Plan Review Details - Permit 15100233
Plan Review Stops For Permit 15100233
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-12-30 Cont ID  
Sent By jwitmer Date 2015-12-30 Time   Rev Time 0.00
Received By jwitmer Date 2015-12-30 Time 07:00 Sent To  
Notes
2015-12-30 08:36:14BUILDING PLAN REVIEW
 W. P. B. PERMIT:15100233
 ADD: 428 AVON RD. (PLUMB PERMIT APP)
 CONT: DON LIPSCOMB PLUMBING
 TEL: (561)310-9245
 E-MAIL: ???????????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 06/2015
 ACTION: DENIED
 2749 SQ. FT./ 30(MERCANTILE)= 92 OCCUPANTS
  
 1) COMPLIED. PLEASE MAKE CORRECTIONS FOR ADDRESSING THE
 SURVEY BY TARGET, SHEET A.02 INDICATES TWO SEPARATE
 BUILDINGS ON TWO SEPARATE LOTS AND DIFFERENT PROPERTY
 CONTROL NUMBERS.
 THE SURVEY INDICATES BY WAY OF A BUBBLE THE BUILDING
 LOCATED ON LOT 1480 ADDRESSED 428 AVON RD.
  
 2) 2ND REQUEST. THIS PERMIT IS BEING PULLED UNDER A CFC
 LICENSE, THE SCOPE OF WORK IS BEYOND WHAT A PLUMBING
 CONTRACTOR CAN DO, F. S. 489.105(M). A BUILDING,
 ELECTRICAL AND MECHANICAL CONTRACTOR WILL NEED TO SIGN
 ONTO THIS PROJECT BEFORE IT CAN BE ISSUED.
  
 3) 2ND REQUEST. 2014 ENERGY CODE C101.5.1.1
 ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS.
 ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS MAY
 UTILIZE FORM C402. FORM C402 CAN BE FOUND IN APPENDIX
 C.
  
 4) COMPLIED. SHEET A0.4 INDICATES THE NEW RESTROOM DOOR
 TO BE A 2'-8" DOOR. PLEASE REVIEW 2014 FBC-ACCESSIBLITY
 CODE 404.2.3 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM.
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES. OPENINGS MORE THAN 24
 INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR OPENING OF
 36 INCHES (915 MM) MINIMUM. THERE SHALL BE NO
 PROJECTIONS INTO THE REQUIRED CLEAR OPENING WIDTH LOWER
 THAN 34 INCHES (865 MM) ABOVE THE FINISH FLOOR OR
 GROUND.
  
 5) 2ND REQUEST. CHANGE OF OCCUPANCY BUSINESS TO
 MERCANTILE. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6A) NEW COMMENT. SHEET A-01 NOW SHOWS A NEW PAVED 60 X
 60 INCH RAMP WITH 2 STEEL BOLLARDS. NOTE FOR RAMPS A
 TOP LANDING AND BOTTOM LANDING ARE REQUIRED. 2014
 FBC-ACCESSIBILITY CODE 405.7 LANDINGS. RAMPS SHALL HAVE
 LANDINGS AT THE TOP AND THE BOTTOM OF EACH RAMP RUN.
 LANDINGS SHALL COMPLY WITH 405.7. E.01 SHOWS THIS IS
 ONE OF THE 2 REQUIRED EXITS.
  
 6B) NEW COMMENT. SINCE 2 ACCESSIBLE MEANS OF EGRESS ARE
 REQUIRED PLEASE PROVIDE WHICH OF THE OTHER EXITS
 COMPLIES WITH 2014 FBC-ACCESSIBILITY CODE 207.1 &
 SECTION 1007.1 OF THE 2003 IBC WHERE MORE THAN ONE
 MEANS OF EGRESS IS REQUIRED BY SECTION 1014.1 OR 1018.1
 FROM ANY ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF
 THE SPACE SHALL BE SERVED BY NOT LESS THAN TWO
 ACCESSIBLE MEANS OF EGRESS.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-06 Cont ID  
Sent By   Date 2015-11-06 Time 15:45 Rev Time  
Received By   Date 2015-11-06 Time 14:55 Sent To  
Notes
2015-11-06 15:35:37BUILDING PLAN REVIEW
 W. P. B. PERMIT:15100233
 ADD: 428 AVON RD. (PERMIT APP)
 CONT: DON LIPSCOMB PLUMBING
 TEL: (561)310-9245
 E-MAIL: ???????????????????
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. NOV. 06/2015
 ACTION: DENIED
  
 1) PLEASE MAKE CORRECTIONS FOR ADDRESSING THE SURVEY BY
 TARGET, SHEET A.02 INDICATES TWO SEPARATE BUILDINGS ON
 TWO SEPARATE LOTS AND DIFFERENT PROPERTY CONTROL
 NUMBERS.
 THE SURVEY INDICATES BY WAY OF A BUBBLE THE BUILDING
 LOCATED ON LOT 1480 ADDRESSED 428 AVON RD.
  
