Plan Review Details - Permit 15100235
Plan Review Stops For Permit 15100235
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2015-12-14 Cont ID  
Sent By skennedy Date 2015-12-14 Time 16:12 Rev Time 0.00
Received By skennedy Date 2015-12-14 Time 16:12 Sent To  
Notes
2015-12-14 16:13:06PLEASE SEE THE PLUMBING COMMENTS FOR ACCESSIBILITY
 ISSUES.

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-12-14 Cont ID  
Sent By skennedy Date 2015-12-14 Time 16:12 Rev Time 0.00
Received By skennedy Date 2015-12-14 Time 16:12 Sent To  
Notes
2015-12-21 15:00:27ELECTRIC IS BY SEPARATE PERMIT AS SUB TO 15100233

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-21 Cont ID  
Sent By skennedy Date 2015-12-21 Time 15:01 Rev Time 0.00
Received By skennedy Date 2015-12-18 Time 13:58 Sent To  
Notes
2015-12-18 13:58:20RESUB ROUTED TO GJOHNSON

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-12-14 Cont ID  
Sent By skennedy Date 2015-12-14 Time 16:13 Rev Time 0.00
Received By skennedy Date 2015-12-14 Time 16:13 Sent To  
Notes
2015-12-21 15:01:06MECHANICAL IS BY SEPARATE PERMIT TO BE RESOLVED AS SUB
 TO 15100233

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By gjohnson Date 2015-12-21 Time 13:19 Rev Time 0.00
Received By gjohnson Date 2015-12-21 Time 13:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-03 Cont ID  
Sent By gjohnson Date 2015-12-03 Time 14:38 Rev Time 0.00
Received By gjohnson Date 2015-12-03 Time 14:38 Sent To  
Notes
2015-12-03 15:00:151ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
 1. SHOW DEMINTIONS INCLUDING CLEAR FLOOR SPACE OF THE
 BATHROOM SHALL COMPLY WITH FBC ACC. SEC 604.2, 604.3.1,
 604.8.1.6
 2.GRAB BARS SHALL COMPLY WITH FBC ACC. SEC. 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 3.PLEASE PROVIDE WATER AND SANITARY RISER DIAGRAM.PER
 WPB AMEND TO FBC SEC. 107.3.5.1.3(13)
 4. SHOW LOCATION OF TANKLESS WATER HEATER. PER WPB
 AMEND.TO FBC 107.2.1
 THE FOLLOWING IS AN UPDATED PLUMBING REVIEW AS OF
 12/9/15;
 5) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK
 BEING DONE TO THE EXISTING TOILET ROOM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 6) SINCE THIS IS A CHANGE OF OCCUPANCY, A SERVICE SINK
 IS REQUIRED FOR A MERCANTILE OCCUPANCY PER THE 2014
 FBC-PLBG. TABLE 403.1.
 7) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW
 FOR ALL NEW PLUMBING FIXTURES. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 8) THE LAVATORY IN THE ADA TOILET ROMM AND THE MOP SINK
 SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014
 FBC -PLBG.SEC.607.1.
 9)SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE LAVATORY IN ADA TOILET ROOM PER THE 2014
 FBC-ACCESS.SEC.604.3.1. & SEC. 606.2 & SEC.305.
 10) SHT. A.01 - THE UPDATE MODIFICATION NOTE SHALL
 INCLUDE THE ADDITION OF THE DRINKING FOUNTAINS, THE MOP
 SINK AND THE REQUIREMENT FOR HOT WATER TO THE SCOPE OF
 WORK. WPB AMEND.TO FBC 107.2.1
 11) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9
 INCHES TO THE CENTERLINE FROM THE FRONT OF THE WATER
 CLOSET. 2014 FBC-ACCESS SEC.604.7.
 12) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014
 FBC-ACCESS. SEC. 307.2. FOR PROTRUSION LIMITS. A SKIRT
 ON THE DRINKING FOUNTAINS MAY BE REQUIRED TO COMPLY.
 SUBMIT MANUF. SPCIFICATION SHEETS FOR THE ACCESSIBLE
 DRINKING FOUNTAIN THAT CLEARLY SHOWS THE HEIGHT OF THE
 LEADING EDGES OF THE UNIT. WPB AMEND. TO FBC SEC.
 107.2.1.
 .