.1.1
 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 7) SHEET A2.01 INDICATES A DETAIL 4 /A5.10 THE SERVICE
 COUNTER TO BE 40 INCHES TALL. PLEASE SHOW COMPLIANCE
 WITH THE 2014 ACCESSIBILITY CODE EITHER 904.4.1PARALLEL
 APPROACH OR 904.4.2 FRONTAL APPROACH.
  
 8) SHEET A2.01 ALSO WILL NEED TO SHOW THE HEIGHT FOR
 ACCESSIBLE TABLES IN COMPLIANCE WITH 2014 ACCESSIBILITY
 CODE 902.3. PLEASE SHOW COMPLIANCE WITH 226.1 AND
 226.2.
  
 9) PLEASE NOTE SHEET M5.1 THE NEW ROOF TOP UNIT C-2
 WIND DESIGN CRITERIA APPEARS TO BE FOR A BUILDING ,
 THAN 60 FEET TALL. THIS BUILDING MEAN ROOF HEIGHT IS 87
 FEET IN HEIGHT. ALSO NOTE SHEET M1.2 INDICATES THIS
 UNIT IS TO TIE DOWN TO A EXISTING ROOF RACK NOT A CURB
 AS INDICATED ON M5.1.
 M- 301.15 WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST THE WIND PRESSURES
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By albarran Date 2015-12-21 Time 15:30 Rev Time 0.00
Received By albarran Date 2015-12-21 Time 14:25 Sent To B
Notes
2015-12-21 15:32:12ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-01 Cont ID  
Sent By albarran Date 2015-12-01 Time 15:12 Rev Time 0.00
Received By albarran Date 2015-12-01 Time 13:38 Sent To I
Notes
2015-12-01 15:13:34THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. REVISE/CORRECT YOUR GENERAL NOTES #3. AMBIENT
 CONDITIONS AND NOT CONDUCTOR SIZING DICTATE INSULATION
 REQUIREMENTS.
 2. NEC 110.16 ALL ELECTRICAL EQUIPMENT SHALL BE LABELED
 TO WARN SERVICED PERSONNEL AGAINST AN ARCH-FLASH
 HAZARD.
 3. NEC 600.5 EVERY COMMERCIAL ESTABLISHMENT ACCESSIBLE
 TO PEDESTRIANS SHALL HAVE AT EVERY PEDESTRIAN ENTRY AT
 LEAST ONE OUTLET IN AN ACCESSIBLE LOCATION FOR SIGNAGE.
 4. NEC 406.9(B) 15 & 20 AMP 125 - 250 VOLT NON-LOCKING
 TYPE RECEPTACLES INSTALLED IN "WET LOCATIONS" SHALL BE
 RATED WEATHER RESISTANT "WR".
 5. ADDITIONAL EMERGENCY LIGHTING SHALL BE INSTALLED IN
 THE DINNING, PREP POS AND PATIO AREAS.
 6. NEC 210.8(B) ALL 15 & 20 AMP 125 VOLT RECEPTACLES
 INSTALLED IN KITCHENS SHALL BE GFCI PROTECTED.
 7. NEC 250.94 AN INTER-SYSTEM BONDING TERMINAL SHALL BE
 INSTALLED.
 8. THE FEEDER TO PANEL ?H? EXCEEDS THE MAXIMUM 3%
 VOLTAGE DROP. 3/0 CU FOR 200 AMP AT 150 FT.
 9. NEC 406.9(B) DETAIL #7 SHALL INDICATE AN ?IN-USE?
 TYPE COVER AS INDICATED
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By cranford Date 2015-12-21 Time 12:44 Rev Time 0.00
Received By cranford Date 2015-12-21 Time 12:42 Sent To  
Notes
2015-12-21 12:44:07GREASE SEPARATOR SIZING IS BASED BASED ON LOW-FAT,
 VEGAN MENU WITH NO ON-SITE FOOD PREPARATION.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-12-01 Cont ID  
Sent By cranford Date 2015-12-01 Time 10:39 Rev Time 0.00
Received By cranford Date 2015-12-01 Time 10:37 Sent To  
Notes
2015-12-01 10:38:59PLEASE SUBMIT SIZING CALCULATIONS FOR THE PROPOSED
 GREASE TRAP. SIZING/DESIGN FOR THIS TYPE OF SEPARATOR
 MUST BE BASED ON BOTH THE FLOW RATE AND ANTICIPATED
 OIL/GREASE LOADING FROM RESTAURANT. PLEASE SUBMIT
 SIZING CALCULATIONS FROM THE MANUFACTURER OR A LICENSED
 PROFESSIONAL.
  
