2015-09-23 08:36:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| 1) THE REMOVAL AND CAPPING OF THE FIRE HOSE CABINET IS |
| NOT APPROVED UNDER THIS PERMIT. |
| |
| |
| 2) THE REQUEST FOR REMOVAL OF THE FIRE HOSE MAY BE |
| SUBMITTED SEPARATELY TO THE FIRE MARSHALS OFFICE AND IN |
| COMPLIANCE WITH THE REQUIREMENTS OF NFPA. |
| |
| NFPA 14--, STANDARD FOR THE INSTALLATION OF STANDPIPE |
| AND HOSE SYSTEMS DETAILS THE DESIGN AND INSTALLATION OF |
| STANDPIPE SYSTEMS. |
| 7.3.4 CLASS III SYSTEMS. CLASS III SYSTEMS SHALL BE |
| PROVIDED WITH HOSE CONNECTIONS AS REQUIRED FOR BOTH |
| CLASS I AND CLASS II SYSTEMS. |
| 7.3.4.1 WHERE THE BUILDING IS PROTECTED THROUGHOUT BY |
| AN APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH NFPA 13, STANDARD FOR THE INSTALLATION OF |
| SPRINKLER SYSTEMS, AND NFPA 13R, STANDARD FOR THE |
| INSTALLATION OF SPRINKLER SYSTEMS IN RESIDENTIAL |
| OCCUPANCIES UP TO FOUR STORIES IN HEIGHT, CLASS II HOSE |
| STATIONS FOR USE BY TRAINED PERSONNEL SHALL NOT BE |
| REQUIRED, SUBJECT TO THE APPROVAL OF THE LOCAL FIRE |
| DEPARTMENT, PROVIDED THAT EACH CLASS I HOSE CONNECTION |
| IS 2 1/2 IN. AND IS EQUIPPED WITH A 2 1/2 IN. ? 1 1/2 |
| IN. REDUCER AND A CAP ATTACHED WITH A CHAIN. |
| |