Plan Review Details - Permit 15100764
Plan Review Stops For Permit 15100764
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-02 Cont ID  
Sent By jwitmer Date 2016-02-02 Time 06:56 Rev Time 0.00
Received By jwitmer Date 2016-02-02 Time 06:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-01-04 Cont ID  
Sent By jwitmer Date 2016-01-04 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-01-04 Time 06:32 Sent To  
Notes
2016-01-04 06:53:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100764
 ADD: 1100 W. TECHNOLOGY PL. SUITE # 110
 CONT: HEDRICK BROS. CONSTRUCION
 TEL: (561)689-8880
 E-MAIL: ???????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JAN. 04/2016
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS INDICATES THIS TENANT SPACE IS A
 CHANGE OF OCCUPANCY FROM A F1 OCCUPANCY, A DRY CLEANING
 FACILITY WHERE THERE WAS A BOILER, NOT JUST A DROP OFF
 AND PICK UP FACILITY. PERMIT # 99111358 SHOULD A FULL
 SCALE DRY CLEANING FACILITY, THE NEW OCCUPANCY IS
 INDICATED AS A BUSINESS OCCUPANCY. SHEET A0.2 & M1.1
 BOTH SHOW THIS SPACE TO NOW BE NON-CONDITIONED SPACE.
  
 PLEASE SHOW HOW THE BUSINESS/ STORAGE OCCUPANCY WILL
 MEET THE CODE SECTION OF:
 2014 FBC-B 1203.4. 1203.4 NATURAL VENTILATION. NATURAL
 VENTILATION OF AN OCCUPIED SPACE SHALL BE THROUGH
 WINDOWS, DOORS, LOUVERS OR OTHER OPENINGS TO THE
 OUTDOORS. THE OPERATING MECHANISM FOR SUCH OPENINGS
 SHALL BE PROVIDED WITH READY ACCESS SO THAT THE
 OPENINGS ARE READILY CONTROLLABLE BY THE BUILDING
 OCCUPANTS.
  
 1203.4.1 VENTILATION AREA REQUIRED. THE OPENABLE AREA
 OF THE OPENINGS TO THE OUTDOORS SHALL BE NOT LESS THAN
 4 PERCENT OF THE FLOOR AREA BEING VENTILATED.
  
  
  
  
 2) AS PREVIOSLY NOTED IN THE 1ST REVIEW, THIS IS A
 CHANGE OF OCCUPANCY FROM A (F-1 FACTORY) TO A BUSINESS
 OCCUPANCY, WHICH REQUIRES COMPLIANCE WITH SECTION:
  
 C101.4.4 OF THE 2014 FBC-ENERGY CONSERVATION CODE.
 C101.4.4 CHANGE IN OCCUPANCY OR USE. SPACES UNDERGOING
 A CHANGE IN OCCUPANCY THAT WOULD RESULT IN AN INCREASE
 IN DEMAND FOR EITHER FOSSIL FUEL OR ELECTRICAL ENERGY
 SHALL COMPLY WITH THIS CODE. WHERE THE USE IN A SPACE
 CHANGES FROM ONE USE IN TABLE C405.5.2(1) OR (2) TO
 ANOTHER USE IN TABLE C405.5.2(1) OR (2), THE INSTALLED
 LIGHTING WATTAGE SHALL COMPLY WITH SECTION C405.5.
  
 3) COMPLIED. N/A.
  
 4)COMPLIED. N/A.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-02 Cont ID  
Sent By jwitmer Date 2015-11-02 Time 15:01 Rev Time 0.00
Received By jwitmer Date 2015-10-30 Time 15:02 Sent To  
Notes
2015-11-02 13:50:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15100764
 ADD: 1100 W. TECHNOLOGY PL. SUITE # 110
 CONT: HEDRICK BROS. CONSTRUCION
 TEL: (561)689-8880
 E-MAIL: ???????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. NOV. 02/2014
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS INDICATES THIS TENANT SPACE IS A
 CHANGE OF OCCUPANCY FROM A F1 OCCUPANCY, A DRY CLEANING
 FACILITY WHERE THERE WAS A BOILER, NOT JUST A DROP OFF
 AND PICK UP FACILITY. PERMIT # 99111358 SHOULD A FULL
 SCALE DRY CLEANING FACILITY, THE NEW OCCUPANCY IS
 INDICATED AS A BUSINESS OCCUPANCY. SHEET A0.2 & M1.1
 BOTH SHOW A NEW
 RTU TO BE INSTALLED ON THE ROOF.
 2014 ENERGY CODE C101.4.5 CHANGE IN SPACE CONDITIONING.
 ANY NONCONDITIONED SPACE THAT IS ALTERED TO BECOME
 CONDITIONED SPACE SHALL BE REQUIRED TO BE BROUGHT INTO
 FULL COMPLIANCE WITH THIS CODE. PLEASE PROVIDE HOW
 COMPLIANCE WILL BE ACHIEVED?
  
 2014 C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL
 COMPLY WITH ONE OF THE FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1.
 2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND
 C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY
 WITH EITHER SECTION C406.2, C406.3 OR C406.4.
 3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2,
 C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE
 BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85
 PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING.
 NOTE THE OVERHEAD DOOR MAYBE REQUIRED TO BE INSULATED,
 DEPENDING ON THE EMERGY CALCULATIONS.
  
 2A) THE PLANS DO NOT INDICATE HOW THE ROOF IS GOING TO
 BE FRAMED IN AROUND THE NEW ROOF TOP HOLE FOR THE NEW
 RTU. PLEASE PROVIDE FRAMING MEMBERS REQUIRED, TYPE OF
 MATERIALS, BAR JOIST WILL REQUIRE STIFFENERS IN THE BAR
 JOIST, FRAMING DETAILS, AND PLEASE PROVIDE HOW THE NEW
 ROOF TOP CURB WILL BE ANCHORED TO THE BAR JOIST AND
 FRAMING MEMBERS. PLEAS ALSO PROVIDE A PRODUCT APPROVAL
 FOR THE NEW ROOF TOP CURB FOR THE RTU UNIT. MWFRS MAIN
 WIND FORCE RESISSTING SYSTEM AND 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS
  
 2B) THE PLANS DO NOT INDICATE HOW THE RTU ROOF TOP UNIT
 IS GOING TO BE ATTACHED TO THE ROOF TOP CURB TO RESIST
 LATERAL SLIDDING AND THE MOMENT OF OVERTURNING. PLEASE
 PROVIDE DETAIL. 2014 FBC-B 1609.6.4.4.1.
  
 3) THW PLANS DO NOT INDICATE THE ROOF ELEVATION NOR IF
 THERE IS A PAREPET AND THE HEIGHT OF THE PAREPET.
 APERMANENT LADDER MAYBE REQUIRED FOR ROOF TOP ACCESS,
 PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-B ? 1509.6.4
 EQUIPMENT AND APPLIANCES ON ROOFS OR ELEVATED
 STRUCTURES.
 WHERE EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED STRUCTURES AT A HEIGHT
 EXCEEDING 16 FEET (4877 MM), SUCH ACCESS SHALL BE
 PROVIDED BY A PERMANENT APPROVED MEANS OF ACCESS, THE
 EXTENT OF WHICH SHALL BE FROM GRADE OR FLOOR LEVEL TO
 THE EQUIPMENT AND APPLIANCES? LEVEL SERVICE SPACE. SUCH
 ACCESS SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS
 GREATER THAN 30 INCHES (762 MM) HIGH OR WALKING ON
 ROOFS HAVING A SLOPE GREATER THAN 4 UNITS VERTICAL IN
 12 UNITS HORIZONTAL (33-PERCENT SLOPE).
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 1. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES (762 MM).
 2. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES (356 MM) ON CENTER.
 3. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN
 6-INCHES (152 MM) DEEP.
 4. THERE SHALL BE A MINIMUM OF 18 INCHES (457 MM)
 BETWEEN RAILS.
 5. RUNGS SHALL HAVE A MINIMUM 0.75-INCH (19 MM)
 DIAMETER AND BE CAPABLE OF WITHSTANDING A 300-POUND
 (136.1 KG) LOAD.
 6. LADDERS OVER 30 FEET (9144 MM) IN HEIGHT SHALL BE
 PROVIDED WITH OFFSET SECTIONS AND LANDINGS CAPABLE OF
 WITHSTANDING 100 POUNDS PER SQUARE FOOT (488.2 KG/M2).
 7. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS. CATWALKS INSTALLED TO PROVIDE THE
 REQUIRED ACCESS SHALL BE NOT LESS THAN 24-INCHES (610
 MM) WIDE AND SHALL HAVE RAILINGS AS REQUIRED FOR
 SERVICE PLATFORMS
  
