Plan Review Details - Permit 15100503
Plan Review Stops For Permit 15100503
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-04-27 Cont ID  
Sent By skennedy Date 2016-04-27 Time 09:51 Rev Time 0.00
Received By skennedy Date 2016-04-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-18 Cont ID  
Sent By cthroop Date 2016-04-18 Time 14:27 Rev Time 0.00
Received By cthroop Date 2016-04-18 Time 13:53 Sent To  
Notes
2016-04-18 14:32:442ND REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. DESIGNER OF RECORD TO SIGN AND SEAL PLANS.
 2. CORRECT GOVERNING CODE REFERENCE, PG. A1.01
 3. REF. DETAIL #1, PG A1.01 - PROVIDE FASTENER SCHEDULE
 FOR NEW FRAMING TO EXISTING STRUCTURE.
 4. REF. DETAIL #3, PG A1.01 - PROVIDE DEMENSIONS FOR
 PROPOSED COLUMN.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By cthroop Date 2015-11-03 Time 11:22 Rev Time 0.00
Received By cthroop Date 2015-11-03 Time 11:22 Sent To FIRE
Notes
2015-11-03 11:26:08CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5). PLEASE INDICATE ANY FLOORING
 INSTALLATION.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-04-27 Cont ID  
Sent By skennedy Date 2016-04-27 Time 09:51 Rev Time 0.00
Received By skennedy Date 2016-04-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-17 Cont ID  
Sent By mvaldes Date 2016-03-17 Time 10:47 Rev Time 0.00
Received By mvaldes Date 2016-03-17 Time 10:47 Sent To  
Notes
2016-03-17 10:56:12REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
 - CKT # 21 SHOWS A 15 AMP OCPD FOR A BATHROOM GFCI NEC
 210.12 C3 STATES A MINIMUM 20 AMPERE BRANCH CIRCUIT.
  
 - KITCHEN ISLAND IS MISSING RECEPTACLES AT EACH END OF
 THE COUNTER WITHIN 12" OF THE TOP. NEC 210.52 C2 ( GFCI
 PROTECTION REQUIRED )
  
 - NEW RECCESSED LIGHTING MUST COMPLY WITH 75 % HIGH
 EFFIENCY AS WELL AS IC RATED /SEALED (2CFM) AS NOT TO
 COMPROMISE THERMAL ENVELOPE. FBC-ER 404.1.1 & 402.4.4

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-02 Cont ID  
Sent By ppetty Date 2015-11-02 Time 09:17 Rev Time 0.00
Received By ppetty Date 2015-11-02 Time 09:11 Sent To B
Notes
2015-11-02 09:18:39210.52 NO ELECTRICAL WORK ON PLAN
 11/2/2015 PP

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-30 Cont ID  
Sent By scaldero Date 2016-03-30 Time 11:35 Rev Time 0.00
Received By scaldero Date 2016-03-30 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By scaldero Date 2015-11-03 Time 15:24 Rev Time 0.00
Received By scaldero Date 2015-11-03 Time 15:24 Sent To I
Notes
2015-11-03 15:25:21PERMIT # 15100503
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED - SEE BUILDING REVIEWER'S COMMENTS.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-27 Cont ID  
Sent By skennedy Date 2016-04-27 Time 09:51 Rev Time 0.00
Received By skennedy Date 2016-04-25 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-18 Cont ID  
Sent By cthroop Date 2016-04-18 Time 14:26 Rev Time 0.00
Received By cthroop Date 2016-03-16 Time 09:46 Sent To  
Notes
2016-03-16 09:46:27B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-03 Cont ID  
Sent By scaldero Date 2015-11-03 Time 15:25 Rev Time 0.00
Received By scaldero Date 2015-10-15 Time 14:05 Sent To  
Notes
2015-10-15 14:05:57ROUTED TO ELECTRICAL INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-04-27 Cont ID  
Sent By skennedy Date 2016-04-27 Time 09:51 Rev Time 0.00
Received By skennedy Date 2016-04-27 Time 09:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-29 Cont ID  
Sent By gjohnson Date 2016-03-29 Time 14:01 Rev Time 0.00
Received By gjohnson Date 2016-03-29 Time 14:01 Sent To  
Notes
2016-03-29 14:05:33 
 1. PLANS MUST BE SIGNED AND SEALED BY DESIGN
 PROFESSIONAL.
 PER FAC SEC 61G15-23.003 PROCEDURES FOR PHYSICALLY
 SIGNING AND SEALING PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MAY BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-11-03 Cont ID  
Sent By skennedy Date 2015-11-03 Time 11:13 Rev Time 0.00
Received By skennedy Date 2015-11-03 Time 11:13 Sent To  
Notes
2015-11-03 11:17:561ST REVIEW: FBC 2014 5TH ED.
  
 THE PLAN IS UNCLEAR. PLEASE PROVIDE THE PLUMBING SCOPE
 OF WORK. AND THE DESIGNER MUST SIGN THE PLAN.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  