 THE BUILDING PLANS ARE ADDRESSED 429 AVON AND NEED TO
 BE CORRECTED, TO 428 AVON RD. THE OTHER ISSUE IN DOING
 A ADDRESS SEARCH THE PERMIT APPLICATION HAS THE WRONG
 LOT ON THE PERMIT APPLICATION OF LOT 1487 THE CORRECT
 LOT NUMBER IS 1480. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK TO BE COMPLETED UNDER THIS PERMIT.
  
 2) THIS PERMIT IS BEING PULLED UNDER A CFC LICENSE, THE
 SCOPE OF WORK IS BEYOND WHAT A PLUMBING CONTRACTOR CAN
 DO, F. S. 489.105(M). A BUILDING, ELECTRICAL AND
 MECHANICAL CONTRACTOR WILL NEED TO SIGN ONTO THIS
 PROJECT BEFORE IT CAN BE ISSUED.
  
 3) 2014 ENERGY CODE C101.5.1.1 ALTERATIONS, RENOVATIONS
 AND BUILDING SYSTEMS. ALTERATIONS, RENOVATIONS AND
 BUILDING SYSTEMS MAY UTILIZE FORM C402. FORM C402 CAN
 BE FOUND IN APPENDIX C.
  
 4) SHEET A0.4 INDICATES THE NEW RESTROOM DOOR TO BE A
 2'-8" DOOR. PLEASE REVIEW 2014 FBC-ACCESSIBLITY CODE
 404.2.3 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM.
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES. OPENINGS MORE THAN 24
 INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR OPENING OF
 36 INCHES (915 MM) MINIMUM. THERE SHALL BE NO
 PROJECTIONS INTO THE REQUIRED CLEAR OPENING WIDTH LOWER
 THAN 34 INCHES (865 MM) ABOVE THE FINISH FLOOR OR
 GROUND.
  
 5) CHANGE OF OCCUPANCY BUSINESS TO MERCANTILE. BEFORE A
 PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE
 PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2016-01-25 Cont ID  
Sent By mvaldes Date 2016-01-25 Time 10:25 Rev Time 0.00
Received By mvaldes Date 2016-01-25 Time 10:25 Sent To  
Notes
2016-01-25 11:02:38FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
 JOB PERMIT NUMBER: 15100233
 JOB ADDRESS: 428 AVON ROAD
 WEST PALM BEACH
 DATE: JAN 25 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
 1- PLEASE PROVIDE A MORE DETAILED RISER DIAGRAM TO
 INCLUDE LOAD CALCULATION, PANEL SCHEDULES, GROUNDING
 SPECS, WIRE AND CONDUIT ROUTING. FBC-107.3.5.3 AND NEC
 215.5
 2- PROVIDE CLARIFICATION OF 2 SERVICES IN ONE BUILDING
 AND NO OUTSIDE DISCONNECTING MEANS FOR FEEDER
 CONDUCTORS ? ARE THESE SERVICE CONDUCTORS CONSIDERED TO
 BE OUTSIDE OF THE BUILDING ? NEC 230.2 , NEC 230.6, NEC
 230.70 A1
 3- EMERGENCY AND EXIT LIGHTS SHALL BE FED BY LIGHTING
 CIRCUIT OF SAME LOCAL AREA AHEAD OF ANY LOCAL SWITCHES.
 NEC 700.12 F
 4- THE LOCATION OF SMOKE DETECTORS SHALL BE BASED ON
 POTENTIAL AMBIENT SOURCES OF SMOKE, MOISTURE, DUST OR
 FUMES, AND ELECTRICAL OR MECHANICAL INFLUENCES TO
 MINIMIZE NUISANCE ALARMS. (NOT PERMITTED IN BATHROOMS)
 NFPA 17.7.1.9
 5- MANDATORY LIGHTING CONTROLS SHALL BE INSTALLED IN
 ALL BATHROOMS (OCCUPANCY SENSORS) FBC-E C405 2.2.2
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-11-13 Cont ID  
Sent By skennedy Date 2015-11-13 Time 07:44 Rev Time 0.00
Received By skennedy Date 2015-11-13 Time 07:44 Sent To  
Notes
2015-11-13 07:50:341ST REVIEW: FBC 2014 5TH ED./ NEC 2011
 EXISTING BUILDING CHANGE OF OCCUPANCY
  
