Plan Review Details - Permit 15091246
Plan Review Stops For Permit 15091246 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2015-12-02 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-02 |
Time |
06:06 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-02 |
Time |
05:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-10-04 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-10-04 |
Time |
06:26 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-10-04 |
Time |
06:10 |
Sent To |
|
|
Notes |
2015-10-04 05:53:55 | 1) SHOW THE DIMENSIONS OF THE AREA OF THE SLAB TO BE | | REMOVED AND SUBMIT A SLAB REPAIR DETAIL SHOWING HOW THE | | THE STRUCTURAL INTEGRITY OF THE SLAB WILL BE | | MAINTAINED. SHOW THE SIZE OF DOWELS, SPACING OF DOWELS, | | EMBEDMENT DEPTH INTO EXISTING SLAB AND NEW SLAB AND HOW | | SECURED INTO EXISTING SLAB. WPB AMEND. TO FBC SEC. | | 107.2.1. | | 2) THE SOIL SHALL BE POISONED FOR TERMITES PRIOR TO | | PLACEMENT OF CONCRETE AND TERMITE CERTIFICIATE SHALL BE | | ON JOBSITE. | | 3) SHOW THE REQUIRED VAPOR BARRIER ON THE SLAB REPAIR | | DETAIL & AND PSI OF CONCRETE. COMPLY WITH FBC | | SEC.1816,1907. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-12-02 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-02 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-01 |
Time |
14:51 |
Sent To |
|
|
Notes |
2015-12-01 14:51:51 | RESUB ROUTED TO TKLARGE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-10-04 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-10-04 |
Time |
06:37 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-09-29 |
Time |
15:59 |
Sent To |
P |
|
Notes |
2015-09-29 15:59:54 | PLUMBING UNDER $5000 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2015-12-02 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-02 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-02 |
Time |
05:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-10-04 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-10-04 |
Time |
06:37 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-10-04 |
Time |
06:26 |
Sent To |
|
|
Notes |
2015-10-04 05:53:15 | 1) SHOW THE SIZE AND LENGTH OF THE PIPE BEING REPLACED | | AND IF IT IS SANITARY OR WATER. I ASSUME IT IS WATER. | | IF SO, INDICATE HOW THE REPAIR WILL BE DONE.WPB AMEND. | | TO FBC SEC. 107.2.1. | | 2) SHOW THE DIMENSIONS OF THE AREA OF THE SLAB TO BE | | REMOVED AND SUBMIT A SLAB REPAIR DETAIL SHOWING HOW THE | | THE STRUCTURAL INTEGRITY OF THE SLAB WILL BE | | MAINTAINED. SHOW THE SIZE OF DOWELS, SPACING OF DOWELS, | | EMBEDMENT DEPTH INTO EXISTING SLAB AND NEW SLAB AND HOW | | SECURED INTO EXISTING SLAB. WPB AMEND. TO FBC SEC. | | 107.2.1. | | 3) THE SOIL SHALL BE POISONED FOR TERMITES PRIOR TO | | PLACEMENT OF CONCRETE AND TERMITE CERTIFICIATE SHALL BE | | ON JOBSITE. | | 4) SHOW THE REQUIRED VAPOR BARRIER ON THE SLAB REPAIR | | DETAIL & AND PSI OF CONCRETE. COMPLY WITH FBC | | SEC.1816,1907. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|
|