Plan Review Details - Permit 15100089
Plan Review Stops For Permit 15100089
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-14 Cont ID  
Sent By shill Date 2015-10-14 Time 16:57 Rev Time 0.00
Received By shill Date 2015-10-14 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By shill Date 2015-10-05 Time 11:21 Rev Time 0.00
Received By shill Date 2015-10-05 Time 11:21 Sent To  
Notes
2015-10-05 11:21:56SEE NFIP COMMENTS
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-14 Cont ID  
Sent By shill Date 2015-10-14 Time 16:57 Rev Time 0.00
Received By shill Date 2015-10-13 Time 12:55 Sent To  
Notes
2015-10-13 12:55:23RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-05 Cont ID  
Sent By shill Date 2015-10-05 Time 15:16 Rev Time 0.00
Received By shill Date 2015-10-05 Time 11:22 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2015-10-14 Cont ID  
Sent By shill Date 2015-10-14 Time 16:57 Rev Time 0.00
Received By shill Date 2015-10-14 Time 16:57 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2015-10-05 Cont ID  
Sent By shill Date 2015-10-05 Time 11:23 Rev Time 0.00
Received By shill Date 2015-10-05 Time 11:23 Sent To  
Notes
2015-10-05 11:32:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 ELEVATION CERTIFICATE FOR MAIN HOUSE:
  
 C2E, ELEVATION OF MECHANICAL EQUIPMENT TO BE ABOVE 7.5,
 ELEVATION CERTIFICATE STATES ELEVATION IS 6.80. PLEASE
 NOTE THAT PHOTOGRAPHS SHOW THE MECHANICAL EQUIPMENT
 ELEVATED ON STANDS. PLEASE REVISE ELEVATION TO STATE
 ELEVATION OF EQUIPMENT (NOT CONCRETE PAD) AND ALSO
 REVISE COMMENTS IN SECTION D.
  
 SEE INSTRUCTIONS FOR BUILDING PHOTOGRAPHS, PHOTOGRAPHS
 MUST SHOW THE FOUNDATION WITH REPRESENTATIVE EXAMPLES
 OF FLOOD OPENINGS OR VENTS.
  
 ELEVATION CERTIFICATE FOR POOL HOUSE:
  
 A9(D) INDICATES THAT THERE ARE ENGINEERED FLOOD
 OPENINGS, PLEASE CLARIFY AS TO LOCATION (IN COMMENTS).
 FLOOD VENTS CAN BE USED ONLY FOR STORAGE, PARKING, AND
 ACCESS. ONLY THE PORTION OF THE FLOOD VENT WHICH IS
 BELOW 7.5' CAN BE COUNTED TOWARDS OPENINGS. COMPLIANCE
 NOT CLEAR.
  
 C2(A) STATES FFE IS 7.4, 7.5 REQUIRED. IF SLAB IS 7.5,
 FLOOD VENTS ARE NOT REQUIRED.
  
 SEE INSTRUCTIONS FOR PHOTOGRAPHS, FLOOD VENTS IN WALLS
 TO BE INCLUDED.
  
 SEE INSTRUCTIONS FOR ELEVATION CERTIFICATE, FLOOD VENT
 PRODUCT APPROVAL TO BE ATTACHED TO THE ELEVATION
 CERTIFICATE. I HAVE PRINTED THE PRODUCT APPROVAL COVER
 SHEET AND ATTACHED THE FLOOD VENT INFORMATION TO THE
 ELEVATION CERTIFICATE FOR THE HOUSE. PLEASE PROVIDE
 ANOTHER SET FOR THE CABANA, IF APPLICABLE.
  
  
  
  
  
  
  
  
  
  
  
  