Plan Review Details - Permit 15091199
Plan Review Stops For Permit 15091199
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-23 Cont ID  
Sent By albarran Date 2015-10-23 Time 10:10 Rev Time 0.00
Received By albarran Date 2015-10-22 Time 16:15 Sent To FIRE
Notes
2015-10-23 10:11:47A PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-14 Cont ID  
Sent By albarran Date 2015-10-14 Time 11:00 Rev Time 0.00
Received By albarran Date 2015-10-13 Time 14:29 Sent To I
Notes
2015-10-14 11:07:09PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
 1. NFPA 72, SECTION 17.14.6 REQUIRES THAT THE MANUAL
 PULL STATION DEVICES BE LOCATION NO MORE THAN 5? FROM
 THE EXITS IN THE PATH OF EGRESS.
 2. THE LOWER LOBBY AS INDICATED ON THE DRAWINGS IS
 MISSING MANUAL INITIATION DEVICES, (PULL STATIONS).
 3. IF THE REASON FOR THE PLACEMENT OF THESE DEVICES SO
 DISTANT FROM THE DOOR WAY IS DUE TO GLASS FACADE,
 PLEASE NOTE THAT THE CODE DOES NOT MAKE AN EXCEPTION
 FOR THIS.
 4. THOUGH THE ADDITION OF THE MISSING PULL STATIONS
 WILL NOT ALTER THE CALCS, THEY WILL ALTER RISER
 DIAGRAM.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-27 Cont ID  
Sent By scaldero Date 2015-10-27 Time 13:01 Rev Time 0.00
Received By scaldero Date 2015-10-27 Time 13:01 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-28 Cont ID  
Sent By scaldero Date 2015-09-28 Time 13:27 Rev Time 0.00
Received By scaldero Date 2015-09-28 Time 13:27 Sent To E
Notes
2015-10-27 13:01:19PERMIT # 15091199
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENTS
 PERMIT APPROVED PROVISO:
  
 1) ADDITIONAL DEVICES ARE NEEDED FOR THE DINING
 TERRACE.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
2015-09-28 13:28:50PERMIT # 15091199
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PERMIT APPROVED PROVISO:
  
 1) ADDITIONAL DEVICES ARE NEEDED FOR THE DINING
 TERRACE.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-27 Cont ID  
Sent By scaldero Date 2015-10-27 Time 13:01 Rev Time 0.00
Received By scaldero Date 2015-10-21 Time 10:02 Sent To  
Notes
2015-10-22 10:02:44ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-14 Cont ID  
Sent By albarran Date 2015-10-14 Time 11:08 Rev Time  
Received By albarran Date   Time   Sent To  
Notes
2015-10-14 11:09:5510/14/15 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA