Plan Review Details - Permit 15100028
Plan Review Stops For Permit 15100028
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-08-18 Cont ID  
Sent By cthroop Date 2016-08-18 Time 08:11 Rev Time 0.00
Received By cthroop Date 2016-08-18 Time 08:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2016-06-17 Cont ID  
Sent By cthroop Date 2016-06-17 Time 13:39 Rev Time 0.00
Received By cthroop Date 2016-06-06 Time 11:43 Sent To E
Notes
2016-06-06 11:44:48WAITING ON APPLICANT TO SUBMIT PRODUCT APPROVALS FOR
 WINDOWS AND DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-05-31 Cont ID  
Sent By cthroop Date 2016-05-31 Time 13:47 Rev Time 0.00
Received By cthroop Date 2016-05-31 Time 13:47 Sent To  
Notes
2016-05-31 14:14:14CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 DATE: 3/31/16
 ACTION: FAILED
  
 1. PROVIDE PRODUCT APPROVALS FOR ALL NEW WINDOWS AND
 DOORS SHOWN ON PLANS SUBJECT TO WIND LOADS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING,
 WINDOW, AND DOOR SUBMITTALS.
  
 2. THE PLAN APPEARS TO INCLUDE THE CONDITIONING OF A
 297 SF AREA OF THE RESIDENCE IDENTIFIED AS A DEN BUT ON
 RECORD AS A PORCH. THE PLAN ASSOCIATED WITH THE WINDOW
 REPLACEMENT PERMIT 10060887 COMPLETED IN 2010 DOES NOT
 SHOW THE CONSTRUCTION OF WALLS AND WINDOWS AS
 CONSISTENT WITH THE PROPOSED PLAN.
  
 PROOF OF COMPLIANCE MAY BE REQUIRED FOR PREVIOUSLY
 COMPLETED UN-PERMITTED WORK.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. PLEASE BE ADVISED
 THE INSPECTOR MAY REQUIRE PREVIOUSLY COMPLETED WORK TO
 BE MADE ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE
 ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK
 PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117.
  
 3. MECHANICAL PERMIT MAY BE REQUIRED.
  
 4. PROVIDE MECHANICAL PLAN TO SHOW SUPPLY DUCTS PER FBC
 - R M16.
  
 5. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
 CONTACT THE PBC IMPACT FEE OFFICE @ 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN AND TAKE TO THAT
 OFFICE FOR REVIEW. PLEASE RETURN STAMPED WITH A COPY OF
 RECEIPT AS APPLICABLE.
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-04-05 Cont ID  
Sent By cthroop Date 2016-04-05 Time 09:26 Rev Time 0.00
Received By cthroop Date 2016-04-05 Time 09:26 Sent To  
Notes
2016-04-05 10:13:042ND REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. VALUE APPEARS LOW.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
 FAILURE TO PROVIDE DOCUMENTATION OF ESTIMATED COSTS MAY
 DELAY THE APPLICATION PROCESS.
  
 2. PROVIDE ENERGY SUBMITTAL - RESIDENTIAL BUILDING FORM
 R405.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
 R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
 (MANDATORY).
 THE BUILDING OFFICIAL SHALL REQUIRE THAT AN ENERGY
 PERFORMANCE LEVEL (EPL) DISPLAY CARD BE COMPLETED AND
 CERTIFIED BY THE BUILDER TO BE ACCURATE AND CORRECT
 BEFORE FINAL APPROVAL OF THE BUILDING FOR OCCUPANCY.
 FLORIDA LAW [SECTION 553.9085, FLORIDA STATUTES)]
 REQUIRES THE EPL DISPLAY CARD TO BE INCLUDED AS AN
 ADDENDUM TO EACH SALES CONTRACT FOR BOTH PRESOLD AND
 NONPRESOLD RESIDENTIAL BUILDINGS. THE EPL DISPLAY CARD
 CONTAINS INFORMATION INDICATING THE ENERGY PERFORMANCE
 LEVEL AND EFFICIENCIES OF COMPONENTS INSTALLED IN A
 DWELLING UNIT. THE BUILDING OFFICIAL SHALL VERIFY THAT
 THE EPL DISPLAY CARD COMPLETED AND SIGNED BY THE
 BUILDER ACCURATELY REFLECTS THE PLANS AND
 SPECIFICATIONS SUBMITTED TO DEMONSTRATE CODE COMPLIANCE
 FOR THE BUILDING. A COPY OF THE EPL DISPLAY CARD CAN BE
 FOUND IN APPENDIX C.
  