 THIS IS A QUALITY CHECK OF THE PREVIUOS REVIEW
 PERFORMED BY A CONTRACT EMPLOYEE REVERSING THE RESULT
 OF THAT REVIEW TO A STATUS OF FAIL AS FOLLOWS:
  
 THE PLANS ARE DEFICIENT AS MINIMUM PLAN REVIEW CRIRERIA
 TO DETERMINE COMPLIANCE IS NOT PROVIDED. PLEASE INCLUDE
 AN ELECTRCAL TO TO INDICATE AT THE MINIMUM, THE
 FOLLOWING.
  
 FBC 107.3.5.1.2 ELECTRICAL
 1. ELECTRICAL:
 WIRING
 SERVICES
 FEEDERS AND BRANCH CIRCUITS
 OVERCURRENT PROTECTION
 GROUNDING
 WIRING METHODS AND MATERIALS
 GFCIS
 2. EQUIPMENT
 3. SPECIAL OCCUPANCIES
 4. EMERGENCY SYSTEMS
 5. COMMUNICATION SYSTEMS
 6. LOW VOLTAGE
 7. LOAD CALCULATIONS
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-11-05 Cont ID  
Sent By ppetty Date 2015-11-05 Time 14:59 Rev Time 0.00
Received By ppetty Date 2015-11-05 Time 14:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-12-30 Cont ID  
Sent By pleduc Date 2015-12-30 Time   Rev Time 0.00
Received By pleduc Date 2015-12-30 Time 16:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-11-04 Cont ID  
Sent By wjolin Date 2015-11-04 Time 10:14 Rev Time 0.00
Received By wjolin Date 2015-11-04 Time 09:58 Sent To  
Notes
2015-11-04 10:14:38428 AVON ROAD
 PERMIT #15100233
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PERMIT APPLICATION INDICATES AN ADDRESS OF 428 AVON
 ROAD; HOWEVER, PLANS INDICATE AN ADDRESS OF 429 AVON
 ROAD.
  
 DESIGN SHALL CONFORM TO THE 5TH EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 PLANS INDICATE A CHANGE OF OCCUPANCY FROM BUSINESS TO
 MERCANTILE. PROVIDE A BUILDING AREA BREAKDOWN WITH
 OCCUPANT LOAD COUNT.
  
 PLANS INDICATE STORAGE RACK LAYOUTS. WHAT IS BEING
 STORED? HOW TALL IS THE STORAGE?
  
 PLANS INDICATE EMERGENCY LIGHT AND EXIT SIGN FIXTURES;
 HOWEVER, NO ELECTRICAL PLAN OR ELECTRICAL INFORMATION
 HAS BEEN PROVIDED.
  
 PROVIDE BOLLARDS OR SIMILAR TO PREVENT VEHICLES FROM
 BLOCKING EXIT DOORS IN PARKING LOT.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-25 Cont ID  
Sent By lmarchan Date 2016-01-25 Time 14:06 Rev Time 0.00
Received By lmarchan Date 2015-12-18 Time 13:55 Sent To  
Notes
2016-01-25 08:49:151/25 TO MVALDES DESK
  
  
2015-12-18 13:55:23B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-06 Cont ID  
Sent By jwitmer Date 2015-11-06 Time 15:41 Rev Time 0.00
Received By jwitmer Date 2015-10-07 Time 09:20 Sent To  
Notes
2015-10-08 09:20:48B03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-12-21 Cont ID  
Sent By ccole Date 2015-12-21 Time 17:07 Rev Time 0.00
Received By ccole Date 2015-12-21 Time 17:07 Sent To  
Notes
2015-12-21 17:10:182ND REVIEW 2014 MECHANICAL
 PERMIT #15100233
 12/21/15
  
