Plan Review Details - Permit 15091362
Plan Review Stops For Permit 15091362
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-24 Cont ID  
Sent By skennedy Date 2015-11-24 Time 16:49 Rev Time 0.00
Received By skennedy Date 2015-11-24 Time 16:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-11-02 Cont ID  
Sent By skennedy Date 2015-11-02 Time 08:17 Rev Time 0.00
Received By skennedy Date 2015-11-01 Time 10:57 Sent To  
Notes
2015-11-01 11:32:101ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 IT IS DIFFICULT TO ACERTAIN IF THE SUBMITTED PLAN HAS
 AN ORIGINAL SIGNATUR FRO THE ENGINEER OF RECORD
 CHRISTIAN LANGLEY PE#67382. IS THE EASY SEAL INSIGNIA A
 DIGALTAL SIGNATURE AUTHENTIFICATION METHOD? PLEASE
 CONFIRM THE SEAL COMPLIES WITH THE CRITERIA IN FAC 61G
 OR IF INTENDED TO BE DIGITAL, THEN FAC 61G1-16.005, IF
 SO, SUBMIT DIGITALLY.
  
 THE PLAN PROVIDES FOR CONNECTOR OPTIONS BASED UPON THE
 SUBSTRATE. PLEASE IDENTIFY THE SUBSTRATE AND SPECIFY A
 CONNECTOR OPTION.
  
 SEE ELECTRICAL COMMENTS.
 THERE IS A STATEMENT ON THE PLAN INDICATING THE DESIGN
 IS FOR STRUCTURAL INTEGRITY ONLY AND THAT THE
 ELECTRICAL DESIGN ON THE PLAN IS THE SOLE
 RESPONSIBILITY OF THE ELECTRICIAN. PLEASE PROVIDE AN
 ELECTRICAL DESIGN BY SOMEONE RESPONSIBLE. INDICATE AT A
 MINIMUM COMPLIANCE WITH THE FOLLOWING AS APPLICABLE:
 APPLICABLE ELECTRICAL CODE IN EFFECT,
 NEC . 600, LISTING. DISCONNECT
 FBC 505, AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR
 WHEN NOT REQUIRED.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-11-24 Cont ID  
Sent By skennedy Date 2015-11-24 Time 16:49 Rev Time 0.00
Received By skennedy Date 2015-11-24 Time 16:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-01 Cont ID  
Sent By skennedy Date 2015-11-01 Time 11:19 Rev Time 0.00
Received By skennedy Date 2015-11-01 Time 11:19 Sent To  
Notes
2015-11-01 11:37:161ST REVIEW: FBC 2014 5TH ED. NEC 2011
  
 THERE IS A STATEMENT ON THE PLAN INDICATING THE DESIGN
 IS FOR STRUCTURAL INTEGRITY ONLY AND THAT THE
 ELECTRICAL DESIGN ON THE PLAN IS THE SOLE
 RESPONSIBILITY OF THE ELECTRICIAN. PLEASE PROVIDE AN
 ELECTRICAL DESIGN BY SOMEONE RESPONSIBLE . INDICATE AT
 A MINIMUM COMPLIANCE WITH THE FOLLOWING AS APPLICABLE:
 1) ELECTRICAL CODE IN EFFECT,
 2) NEC . 600, LISTING. DISCONNECT
 3) FBC 505, AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED.
 4) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-24 Cont ID  
Sent By skennedy Date 2015-11-24 Time 16:49 Rev Time 0.00
Received By skennedy Date 2015-11-09 Time 15:45 Sent To  
Notes
2015-11-09 15:45:26ROUTED TO ESCHEIDER VIA SGRAHAM'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-02 Cont ID  
Sent By skennedy Date 2015-11-02 Time 08:17 Rev Time 0.00
Received By skennedy Date 2015-09-30 Time 14:11 Sent To  
Notes
2015-10-01 14:11:14ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-11-24 Cont ID  
Sent By eschneid Date 2015-11-24 Time 13:10 Rev Time 0.25
Received By eschneid Date 2015-11-24 Time 13:10 Sent To B
Notes
2015-11-24 13:24:31WESTERN FACADE BUILDING IDENTITY SIGN - HILTON TEXT
 ONLY
  
 ALLOWED: 200 SQ. FT.
 PROPOSED: 88.4 SQ. FT.
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-10-28 Cont ID  
Sent By eschneid Date 2015-10-28 Time 09:26 Rev Time 0.50
Received By eschneid Date 2015-10-27 Time 16:39 Sent To B
Notes
2015-10-28 09:28:46WESTERN FACADE SIGN
  
 1) STAFF IS CONFUSED BY WHAT IS ACTUALLY BEING
 PERMITTED FOR THE SIGN ON THE WEST ELEVATION. THE BARON
 SIGN COLOR RENDERING SHEETS 3 AND 4 SHOW THE WORD
 "HILTON" WITH SCRIPT "WEST PALM BEACH" BELOW. THE BARON
 SIGN DETAIL SHEET 2 AND THE LAURETNO SIGN GROUP SHEET 1
 SHOWS ONLY THE WORD "HILTON".
  
 2) THE DIMENSIONS WERE ONLY SHOWN FOR THE "HILTON"
 TEXT. IF THIS IS TO BE THE ONLY SIGN ON THE WESTERN
 FACADE, THEN THE SIZE COMPLIES WITH THE CODE.
  
 WESTERN FACADE BUILDING IDENTITY SIGN - HILTON TEXT
 ONLY
  
 ALLOWED: 200 SQ. FT.
 PROPOSED: 88.4 SQ. FT.
  
 NORTHEAST FACADE SIGN
  
 1) STAFF IS CONFUSED BY WHAT IS ACTUALLY BEING
 PERMITTED FOR THE SIGN ON THE NORTHEAST ELEVATION. THE
 BARON SIGN COLOR RENDERING SHEETS 1 AND 2 SHOWS THE
 WORD "HILTON" WITH SCRIPT "WEST PALM BEACH" BELOW. THE
 BARON SIGN DETAIL SHEET 1 SHOWS ONLY THE WORD "HILTON".
  
 2) THE SIGN CODE PERMITS TWO TYPES OF SIGNS FOR THIS
 BUILDING, THE BUILDING IDENTITY SIGN AND THE EXTERNAL
 SIGN BAND. THE PROPOSED NORTHEAST FACADE SIGN IS TOO
 TALL TO BE AN EXTERNAL SIGN BAND (MAXIMUM HEIGHT 36
 INCHES), SO STAFF IS REVIEWING IT AS A BUILDING
 IDENTITY SIGN. THERE MAY BE ONLY TWO BUILDING IDENTITY
 SIGNS PER BUILDING, SO NO MORE BUILDING IDENTITY SIGNS
 WOULD BE PERMITTED.
  
 3) THE DIMENSIONS WERE ONLY SHOWN FOR THE "HILTON"
 TEXT. IF THIS IS TO BE THE ONLY SIGN ON THE WESTERN
 FACADE, THEN THE SIZE COMPLIES WITH THE CODE.
  
 NORTHEAST FACADE BUILDING IDENTITY SIGN - HILTON TEXT
 ONLY
  
 ALLOWED: 200 SQ. FT.
 PROPOSED: 69.9 SQ. FT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.