 4) THE OTHER ISSUE MAYBE THE ARCHITECTURAL PLANS DO NOT
 PROVIE THE HEIGHT OF THE PARAPET WALL, ZONING MAY
 REQUIRE THE A/C RTU ROOF TOP UNIT TOBE SCREENED. IF SO
 PLEASE PROVIDE HOW THE FRAMEWORK WILL BE ATTACHED TO
 THE MAINWIND FORCE RESISTING SYSTEM AND HOW THE WIND
 SCREEN IS TO BE ATTACHED TO THE FRAME. WHAT WIND DESIGN
 PERAMETERS ARE GOING TO BE USED TO FORMULATE THE
 RELEASE OF THE FABRIC IN HIGH WIND EVENTS?
 1609.6.4.4.1/ 3105.4.2.1.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-01-25 Cont ID  
Sent By mvaldes Date 2016-01-25 Time 19:53 Rev Time 0.00
Received By mvaldes Date 2016-01-25 Time 19:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-01-21 Cont ID  
Sent By mvaldes Date 2016-01-21 Time 13:26 Rev Time 0.00
Received By mvaldes Date 2016-01-21 Time 13:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-19 Time 17:07 Rev Time 0.00
Received By albarran Date 2015-11-19 Time 16:17 Sent To I
Notes
2015-11-19 17:07:36THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1. FBC-E402.4.8, ALL RECESSED LUMINAIRES INSTALLED IN
 THE BUILDING'S THERMAL ENVELOPE SHALL BE IC RATED AND
 SEALED TO LIMIT AIR LEAKAGE BETWEEN THE CONDITIONED AND
 THE NON-CONDITIONED SPACE.
 2. FBC-E405.2.2.2, OCCUPANCY SENSORS SHALL BE INSTALLED
 IN ALL BATHROOMS 300 SQ. FT. OR LESS.
 3. FBC-B714.3, ALL OUTLETS AND/OR ELECTRICAL PANELS
 INSTALLED IN A FIRE RATED WALL SHALL COMPLY AS
 INDICATED.
 4. NEC210.63, THERE SHALL BE A 15 - 20 AMP SERVICE
 OUTLET WITHIN 25' OF THE HVAC EQUIPMENT.
 5. NEC300.5(B), THE INTERIOR OF A RACEWAY INSTALLED
 UNDERGROUND SHALL BE CONSIDERED A WET LOCATION AND
 THEREFORE THE FEEDER CONDUCTORS SHALL BE LISTED
 ACCORDINGLY.
 6. NEC410.36, LUMINAIRES INSTALLED ON FRAMING MEMBERS
 OF A SUSPENDED CEILING SHALL BE SECURELY FASTENED TO
 THE CEILING FRAMING MEMBERS BY MECHANICAL MEANS.
 7. NEC600.5, EVERY COMMERCIAL ESTABLISHMENT SHALL HAVE
 AT EVERY ENTRY ACCESSIBLE TO PEDESTRIANS A DEDICATED
 SIGN OUTLET.
 8. NEC700.12(F), ALL EMERGENCY AND EXIT LIGHTS SHALL BE
 CONNECTED TO THE ELECTRICAL CIRCUIT FOR THE AREA IN
 WHICH THEY ARE LOCATED. A DEDICATED EMERGENCY LIGHT
 CIRCUIT IS NOT ALLOWED BY CODE UNLESS THERE IS A
 MINIMUM OF THREE DIFFERENT CIRCUITS FOR THE AREA.
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-01-26 Cont ID  
Sent By pleduc Date 2016-01-26 Time   Rev Time 0.00
Received By pleduc Date 2016-01-26 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-31 Cont ID  
Sent By pleduc Date 2015-12-31 Time   Rev Time 0.00
Received By pleduc Date 2015-12-31 Time 09:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-10-29 Cont ID  
Sent By pleduc Date 2015-10-29 Time   Rev Time 0.00
Received By pleduc Date 2015-10-29 Time 10:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-02 Cont ID  
Sent By jwitmer Date 2016-02-02 Time 06:56 Rev Time 0.00
Received By jwitmer Date 2016-01-22 Time 10:29 Sent To  
Notes
2016-01-25 10:29:49B32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-21 Cont ID  
Sent By lmarchan Date 2016-01-21 Time 15:19 Rev Time 0.00
Received By lmarchan Date 2015-12-22 Time 10:44 Sent To  
Notes
2015-12-22 10:45:01B16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-19 Cont ID  
Sent By albarran Date 2015-11-19 Time 17:10 Rev Time 0.00
Received By albarran Date 2015-10-21 Time 10:06 Sent To  
Notes
2015-11-19 17:11:2811/19/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "H". MA
2015-10-22 10:07:05B17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-01-26 Cont ID  
Sent By ccole Date 2016-01-26 Time 09:26 Rev Time 0.00
Received By ccole Date 2016-01-26 Time 09:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-01-26 Cont ID  
Sent By ccole Date 2015-12-29 Time 09:25 Rev Time 0.00
Received By ccole Date 2015-12-29 Time 10:51 Sent To  
Notes
2015-12-29 11:16:102ND REVIEW 2014 MECHANICAL
 PERMIT #15100764
 12/29/15
  