 KELLY CRANFORD, P.E.
 CAPITAL IMPROVEMENT PLAN MANAGER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By pleduc Date 2015-12-21 Time   Rev Time 0.00
Received By pleduc Date 2015-12-21 Time 15:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-30 Cont ID  
Sent By pleduc Date 2015-10-30 Time   Rev Time 0.00
Received By pleduc Date 2015-10-30 Time 11:13 Sent To  
Notes
2015-10-30 13:07:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET E 0.1, PROVIDES NO READILY IDENTIFIABLE
 INDICATION OF FIRE ALARM WORK. THE EXTENT OF THE
 REMODEL OR REVISION IS UNCLEAR AND DOES NOT INDICATE
 SUFFICIENT DETAIL TO ADDRESS THE FIRE ALARM OF THE
 PROPOSED PROJECT.
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 2. SHEET P 1.1, INDICATES INFORMATION REGARDING GREASE
 AND GREASE TRAPS. THERE IS TO BE NO COOKING OF ANY
 PRODUCT PRODUCING GREASE LADEN VAPORS WITHOUT A NFPA 96
 COMPLIANT HOOD AND FIRE SUPRESSION SYSTEM.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By fmittner Date 2015-12-21 Time 15:46 Rev Time 0.00
Received By fmittner Date 2015-12-21 Time 15:46 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-12-01 Cont ID  
Sent By fmittner Date 2015-12-01 Time 10:11 Rev Time 0.00
Received By fmittner Date 2015-12-01 Time 10:11 Sent To  
Notes
2015-12-01 10:12:58NO EXTERIOR DOOR SPECS. FRIEDERIKE MITTNER, CITY
 HISTORIC PRESERVATION PLANNER 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-22 Cont ID  
Sent By skennedy Date 2015-12-22 Time 08:09 Rev Time 0.00
Received By skennedy Date 2015-12-15 Time 10:31 Sent To  
Notes
2015-12-16 10:31:35C21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-01 Cont ID  
Sent By albarran Date 2015-12-01 Time 15:20 Rev Time 0.00
Received By albarran Date 2015-10-21 Time 08:45 Sent To  
Notes
2015-12-01 15:19:4412/1/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "L". MA
2015-11-02 15:31:01*NEW LOCATION C23
2015-10-22 08:46:02B21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-12-21 Cont ID  
Sent By skennedy Date 2015-12-21 Time 16:59 Rev Time 0.00
Received By skennedy Date 2015-12-21 Time 16:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By ccole Date 2015-12-21 Time 10:28 Rev Time 0.00
Received By ccole Date 2015-12-21 Time 10:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By ccole Date 2015-11-05 Time 13:16 Rev Time 0.00
Received By ccole Date 2015-11-05 Time 12:22 Sent To  
Notes
2015-11-05 13:34:101ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100773
 11/5/2015
  
 1) DUE TO CHANGES IN THE FLOOR PLAN, THE AHU-1 IS NOW
 SHOWN TO BE LOCATED ABOVE THE WOMEN'S TOILET ROOM
 SUSPENDED CEILING. PLEASE REFER TO SECTION 306.1 AND
 INDICATE HOW ACCESS FOR INSPECTION, SERVICE, REPAIR,
 AND REPLACEMENT WILL BE ACCOMPLISHED WITHOUT REMOVING
 PERMANENT CONSTRUCTION.
 2) SHOW THE AC CONDENSATE PIPING RUNS AND DISCHARGE
 LOCATIONS.
 3) THE AC SYSTEM DATA FOR COOLING CAPACITY AND SEER
 LISTED IN THE SCHEDULE ON M0.1 DOES NOT MATCH THE DATA
 LISTED UNDER SYSTEM REPORT COMPLIANCE IN THE ENERGY
 CONSERVATION FORM SUBMITTAL: PLEASE CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By gjohnson Date 2015-12-21 Time 13:54 Rev Time 0.00
Received By gjohnson Date 2015-12-21 Time 13:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-27 Cont ID  
Sent By gjohnson Date 2015-10-27 Time 14:40 Rev Time 0.00
Received By gjohnson Date 2015-10-27 Time 14:40 Sent To  
Notes
2015-10-27 14:59:121ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE MANUFACTURE SPEC SHEETS, SIZING CALCULATIONS
 AND INSTALLATION GUIDES FOR GREASE INTERSEPTOR AND
 DUPLEX PUMP AND TANK.PER WPB AMEND. TO FBC SEC 107.2.1
 AND 107.2.1.3

Review Stop Z ZONING
Rev No 2 Status P Date 2015-12-16 Cont ID  
Sent By aaponte Date 2015-12-16 Time 14:49 Rev Time 0.00
Received By aaponte Date 2015-12-16 Time 14:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-12-01 Cont ID  
Sent By aaponte Date 2015-12-01 Time 10:17 Rev Time 0.00
Received By aaponte Date 2015-12-01 Time 10:17 Sent To  
Notes
2015-12-01 10:23:32PLEASE SUBMIT A SURVEY OF THE FUTURE PARK INDICATING
 THE EXACT AREA THAT WILL BE DEDICATED FOR THE OUTDOOR
 SEATING. THE PARK AREA SHALL BE MAINTAINDED AS
 12,500SF. REVISED SURVEY WILL BE NEEDED UPDATING FINAL
 PARK BOUNDARIES.
 PLEASE CONTACT ANA MARIA APONTE FOR ADDITIONAL
 INFORMATION AT 561-822-1439.