Plan Review Details - Permit 15091327
Plan Review Stops For Permit 15091327
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-12-09 Cont ID  
Sent By skennedy Date 2015-12-09 Time 10:25 Rev Time 0.00
Received By skennedy Date 2015-12-09 Time 10:11 Sent To  
Notes
2015-12-09 10:18:212ND REVIEW: FBC 2014 5TH ED.
  
 PROVISIONALLY APPROVED:
  
 THE PURPOSE OF THIS APPLICATION IS TO ATTEMPT TO
 LEGALLY ESTABLISH AN ATTACHED STORAGE ROOM THAT WAS
 BUILT WITHOUT A PERMIT HOWEVER; THE APPLICATION
 DESCRIPTION ONLY INDICATES POURING A SLAB AND IS VALUED
 AT $500.00. THE PERMIT DESCRIPTION HAS BEEN CHANGED TO
 AN APPROPRIATE DESCRIPTION AND THE VALUE IS INCREASED
 TO $6,020.00 BASED FBC 109.3 RESULTING IN AN INCREASED
 PERMIT FEE.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE DOOR SUBMITTALS.
  
 PLEASE NOTE THE ROOFING PRODUCT SUPPLIED, NOA
 12-0601.10 REQUIRES ENHANCED FASTENING CALCULATIONS PER
 IT'S LIMITATION #7. PLEASE PROVIDE AS A SUBMITTAL.
  
 PLEASE NOTE THE WINDOW PRODUCT APPROVAL ORIGINALLY
 SUPPLIED WITH PERMIT 15070876 HAS BEEN INCORPORATED
 INTO THIS APPLICATION AND APPLICATION 15070876 HAS BEEN
 REVOKED AND FEES PAID IN ASSOCIATION WITH THAT
 APPLICATION ARE TO BE CREDITED TO THIS APPLICATION.
  
 FBC 107.3.5.3 INDICATE THE MEANS OF TERMITE PROTECTION
 PROPOSED PURSUANT TO FBC-R318.
  
 GENERAL AFTER THE FACT PERMITS
  
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-11-08 Cont ID  
Sent By skennedy Date 2015-11-08 Time 09:37 Rev Time 0.00
Received By skennedy Date 2015-11-08 Time 09:37 Sent To  
Notes
2015-11-08 10:00:411ST REVIEW: FBC 2014 5TH ED.
 ADMINISTRATIVE REVIEW INTENDED TO PROVIDE DIRECTION TO
 THE APPLICANT AS TO HOW TO PROCEED.
  
 IT APPEARS THE PURPOSE OF THIS APPLICATION IS TO
 ATTEMPT TO LEGALLY ESTABLISH AN ATTACHED STORAGE ROOM
 THAT WAS BUILT WITHOUT A PERMIT HOWEVER; THE
 APPLICATION DESCRIPTION ONLY INDICATES POURING A SLAB
 AND IS VALUED AT $500.00. THE VALUE IS INCREASED TO
 $6,020.00 BASED FBC 109.3 AND THE RESULTING INCREASED
 PERMIT FEES IS TBD AND MUST BE PAID IN FULL PRIOR TO
 THE REVIEW CONTINUING FURTHER. THE PLANS SHOW CREATING
 A NEW FOUNDATION AND DO NOT INDICATING THE STRUCTURE
 ABOVE WAS CONSTRUCTED WITHOUT A PERMIT AND DOES NOT
 CERTIFY THE WORK IS CODE COMPLIANT, AND DOES NOT
 SPECIFY MEANS AND METHODS TO ASSURE THE STRUCTURE WILL
 BE CODE COMPLIANT. MORE DESCRIPTIVE PLANS ARE REQUIRED
 AS WELL AS AN ENGINEER'S EVALUATION OF ALL THE
 STRUCTURE WITH IN ORDER TO EVALUATE, AND SPECIFY
 REQUIRED ENHANCEMENTS AND TO CERTIFY ANY WORK THAT IS
 COVERED SUCH AS BUT NOT LIMITED TO ALL NAILING,
 STRAPPING, AND ALL ROOF COVERING COMPONENTS, PRODUCT
 APPROVAL OF ROOFING, WINDOWS, AND DOORS ARE REQUIRED TO
 BE SUPPLIED AND REVIEWED BY THE DESIGNER OF RECORD.
  