 1) THE NEW TENANT OCCUPANCY, WHETHER IT IS BUSINESS AS
 SPECIFIED ON A.01 AND A.04, OR S-2 AS SPECIFIED ON THE
 A.04 LS PLAN REQUIRES A MEANS OF VENTILATION IN
 ACCORDANCE WITH SECTION 401.2 AND TABLE 403.3 FBC-14
 MECHANICAL. AS PREVIOUSLY REQURESTED IN THE 1ST REVIEW,
 PROVIDE VENTILATION CALCULATIONS AND A VENTILATION
 SYSTEM. PLEASE NOTE THAT IF THE OCCUPANCY IS TO BE
 BUSINESS THEN AN ACTIVE OR PASSIVE SPACE-HEATING SYSTEM
 CAPABLE OF MAINTAINING A MINIMUM INDOOR TEMPERATURE OF
 68 DEGREES F IS REQUIRED- SECTION 309.1 FBC-14
 MECHANICAL,
 2) AS PREVIOUSLY NOTED IN THE 1ST REVIEW THIS IS A
 CHANGE OF OCCUPANCY FROM F-1 TO EITHER A B OR S-2
 OCCUPANCY, WHICH REQUIRES COMPLIANCE WITH SECTION
 C101.4.4 FBC-14 ENERGY CONSERVATION. THE REMOVAL OF THE
 AC SYSTEM DOES NOT EXEMPT THE SPACE FROM MEETING
 COMPLIANCE- SEE SECTION C101.4.8 FBC-14 ENERGY
 CONSERVATION AND SUBMIT ENERGY CALCULATIONS USING
 EITHER THE PERFORMANCE OR PRESCRIPTIVE BASED METHOD-
 SECTION C101.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By ccole Date 2015-11-03 Time 16:46 Rev Time 0.00
Received By ccole Date 2015-11-03 Time 16:45 Sent To  
Notes
2015-11-03 16:51:591ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100764
 11/3/15
  