 3. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 4, PROVIDE PRODUCT APPROVALS FOR NEW WINDOWS. PROVIDE
 EMERGENCY ESCAPE IN MASTER BEDROOM.
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW SUBMITTALS.
 FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED IN
 M-BEDROOM AS FOLLOWS: WHERE EMERGENCY ESCAPE AND RESCUE
 OPENINGS ARE PROVIDED THEY SHALL HAVE A SILL HEIGHT OF
 NOT MORE THAN 44 INCHES (1118 MM) MEASURED FROM THE
 FINISHED FLOOR TO THE BOTTOM OF THE CLEAR OPENING.
 R310.1.1 MINIMUM OPENING AREA GRADE FLOOR OPENINGS
 SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5 SQUARE FEET
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
 R310.1.3 MINIMUM OPENING WIDTH.
 THE MINIMUM NET CLEAR OPENING WIDTH SHALL BE 20 INCHES
  
 5. PROOF OF COMPLIANCE MAY BE REQUIRED FOR PREVIOUSLY
 COMPLETED UN-PERMITTED WORK.
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE PLEASE BE ADVISED
 THE INSPECTOR MAY REQUIRE PREVIOUSLY COMPLETED WORK TO
 BE MADE ACCESSIBLE AND OPEN FOR INSPECTION OR REQUIRE
 ADDITIONAL DOCUMENTATION FOR ALL CONCEALED WORK
 PREVIOUSLY COMPLETED PURSUANT TO FBC 110 & FBC 117.
  
 6. REF. DETAIL B-B, PG. A-1. PROVIDE CONNECTION DETAIL
 OF 16" STRAP TO EXISTING CONCRETE BEAM AND EXISTING
 ROOF FRAMING.
 7. REF. DETAIL A-A, PG. A-1. PROVIDE CONNECTION DETAIL
 FOR 2X8 WOOD FRAMING TO EXISTING CONCRETE BEAM AND TO
 EXISTING CONCRETE SLAB.
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 10:19 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 10:19 Sent To  
Notes
2015-10-20 10:52:491ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 THE PLAN APPEARS TO PROPOSE CONDITIONING A 297 SF AREA
 OF THE RESIDENCE IDENTIFIED AS A DEN BUT ON RECORD AS A
 PORCH. THE PLAN ASSOCIATED WITH WINDOW REPLACEMENT
 PERMIT 10060887 COMPLETED IN 2010 DOES NOT SHOW THE
 CONSTRUCTION OF WALLS AND WINDOWS AS CONSISTENT WITH
 THE PROPOSED PLAN.
  
 PLEASE PROVIDE INFORMATION AS TO THE EXISTING
 CONSTRUCTION OF THE 27' LONG AND 11' LONG EXTERIOR
 WALLS WHICH ENCLOSE THE 297SF PORCH. INCLUDE THERMAL
 INSULATION INFORMATION FOR THE WALLS AND CEILING.
 ADDITIONALLY PROVIDE AN ENERGY SUBMITTAL. SHOW ALL WORK
 THAT THERE IS NO PERMIT RECORD OF. PLEASE CLARIFY IF
 THERE IS TO BE A DOOR OR OPEN PASS THROUGH FOR THE AREA
 WHERE THE MASTER BEDROOM COMMUNICATES WITH THE PROPOSED
 DEN. PLEASE INDICATE WHAT THE PROPOSED MEANS OF
 EMERGENCY EGRESS IS FOR THE MASTER BEDROOM, IF IT IS
 THE EXISTING WINDOW TAKING THE PLACE OF A FORMER
 EXTERIOR SGD, IT WILL HAVE TO MEET THE REQUIREMENTS FOR
 NEW CONSTRUCTION.
  
