Plan Review Stops For Permit 15100503 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2016-04-27 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-04-27 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-04-27 |
Time |
09:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-04-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-04-18 |
Time |
14:27 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-04-18 |
Time |
13:53 |
Sent To |
|
|
Notes |
2016-04-18 14:32:44 | 2ND REVIEW: FBC 2014 5TH ED | | CHRISTOPHER S. THROOP, C.B.O. | | BLDG. PLANS EXAMINER ? PX3169 | | (561) 805-6718 | | [email protected] | | | | 1. DESIGNER OF RECORD TO SIGN AND SEAL PLANS. | | 2. CORRECT GOVERNING CODE REFERENCE, PG. A1.01 | | 3. REF. DETAIL #1, PG A1.01 - PROVIDE FASTENER SCHEDULE | | FOR NEW FRAMING TO EXISTING STRUCTURE. | | 4. REF. DETAIL #3, PG A1.01 - PROVIDE DEMENSIONS FOR | | PROPOSED COLUMN. | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | SECTION 107.3.5). | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-11-03 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2015-11-03 |
Time |
11:22 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2015-11-03 |
Time |
11:22 |
Sent To |
FIRE |
|
Notes |
2015-11-03 11:26:08 | CHRISTOPHER S. THROOP, C.B.O. | | BLDG. PLANS EXAMINER ? PX3169 | | (561) 805-6718 | | [email protected] | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | SECTION 107.3.5). PLEASE INDICATE ANY FLOORING | | INSTALLATION. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2016-04-27 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-04-27 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-04-27 |
Time |
09:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2016-03-17 |
|
|
Cont ID |
|
Sent By |
mvaldes |
Date |
2016-03-17 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
mvaldes |
Date |
2016-03-17 |
Time |
10:47 |
Sent To |
|
|
Notes |
2016-03-17 10:56:12 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 516-805-6713 | | [email protected] | | | | | | - CKT # 21 SHOWS A 15 AMP OCPD FOR A BATHROOM GFCI NEC | | 210.12 C3 STATES A MINIMUM 20 AMPERE BRANCH CIRCUIT. | | | | - KITCHEN ISLAND IS MISSING RECEPTACLES AT EACH END OF | | THE COUNTER WITHIN 12" OF THE TOP. NEC 210.52 C2 ( GFCI | | PROTECTION REQUIRED ) | | | | - NEW RECCESSED LIGHTING MUST COMPLY WITH 75 % HIGH | | EFFIENCY AS WELL AS IC RATED /SEALED (2CFM) AS NOT TO | | COMPROMISE THERMAL ENVELOPE. FBC-ER 404.1.1 & 402.4.4 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-11-02 |
|
|
Cont ID |
|
Sent By |
ppetty |
Date |
2015-11-02 |
Time |
09:17 |
Rev Time |
0.00 |
Received By |
ppetty |
Date |
2015-11-02 |
Time |
09:11 |
Sent To |
B |
|
Notes |
2015-11-02 09:18:39 | 210.52 NO ELECTRICAL WORK ON PLAN | | 11/2/2015 PP |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-03-30 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2016-03-30 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2016-03-30 |
Time |
11:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2015-11-03 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2015-11-03 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2015-11-03 |
Time |
15:24 |
Sent To |
I |
|
Notes |
2015-11-03 15:25:21 | PERMIT # 15100503 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAILED - SEE BUILDING REVIEWER'S COMMENTS. | | | | SUE ELLEN CALDERON | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-04-27 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-04-27 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-04-25 |
Time |
09:45 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-04-18 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2016-04-18 |
Time |
14:26 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2016-03-16 |
Time |
09:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-11-03 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2015-11-03 |
Time |
15:25 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2015-10-15 |
Time |
14:05 |
Sent To |
|
|
Notes |
2015-10-15 14:05:57 | ROUTED TO ELECTRICAL INBOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2016-04-27 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-04-27 |
Time |
09:51 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-04-27 |
Time |
09:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2016-03-29 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-03-29 |
Time |
14:01 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-03-29 |
Time |
14:01 |
Sent To |
|
|
Notes |
2016-03-29 14:05:33 | | | 1. PLANS MUST BE SIGNED AND SEALED BY DESIGN | | PROFESSIONAL. | | PER FAC SEC 61G15-23.003 PROCEDURES FOR PHYSICALLY | | SIGNING AND SEALING PLANS, SPECIFICATIONS, REPORTS OR | | OTHER DOCUMENTS. | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025, | | F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY | | SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE | | PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE | | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR | | COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE | | USED. | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-11-03 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-11-03 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-11-03 |
Time |
11:13 |
Sent To |
|
|
Notes |
2015-11-03 11:17:56 | 1ST REVIEW: FBC 2014 5TH ED. | | | | THE PLAN IS UNCLEAR. PLEASE PROVIDE THE PLUMBING SCOPE | | OF WORK. AND THE DESIGNER MUST SIGN THE PLAN. | | | | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE | | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE | | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT | | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND | | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM | | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, | | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE | | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, | | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE | | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS | | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO | | SECTION 107.3.5). | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|