 THE 1ST REVIEW COMMENTS STILL EXIST. I HAVE RE-PRINTED
 THEM BELOW FOR REVIEW, PLEASE COMPLY.
 1) REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION: CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
 IN ACCORDANCE WITH THIS SECTION PLEASE PROVIDE ENERGY
 CALCULATIONS- SEE THE FOLLOWING SECTIONS FOR COMPLIANCE
 SUBMITTAL INFORMATION: C101.5.1 COMPLIANCE MATERIALS.
 THE FLORIDA BUILDING COMMISSION SHALL APPROVE SPECIFIC
 COMPUTER SOFTWARE. THE CODE OFFICIAL SHALL BE PERMITTED
 TO APPROVE WORKSHEETS, COMPLIANCE MANUALS AND OTHER
 SIMILAR MATERIALS THAT MEET THE INTENT OF THIS CODE.
 C101.5.1.1 ALTERATIONS, RENOVATIONS AND BUILDING
 SYSTEMS. ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS
 MAY UTILIZE FORM C402. FORM C402 CAN BE FOUND IN
 APPENDIX C.
 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS ON
 THE PLAN IN ACCORDANCE WUITH TABLE 403.3 FBC-14
 MECHANICAL. THE CALCULATIONS SHALL INDICATE THE AMOUNT
 OF CFM'S OF OUTSIDE AIR REQUIRED FOR THE RETAIL SPACE
 OCCUPANTS, AND THE AMOUNT OF CFM'S PROVIDED BY THE
 EXISTING OR PROPOSED SYSTEMS.
 3) MECHANICAL EXHAUST IS REQUIRED FOR THE NEW TOILET
 ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-11-05 Cont ID  
Sent By ccole Date 2015-11-05 Time 11:48 Rev Time 0.00
Received By ccole Date 2015-11-05 Time 11:46 Sent To  
Notes
2015-11-05 11:53:131ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15100233
 11/5/2015
  
 1) REFER TO SECTION C101.4.4 FBC-14 ENERGY
 CONSERVATION: CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
 IN ACCORDANCE WITH THIS SECTION PLEASE PROVIDE ENERGY
 CALCULATIONS- SEE THE FOLLOWING SECTIONS FOR COMPLIANCE
 SUBMITTAL INFORMATION: C101.5.1 COMPLIANCE MATERIALS.
 THE FLORIDA BUILDING COMMISSION SHALL APPROVE SPECIFIC
 COMPUTER SOFTWARE. THE CODE OFFICIAL SHALL BE PERMITTED
 TO APPROVE WORKSHEETS, COMPLIANCE MANUALS AND OTHER
 SIMILAR MATERIALS THAT MEET THE INTENT OF THIS CODE.
 C101.5.1.1 ALTERATIONS, RENOVATIONS AND BUILDING
 SYSTEMS. ALTERATIONS, RENOVATIONS AND BUILDING SYSTEMS
 MAY UTILIZE FORM C402. FORM C402 CAN BE FOUND IN
 APPENDIX C.
 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING
 CODE AND PROVIDE MINIMUM VENTILATION CALCULATIONS ON
 THE PLAN IN ACCORDANCE WUITH TABLE 403.3 FBC-14
 MECHANICAL. THE CALCULATIONS SHALL INDICATE THE AMOUNT
 OF CFM'S OF OUTSIDE AIR REQUIRED FOR THE RETAIL SPACE
 OCCUPANTS, AND THE AMOUNT OF CFM'S PROVIDED BY THE
 EXISTING OR PROPOSED SYSTEMS.
 3) MECHANICAL EXHAUST IS REQUIRED FOR THE NEW TOILET
 ROOM IN COMPLIANCE WITH TABLE 403.3 FBC-14 MECHANICAL.
 PLEASE REVISE THE PLANS TO SHOW COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-12-26 Cont ID  
Sent By tklarge Date 2015-12-26 Time 03:09 Rev Time 0.00
Received By tklarge Date 2015-12-26 Time 02:40 Sent To  
Notes
2015-12-26 02:50:021) A SANITARY AND WATER RISER IS REQUIRED FOR THE NEW
 SERVICE SINK, THE NEW DRINKING FOUNTAINS AND A WATER
 RISER IS REQUIRED FOR THE ADDITION OF THE NEW TANKLESS
 WATER HEATER PER THE CITY OF WPB AMEND. TO THE FBC SEC.
 107.3.5.1.3. SUBMIT TWO COPIES OF A WATER AND SANITARY
 RISER FOR REVIEW. 2ND REQUEST.
 2) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE, NOT TO CENTERLINE AS SHOWN ON
 SHT.A.03. 2014 FBC ACCESSIBILITY SEC. 609.4. 2ND
 REQUEST.
 3) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9
 INCHES FROM THE FRONT OF THE WATER CLOSET TO THE
 CENTERLINE OF THE DISPENSER. 2014 FBCA- SEC.604.7
 4) PLEASE UPDATE THE MODIFICATION NOTE ON SHT.A.01 TO
 INCLUDE THE ADDITION OF THE DRINKING FOUNTAINS, THE MOP
 SINK, THE TANKLESS WATER HEATER AND THE ADDITION OF THE
 HOT WATER PIPING. WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-13 Cont ID  
Sent By gjohnson Date 2015-10-09 Time 17:14 Rev Time 0.00
Received By gjohnson Date 2015-10-09 Time 17:14 Sent To  
Notes
2015-10-13 06:59:191ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  
  