 FBC 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. WHERE
 EMERGENCY ESCAPE AND RESCUE OPENINGS ARE PROVIDED THEY
 SHALL HAVE A SILL HEIGHT OF NOT MORE THAN 44 INCHES.
 R310.1.1 MINIMUM OPENING AREA.
 ALL EMERGENCY ESCAPE GRADE FLOOR OPENINGS SHALL HAVE A
 MINIMUM NET CLEAR OPENING OF 5 SQUARE FEET
 R310.1.2 MINIMUM OPENING HEIGHT.
 THE MINIMUM NET CLEAR OPENING HEIGHT SHALL BE 24 INCHES
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 THE CLAIMED VALUE APPEARS TO BE LOW FOR THE WORK
 PROPOSED AND ESPECIALLY AS THE RECORD DOES NOT
 DEMONSTRATE POSSIBLE PREVIOUS WORK TO ENCLOSE THE
 SCREEN ROOM TO A DEN AND MASTER SITTING ROOM.
  
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 PLEASE BE ADVISED IF PREVIOUS NON-PERMITTED WORK IS
 PROPOSED TO REMAIN IN PLACE, THEN PURSUANT TO FBC 117 -
 THE BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST REPORTS
 AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO BE MADE
 AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN APPROVED
 TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2016-07-28 Cont ID  
Sent By mvaldes Date 2016-07-28 Time 11:03 Rev Time 0.00
Received By mvaldes Date 2016-07-28 Time 10:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-20 Cont ID  
Sent By mvaldes Date 2016-06-20 Time 11:34 Rev Time 0.00
Received By mvaldes Date 2016-06-20 Time 11:34 Sent To  
Notes
2016-06-20 12:00:31SENT TO GEORGE PLUMBING.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-04 Cont ID  
Sent By mvaldes Date 2016-04-04 Time 15:51 Rev Time 0.00
Received By mvaldes Date 2016-04-04 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 10:59 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 10:59 Sent To  
Notes
2015-10-20 11:30:231ST REVIEW: FBC 2014 5TH ED.
  
 PLEASE SEE NOTES IN BUILDING REVIEW AS TO THE CONFLICT
 BETWEEN THE PROPOSED PLAN WHICH DESIGNATES THE 297 SF
 PORCH AS A DEN. PLEASE PROVIDE AN ELECTRICAL PLAN FOR
 THE AREA DESIGNATED AS A DEN AND REGARDING SMOKE
 DETECTORS AS FOLLOWS: EXISTING OR PROPOSED ELECTRICAL
 OUTLETS AND LIGHTING TO DEMONSTRATE COMPLIANCE WITH THE
 FOLLOWING:
  
 FBCRE4002.14 TAMPER-RESISTANT RECEPTACLES.
 IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15-
 AND 20-AMPERE RECEPTACLES SHALL BE LISTED
 TAMPER-RESISTANT RECEPTACLES.
  
 FBCRE3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION.
 ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE,
 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED
 BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER
 INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT.
  
 FBCRE3901.2.2 SPACING.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE
 OUTLET.
  
 E3903.3 ADDITIONAL LOCATIONS.
 AT LEAST ONE WALL-SWITCH-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE
 EXTERIOR SIDE OF EACH OUTDOOR EGRESS DOOR HAVING GRADE
 LEVEL ACCESS.
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2016-08-22 Cont ID  
Sent By cthroop Date 2016-08-22 Time 12:07 Rev Time 0.00
Received By cthroop Date 2016-08-22 Time 12:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-08-19 Cont ID  
Sent By cpuell Date 2016-08-19 Time 10:15 Rev Time 0.00
Received By cpuell Date 2016-07-13 Time 10:18 Sent To  
Notes
2016-07-14 10:18:19R24

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-06-22 Cont ID  
Sent By lmarchan Date 2016-06-22 Time 08:12 Rev Time 0.00
Received By lmarchan Date 2016-06-17 Time 13:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-31 Cont ID  
Sent By cthroop Date 2016-05-31 Time 13:47 Rev Time 0.00
Received By cthroop Date 2016-05-27 Time 14:18 Sent To  
Notes
2016-05-27 14:18:30RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-05 Cont ID  
Sent By cpuell Date 2016-04-05 Time 17:18 Rev Time 0.00
Received By cpuell Date 2016-03-18 Time 13:22 Sent To  
Notes
2016-03-18 13:22:15RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status P Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 12:01 Rev Time 0.00
Received By skennedy Date 2015-10-01 Time 13:29 Sent To  
Notes
2015-10-02 13:30:03R17