 1) ENERGY CALCULATIONS ARE REQUIRED PER SECTIONS
 C101.4.4 AND C101.4.5 FBC-14 ENERGY CONSERVATION.
 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND
 PROVIDE VENTILATION CALCULATIONS IN COMPLIANCE WITH
 TABLE 403.3 FBC-14 MECHANICAL.
 3) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 THE RTU AND CURB ATTACHMENT TO THE EXISTING STRUCTURE.
 THE ENGINEER OF RECORD SHALL PROVIDE THE WIND LOAD
 DESIGN CRITERIA AND DESIGN PRESSURES ON THE PLANS.
 SECTION CUTS OF THE ROOF STRUCTURE, CURB, AND RTU SHALL
 BE PLACED ON THE PLAN TO CLEARLY INDICATE ALL REQUIRED
 STRUCTURAL REINFORCEMENTS AND ATTACHMENTS.
 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW RTU-
 REFER TO SECTION 307
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-01-25 Cont ID  
Sent By gjohnson Date 2016-01-25 Time 17:07 Rev Time 0.00
Received By gjohnson Date 2016-01-25 Time 17:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-01-05 Cont ID  
Sent By gjohnson Date 2016-01-05 Time 13:54 Rev Time 0.00
Received By gjohnson Date 2016-01-05 Time 13:54 Sent To  
Notes
2016-01-05 14:06:202ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ACCORDING TO FBC TABLE 1004.1.2 YOUR OCCUPANT LOAD
 IS 18 PEOPLE ACCORDING TO FBC PL TABLE 403.1 IN B
 OCCUPANCY'S WITH OVER 15 PEOPLE A SERVICE SINK IS
 REQUIRED. THIS IS THE SECOND REQUEST FOR THIS.
 2. SHEETS A.01- A.03 AND E1 SHOW SINGLE WATER FOUNTAIN
 ON P1 YOU SHOW A DOUBLE OR HILO PLEASE CLARIFY.
 3. PLEASE SHOW THAT THE WATER FOUNTAIN COMPLIES WITH
 FBC ACC SEC 307.2 PROTRUSION LIMITS.
 OBJECTS WITH LEADING EDGES MORE THAN 27 INCHES (685 MM)
 AND NOT MORE THAN 80 INCHES (2030 MM) ABOVE THE FINISH
 FLOOR OR GROUND SHALL PROTRUDE 4 INCHES (100 MM)
 MAXIMUM HORIZONTALLY INTO THE CIRCULATION PATH.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-27 Cont ID  
Sent By gjohnson Date 2015-10-27 Time 10:33 Rev Time 0.00
Received By gjohnson Date 2015-10-27 Time 10:32 Sent To  
Notes
2015-10-27 10:59:021ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. SERVICE SINK REQUIRED IN B OCCUPANCY WITH OCCUPENCY
 LOAD OF OVER 15 PER FBC P TABLE 403.1 YOUR OCCUPANT
 LOAD FACTOR FOR BUSINESS IS 100 GROSS PER FBC TABLE
 1004.1.2 WITCH GIVES YOU 18 .
 2. GRAB BARS SHALL COMPLY WITH FBC ACC. SEC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 3. TOILETS SHALL COMPLY WITH FBC ACC SEC 604.2
 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL
 4. TOILET PAPER DISPENCER SHALL COMPLY WITH FBC ACC SEC
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.