 NOTE: THE OWNER MAY WISH TO CONSIDER DEMOLITION AS AN
 OPTION FOR THE 140 SF ILLEGALLY ESTABLISHED ADDITION.
  
 PLEASE REFERENCE:
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 FBC 107.3.5.3 ? INDICATE THE MEANS OF TERMITE
 PROTECTION PROPOSED PURSUANT TO FBC-R318.
  
 GENERAL AFTER THE FACT PERMITS
  
 FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
  
 FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-10-26 Cont ID  
Sent By aclange Date 2015-10-26 Time 11:20 Rev Time 0.00
Received By aclange Date 2015-10-26 Time 11:20 Sent To  
Notes
2015-10-26 11:21:35REVIEWED BY:
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, BLDG.
 757-769-9505
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-09 Cont ID  
Sent By skennedy Date 2015-12-09 Time 10:10 Rev Time 0.00
Received By skennedy Date 2015-12-09 Time 10:10 Sent To  
Notes
2015-12-09 10:11:262ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 PROVISIONALLY APPROVED:
  
 ELECTRICAL. NO ELECTRICAL PLAN IS PROVIDED ALTHOUGH
 ELECTRICAL IS REQUIRED. A REVIEW CANNOT BE PERFORMED.
 PROVIDE A PLAN AS A REVISION PER FBC 107; SHOW AT A
 MINIMUM, WIRE SIZES, WIRING METHOD, SHOW CIRCUITS,
 DEVICES, LUMINARIES ON FLOOR PLAN. AND DEMONSTRATE
 COMPLIANCE WITH FBCRE3901.9 BASEMENTS, GARAGES AND
 ACCESSORY BUILDINGS, & FBCE3903 LIGHTING OUTLETS;
 E3903.3 ADDITIONAL LOCATIONS; STORAGE ROOM & AT EGRESS.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-08 Cont ID  
Sent By skennedy Date 2015-11-08 Time 09:37 Rev Time 0.00
Received By skennedy Date 2015-11-08 Time 09:37 Sent To  
Notes
2015-11-08 09:47:541ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
  
 ELECTRICAL. NO ELECTRICAL PLAN IS PROVIDED ALTHOUGH
 ELECTRICAL IS REQUIRED. A REVIEW CANNOT BE PERFORMED.
 PROVIDE A PLAN PER FBC 107; SHOW AT A MINIMUM, WIRE
 SIZES, WIRING METHOD, SHOW CIRCUITS, DEVICES,
 LUMINARIES ON FLOOR PLAN. AND DEMONSTRATE COMPLIANCE
 WITH FBCRE3901.9 BASEMENTS, GARAGES AND ACCESSORY
 BUILDINGS, & FBCE3903 LIGHTING OUTLETS; E3903.3
 ADDITIONAL LOCATIONS; STORAGE ROOM & AT EGRESS.
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-18 Cont ID  
Sent By skennedy Date 2015-12-18 Time 11:16 Rev Time 0.00
Received By skennedy Date 2015-12-17 Time 09:02 Sent To  
Notes
2015-12-18 09:02:17RESUB ROUTED TO SKENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-09 Cont ID  
Sent By skennedy Date 2015-12-09 Time 10:25 Rev Time 0.00
Received By skennedy Date 2015-12-01 Time 14:43 Sent To  
Notes
2015-12-01 14:43:10RESUB ROUTED TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-08 Cont ID  
Sent By skennedy Date 2015-11-08 Time 09:37 Rev Time 0.00
Received By skennedy Date 2015-09-30 Time 13:08 Sent To  
Notes
2015-09-30 13:08:45ROUTED TO ZONING

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-12-18 Cont ID  
Sent By skennedy Date 2015-12-18 Time 11:16 Rev Time 0.00
Received By skennedy Date 2015-12-18 Time 11:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-11-08 Cont ID  
Sent By skennedy Date 2015-11-08 Time 09:37 Rev Time 0.00
Received By skennedy Date 2015-11-08 Time 09:37 Sent To  
Notes
2015-11-08 09:48:04PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-12-02 Cont ID  
Sent By sgraham Date 2015-12-02 Time 09:48 Rev Time 0.00
Received By sgraham Date 2015-12-02 Time 09:48 Sent To AD
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-10-01 Cont ID  
Sent By sgraham Date 2015-10-01 Time 09:04 Rev Time 0.00
Received By sgraham Date 2015-10-01 Time 09:04 Sent To B
Notes
***NONE***