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status P Date 2016-08-22 Cont ID  
Sent By cthroop Date 2016-08-22 Time 12:07 Rev Time 0.00
Received By cthroop Date 2016-08-22 Time 12:07 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2016-08-18 Cont ID  
Sent By cthroop Date 2016-08-18 Time 08:11 Rev Time 0.00
Received By cthroop Date 2016-08-18 Time 08:11 Sent To  
Notes
2016-08-18 08:11:41CONTRACTOR TO SIGN OUT PLANS AFTER PLAN REVIEW.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2016-06-17 Cont ID  
Sent By cthroop Date 2016-06-17 Time 13:36 Rev Time 0.00
Received By cthroop Date 2016-06-17 Time 13:36 Sent To  
Notes
2016-06-17 13:37:53BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 4TH REVIEW
 DATE: 6/17/16
 ACTION: DENIED
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-05-31 Cont ID  
Sent By cthroop Date 2016-05-31 Time 13:40 Rev Time 0.00
Received By cthroop Date 2016-05-31 Time 13:40 Sent To  
Notes
2016-05-31 13:47:24CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-7918
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 3RD REVIEW
 DATE: 5/31/16
 ACTION: FAILED
  
 1. THE PLAN APPEARS TO INCLUDE THE CONDITIONING OF A
 297 SF AREA OF THE RESIDENCE IDENTIFIED AS A DEN BUT ON
 RECORD AS A PORCH.
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-04-05 Cont ID  
Sent By cthroop Date 2016-04-05 Time 09:24 Rev Time 0.00
Received By cthroop Date 2016-04-05 Time 09:24 Sent To  
Notes
2016-04-05 09:26:18 
 2ND REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURN STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 10:05 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 10:05 Sent To  
Notes
2015-10-20 10:05:291ST REVIEW: FBC 2014 5TH ED.
  
 THE PLAN APPEARS TO PROPOSE CONDITIONING A 297 SF AREA
 OF THE RESIDENCE APPARENTLY ON RECORD AS A PORCH.
 WINDOW REPLACEMENT PERMIT 10060887 PLAN COMPLETED IN
 2010 DOES NOT SHOW THE CONSTRUCTION OF WALLS AND
 WINDOWS AS CONSISTENT WITH THE PROPOSED PLAN,
 THEREFORE:
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-08-18 Cont ID  
Sent By jvalido Date 2016-08-18 Time 17:40 Rev Time 0.00
Received By jvalido Date 2016-08-18 Time 17:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-06-21 Cont ID  
Sent By jvalido Date 2016-06-21 Time 18:11 Rev Time 0.00
Received By jvalido Date 2016-06-21 Time 17:56 Sent To  
Notes
2016-06-21 18:09:27CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE MECHANICAL PLANS.
 (2) SHOW DUCT SIZES, SUPPLY OUTLET SIZES AND CFM
 QUANTITIES.
 (3) DIFFERENTIATE WHAT IS EXISTING AND WHAT IS NEW.
 (4) PROVIDE EXISTING AHU EQUIPMENT SCHEDULE (TO INCLUDE
 TOTAL CFM).
 (5) PROVIDE EXHAUST DUCT SIZES FOR KITCHEN EXHAUST.
 (6) HAVE ALL MANUFACTURER SPECIFICATION DOCUMENTATION
 FOR KITCHEN EXHAUST AT JOBSITE FOR INSPECTOR TO VERIFY
 INSTALLATION.
  
 M1503.4 MAKEUP AIR REQUIRED.
 EXHAUST HOOD SYSTEMS CAPABLE OF EXHAUSTING IN EXCESS OF
 400 CUBIC FEET PER MINUTE (0.19 M3/S) SHALL BE PROVIDED
 WITH MAKEUP AIR AT A RATE APPROXIMATELY EQUAL TO THE
 EXHAUST AIR RATE. SUCH MAKEUP AIR SYSTEMS SHALL BE
 EQUIPPED WITH A MEANS OF CLOSURE AND SHALL BE
 AUTOMATICALLY CONTROLLED TO START AND OPERATE
 SIMULTANEOUSLY WITH THE EXHAUST SYSTEM.
  
