2015-11-17 07:49:07 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15091271 |
| ADD: 2600 N. FLAGLER DR. SUITE # 307 |
| CONT: RHODES REMODELING |
| TEL: (561)798-1382 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. NOV.17/ 2015 |
| ACTION: DENIED |
| |
| 1) COMPLIED. CONTRACTOR (QUALIFIER) ACTING AS THE |
| DESIGNER OF RECORD SHALL PRINT THEIR NAME, SIGN THEIR |
| NAME AND LICENSE NUMBER TO THE PLANS THEY HAVE CREATED. |
| 107.1. |
| |
| 2) THE FLOOR PLAN AND ITEMIZED LIST OF THE SCOPE OF |
| WORK TO BE COMPLETED UNDER THIS PERMIT LIST THE REMOVAL |
| OF FLOOR TILE IN THE MASTER BATH AND GUEST BATH. PLEASE |
| PROVIDE COMPLIANCE WITH: |
| |
| 2A)2ND REQUEST. THE REPORT SUBMITTED PROLEX MSC MEGA |
| SOUND CONTROL MEMBRANE UNDERLAYMENT WITH A IIC = 68.0 |
| DB IS FO A 8 INCH SLAB WITH A DROPPED SUSPENDED PLENUM |
| CEILING WITH INSULATION. THE REPORT HAS TO BE TESTED ON |
| A 6 INCH CONCRETE SLAB NO DROPPED CEILING. |
| |
| 1ST REVIEW. FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 2B) THE REPORT SUBMITTED PROLEX MSC MEGA SOUND CONTROL |
| MEMBRANE UNDERLAYMENT WITH A STC = 72 DB IS FO A 8 INCH |
| SLAB WITH A DROPPED SUSPENDED PLENUM CEILING WITH |
| INSULATION. THE REPORT HAS TO BE TESTED ON A 6 INCH |
| CONCRETE SLAB NO DROPPED CEILING. |
| |
| |
| 1ST REVIEW. FBC-B 2014 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 2C)COMPLIED. FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION |
| 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND |
| SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 3) 2ND REQUEST. MR BOARD CAN NOT BE USED IN A SHOWER. |
| IT IS OK TO USE AROUND A TOLIET COMPARTMENT. SEE CODE |
| SECTION BELOW. |
| |
| 1ST REVIEW. THE FLOOR PLAN AND ITEMIZED LIST OF THE |
| SCOPE OF WORK TO BE COMPLETED UNDER THIS PERMIT LIST |
| THE REMOVAL OF SHOWER WALLS UP TO 48 INCHES. PLEASE |
| PROVIDE WHAT TYPE OF TILE BACKING MATERIAL TO BE |
| INSTALLED IN THE SHOWER. |
| 2014 FBC-B 2509.2 BASE FOR TILE. |
| GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENTITIOUS |
| BACKER UNITS IN COMPLIANCE WITH ASTM C 1178, C 1288 OR |
| C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 15091271 2600 N FLAGLER # 307.DOC |
| |
| |
| |
| |
| |