Plan Review Stops For Permit 15091282 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2015-10-01 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-10-01 |
Time |
10:06 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-10-01 |
Time |
9:00 |
Sent To |
I |
|
Notes |
2015-10-01 10:09:11 | I RECEIVED THE PDF AND MADE TWO CORRECTIONS. | | 1. THE MANUFACTURER SPECS CALL FOR A 15 AMP FUSE NOT A | | 20. | | 2. MADE A NOTE TO THE NEC 300.5 REQUIREMENT SHOULD THE | | RACEWAY BE UNDERGROUND. | | THIS WAS APPROVED AS INDICATED ABOVE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-09-29 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-09-29 |
Time |
19:23 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-09-29 |
Time |
19:14 |
Sent To |
|
|
Notes |
2015-09-29 19:25:59 | INCOMPLETE SUBMITTAL. EMAILED EC FOR THE REMAINDER OF | | THE DOCUMENTATION. IN THE MEANTIME THIS IS ON MY DESK. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-10-01 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-10-01 |
Time |
10:11 |
Rev Time |
|
Received By |
albarran |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2015-10-01 10:12:52 | 10/1/15 PASSED ELECTRICAL REVIEW WITH EXCEPTIONS AS | | NOTED. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL | | READY BIN "S". MA |
|
|
|