 EXCEPTION: IN A SINGLE-FAMILY DWELLING, MAKE-UP AIR IS
 NOT REQUIRED FOR RANGE HOOD EXHAUST SYSTEMS CAPABLE OF
 EXHAUSTING:
 (A) FOUR HUNDRED CUBIC FEET PER MINUTE OR LESS; OR
 (B) MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE
 THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY
 VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF
 THE STRUCTURE.
  
 FLORIDA ENERGY CODE FBC 2014
  
 PROVIDE (2) SETS OF SIGNED ENERGY CALCULATIONS (FORM
 R405-2014 AND HEAT LOAD CALCULATIONS). ONLY ONE
 PROVIDED
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-04-05 Cont ID  
Sent By jvalido Date 2016-04-05 Time 16:45 Rev Time 0.00
Received By jvalido Date 2016-04-05 Time 16:42 Sent To  
Notes
2016-04-05 16:45:08NO MECHANICAL WORK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-20 Cont ID  
Sent By skennedy Date 2015-10-20 Time 10:53 Rev Time 0.00
Received By skennedy Date 2015-10-20 Time 10:53 Sent To  
Notes
2015-10-20 10:57:511ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PLEASE SEE THE COMMENTS UNDER BUILDING AS TO THE
 REQUIRED ENERGY SUBMITTAL AND QUALITY OF PLAN REQUIRED.
 PROVIDE A MECHANICAL PLAN.
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2016-07-23 Cont ID  
Sent By tklarge Date 2016-07-23 Time 12:29 Rev Time 0.00
Received By tklarge Date 2016-07-23 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2016-06-21 Cont ID  
Sent By cthroop Date 2016-06-21 Time 10:02 Rev Time 0.00
Received By gjohnson Date 2016-06-21 Time 10:02 Sent To  
Notes
2016-06-21 10:39:133RD REVIEW
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 PLUMBING COMMENTS:
  
 1.NEW BATHROOM AND OUTDOOR KITCHEN ARE NOT VENTED SHOW
 ON RISER DIAGRAM. PER FBC PL SEC. P3101.2.1
  
 2. OUT DOOR KITCHEN SHALL TIE INTO BUILDING DRAIN DOWN
 STREAM OF BATHROOM GROUP. PER FBC PL SEC.P3108.1
  
 3. PROVIDE DETAILED SCOPE OF PLUMBING WORK IT IS
 UNCLEAR ON PLAN . THERE IS A NOTE FOR DOMESTIC WATER
 SCOPE OF WORK IT APPEARS THAT YOU ARE INSTALLING ALL
 NEW HOT AND COLD WATER SYSTEM PLEASE CLARIFY. ARE THE
 EXISTING FIXTURES BEING REPLACED REMAINING IN SAME
 LOCATION PLEASE CLARIFY. PER WPB AMEND. TO FBC SEC.
 107.2.1
  
 4. VALUATION OF JOB PLEASE CLARIFY AND UPDATE. YOUR
 PROPOSAL STATES A VALUE OF $60,000 DOES THIS INCLUDE
 FIXTURES, DOORS AND WINDOWS SUPPLIED BY OWNER, IT ALSO
 HAS TO INCLUDE NEW BATHROOM AND NEW WATER PIPING SYSTEM
 THESE WERE NOT IN YOUR DECRYPTION OF WORK. THE VALUE ON
 PERMIT APPLICATION DOES NOT MATCH WHAT IS ON YOUR
 PROPOSAL . THE VALUE ON PERMIT APPLICATION SHALL
 INCLUDE COMPLETE JOB EXCLUDING ONLY LAND VALUE. PER WPB
 AMEND. TO FBC SEC. 109.3
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-06-01 Cont ID  
Sent By skennedy Date 2016-06-01 Time 12:06 Rev Time 0.00
Received By skennedy Date 2016-06-01 Time 12:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-05 Cont ID  
Sent By gjohnson Date 2016-03-23 Time 12:34 Rev Time 0.00
Received By gjohnson Date 2016-03-23 Time 12:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-10-13 Cont ID  
Sent By gjohnson Date 2015-10-13 Time 10:37 Rev Time 0.00
Received By gjohnson Date 2015-10-13 Time 10:37 Sent To  
Notes
***NONE***