  
 PLUMBING COMMENTS:
  
 1.SHOW CLEAR FLOOR SPACE FOR LAVATORY IN ACCESSIBLE
 BATHROOM.
 PER WPB AMEN. SEC 107.2.1
 2.GRAB BARS SHALL COMPLY WITH.FBC ACC SEC 609.4
 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, EXCEPT THAT AT WATER CLOSETS FOR
 CHILDREN?S USE COMPLYING WITH 604.9, GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION 18 INCHES (455 MM)
 MINIMUM AND 27 INCHES (685 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE. THE
 HEIGHT OF THE LOWER GRAB BAR ON THE BACK WALL OF A
 BATHTUB SHALL COMPLY WITH 607.4.1.1 OR 607.4.2.1.
 3.TOILET SHALL COMPLY WITH FBC ACC.SEC 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION,
 4. A DRINKING FOUNTAIN IS REQUIRED TO COMPLY WITH FBC
 ACC. SEC
 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 5.PROVIDE SANITARY AND WATER RISER DIAGRAM.
 PER WPB AMEN. 107 .3.5.1.3(13)
 THE FOLLOWING IS AN UPDATED PLUMBING REVIEW AS OF
 12/9/15;
 1) SUBMIT AN EXISTING FLOOR PLAN AND A PROPOSED FLOOR
 PLAN THAT CLEARLY REFLECTS THE ENTIRE SCOPE OF WORK
 BEING DONE TO THE EXISTING TOILET ROOM. WPB AMEND. TO
 FBC SEC. 107.2.1.
 2) SINCE THIS IS A CHANGE OF OCCUPANCY, A SERVICE SINK
 IS REQUIRED FOR A MERCANTILE OCCUPANCY PER THE 2014
 FBC-PLBG. TABLE 403.1.
 3) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR REVIEW
 FOR ALL NEW PLUMBING FIXTURES. WPB AMEND. TO FBC SEC.
 107.3.5.1.3.
 4) THE LAVATORY IN THE ADA TOILET ROMM AND THE MOP SINK
 SHALL BE SUPPLIED WITH HOT OR TEMPERED WATER PER 2014
 FBC -PLBG.SEC.607.1.
 5)SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE LAVATORY IN ADA TOILET ROOM PER THE 2014
 FBC-ACCESS.SEC.604.3.1. & SEC. 606.2 & SEC.305.
 6) SHT. A.01 - THE UPDATE MODIFICATION NOTE SHALL
 INCLUDE THE ADDITION OF THE DRINKING FOUNTAINS, THE MOP
 SINK AND THE REQUIREMENT FOR HOT WATER TO THE SCOPE OF
 WORK. WPB AMEND.TO FBC 107.2.1
 7) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7-9
 INCHES TO THE CENTERLINE FROM THE FRONT OF THE WATER
 CLOSET. 2014 FBC-ACCESS SEC.604.7.
 8) THE DRINKING FOUNTAINS SHALL COMPLY WITH 2014
 FBC-ACCESS. SEC. 307.2. FOR PROTRUSION LIMITS. A SKIRT
 ON THE DRINKING FOUNTAINS MAY BE REQUIRED TO COMPLY.
 SUBMIT MANUF. SPCIFICATION SHEETS FOR THE ACCESSIBLE
 DRINKING FOUNTAIN THAT CLEARLY SHOWS THE HEIGHT OF THE
 LEADING EDGES OF THE UNIT. WPB AMEND. TO FBC SEC.
 107.2.1.
 9) TWO SETS OF PLANS REQUIRED WPB AMEND. TO FBC
 SEC107.1 THREE SETS OF PLANS HAVE BEEN VOIDED AND ONE
 HAS NOT LEAVING OMLY ONE SET FOR REVIEW.