Plan Review Details - Permit 15091362
Plan Review Stops For Permit 15091362 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2015-11-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-11-24 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-11-24 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-11-02 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-11-02 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-11-01 |
Time |
10:57 |
Sent To |
|
|
Notes |
2015-11-01 11:32:10 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | | IT IS DIFFICULT TO ACERTAIN IF THE SUBMITTED PLAN HAS | | AN ORIGINAL SIGNATUR FRO THE ENGINEER OF RECORD | | CHRISTIAN LANGLEY PE#67382. IS THE EASY SEAL INSIGNIA A | | DIGALTAL SIGNATURE AUTHENTIFICATION METHOD? PLEASE | | CONFIRM THE SEAL COMPLIES WITH THE CRITERIA IN FAC 61G | | OR IF INTENDED TO BE DIGITAL, THEN FAC 61G1-16.005, IF | | SO, SUBMIT DIGITALLY. | | | | THE PLAN PROVIDES FOR CONNECTOR OPTIONS BASED UPON THE | | SUBSTRATE. PLEASE IDENTIFY THE SUBSTRATE AND SPECIFY A | | CONNECTOR OPTION. | | | | SEE ELECTRICAL COMMENTS. | | THERE IS A STATEMENT ON THE PLAN INDICATING THE DESIGN | | IS FOR STRUCTURAL INTEGRITY ONLY AND THAT THE | | ELECTRICAL DESIGN ON THE PLAN IS THE SOLE | | RESPONSIBILITY OF THE ELECTRICIAN. PLEASE PROVIDE AN | | ELECTRICAL DESIGN BY SOMEONE RESPONSIBLE. INDICATE AT A | | MINIMUM COMPLIANCE WITH THE FOLLOWING AS APPLICABLE: | | APPLICABLE ELECTRICAL CODE IN EFFECT, | | NEC . 600, LISTING. DISCONNECT | | FBC 505, AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR | | WHEN NOT REQUIRED. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2015-11-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-11-24 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-11-24 |
Time |
16:49 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-11-01 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-11-01 |
Time |
11:19 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-11-01 |
Time |
11:19 |
Sent To |
|
|
Notes |
2015-11-01 11:37:16 | 1ST REVIEW: FBC 2014 5TH ED. NEC 2011 | | | | THERE IS A STATEMENT ON THE PLAN INDICATING THE DESIGN | | IS FOR STRUCTURAL INTEGRITY ONLY AND THAT THE | | ELECTRICAL DESIGN ON THE PLAN IS THE SOLE | | RESPONSIBILITY OF THE ELECTRICIAN. PLEASE PROVIDE AN | | ELECTRICAL DESIGN BY SOMEONE RESPONSIBLE . INDICATE AT | | A MINIMUM COMPLIANCE WITH THE FOLLOWING AS APPLICABLE: | | 1) ELECTRICAL CODE IN EFFECT, | | 2) NEC . 600, LISTING. DISCONNECT | | 3) FBC 505, AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT | | OR WHEN NOT REQUIRED. | | 4) 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL | | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, | | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS | | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH | | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES | | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE | | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE | | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | DESIGN. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-11-24 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-11-24 |
Time |
16:49 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-11-09 |
Time |
15:45 |
Sent To |
|
|
Notes |
2015-11-09 15:45:26 | ROUTED TO ESCHEIDER VIA SGRAHAM'S DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-11-02 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-11-02 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-09-30 |
Time |
14:11 |
Sent To |
|
|
Notes |
2015-10-01 14:11:14 | ROUTED TO ZONING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2015-11-24 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2015-11-24 |
Time |
13:10 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2015-11-24 |
Time |
13:10 |
Sent To |
B |
|
Notes |
2015-11-24 13:24:31 | WESTERN FACADE BUILDING IDENTITY SIGN - HILTON TEXT | | ONLY | | | | ALLOWED: 200 SQ. FT. | | PROPOSED: 88.4 SQ. FT. | | | | | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2015-10-28 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2015-10-28 |
Time |
09:26 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2015-10-27 |
Time |
16:39 |
Sent To |
B |
|
Notes |
2015-10-28 09:28:46 | WESTERN FACADE SIGN | | | | 1) STAFF IS CONFUSED BY WHAT IS ACTUALLY BEING | | PERMITTED FOR THE SIGN ON THE WEST ELEVATION. THE BARON | | SIGN COLOR RENDERING SHEETS 3 AND 4 SHOW THE WORD | | "HILTON" WITH SCRIPT "WEST PALM BEACH" BELOW. THE BARON | | SIGN DETAIL SHEET 2 AND THE LAURETNO SIGN GROUP SHEET 1 | | SHOWS ONLY THE WORD "HILTON". | | | | 2) THE DIMENSIONS WERE ONLY SHOWN FOR THE "HILTON" | | TEXT. IF THIS IS TO BE THE ONLY SIGN ON THE WESTERN | | FACADE, THEN THE SIZE COMPLIES WITH THE CODE. | | | | WESTERN FACADE BUILDING IDENTITY SIGN - HILTON TEXT | | ONLY | | | | ALLOWED: 200 SQ. FT. | | PROPOSED: 88.4 SQ. FT. | | | | NORTHEAST FACADE SIGN | | | | 1) STAFF IS CONFUSED BY WHAT IS ACTUALLY BEING | | PERMITTED FOR THE SIGN ON THE NORTHEAST ELEVATION. THE | | BARON SIGN COLOR RENDERING SHEETS 1 AND 2 SHOWS THE | | WORD "HILTON" WITH SCRIPT "WEST PALM BEACH" BELOW. THE | | BARON SIGN DETAIL SHEET 1 SHOWS ONLY THE WORD "HILTON". | | | | 2) THE SIGN CODE PERMITS TWO TYPES OF SIGNS FOR THIS | | BUILDING, THE BUILDING IDENTITY SIGN AND THE EXTERNAL | | SIGN BAND. THE PROPOSED NORTHEAST FACADE SIGN IS TOO | | TALL TO BE AN EXTERNAL SIGN BAND (MAXIMUM HEIGHT 36 | | INCHES), SO STAFF IS REVIEWING IT AS A BUILDING | | IDENTITY SIGN. THERE MAY BE ONLY TWO BUILDING IDENTITY | | SIGNS PER BUILDING, SO NO MORE BUILDING IDENTITY SIGNS | | WOULD BE PERMITTED. | | | | 3) THE DIMENSIONS WERE ONLY SHOWN FOR THE "HILTON" | | TEXT. IF THIS IS TO BE THE ONLY SIGN ON THE WESTERN | | FACADE, THEN THE SIZE COMPLIES WITH THE CODE. | | | | NORTHEAST FACADE BUILDING IDENTITY SIGN - HILTON TEXT | | ONLY | | | | ALLOWED: 200 SQ. FT. | | PROPOSED: 69.9 SQ. FT. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|
|
|