Plan Review Details - Permit 15090766
Plan Review Stops For Permit 15090766
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-11-03 Cont ID  
Sent By shill Date 2015-11-03 Time 09:24 Rev Time 0.00
Received By shill Date 2015-11-03 Time 09:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-22 Cont ID  
Sent By shill Date 2015-09-22 Time 08:04 Rev Time 0.00
Received By shill Date 2015-09-22 Time 08:04 Sent To FIRE
Notes
2015-09-22 08:25:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS PREPARED BY A DESIGN PROFESSIONAL REQUIRED,
 FS471 DUE TO THE MODIFICATION (ELIMINATION OF A DOOR)
 TO A PUBLIC BUILDING.
  
 2. THE DETAIL PROVIDED DOES NOT SHOW HOW THE BLOCK
 INFILL WILL RESIST LOADS, FBC 1601. NO STEEL EMBEDMENT
 INTO EXISTING SUBSTRATE IS PROPOSED.
  
 3. PLAN PROPOSES TO CLOSE IN A ROOM, CREATING A SPACE
 WHICH HAS NO INGRESS AND EGRESS. REVISE PLAN TO INCLUDE
 ROOM DESIGNATION, FBC 107. SCOPE NOT CLEAR; WHY IS IT
 NECESSARY TO CLOSE IN THIS SPACE, CREATING A CONCEALED
 SPACE? REVISE PLAN TO CLARIFY SCOPE.
  
 4. PRODUCT APPROVAL FL 14237 IS EXPIRED; CODE CHANGED
 ON 6/31/15. PROVIDE A CURRENT (FBC 2014) PRODUCT
 APPROVAL, FBC 1609, FAC9N-3.
  
 5. PRODUCT APPROVAL FL 16356 HAS AN APPLICATION STATUS
 OF "VALIDATED"; THIS SHOULD BE "APPROVED." PLEASE PRINT
 THE FLORIDA STATE PRODUCT APPROVAL COVER SHEET WHICH
 SHOWS AN "APPROVED" STATUS, FBC 1609, FAC9N-3.
  
 PLEASE NOTE THAT IT APPEARS THAT THE PRODUCT APPROVAL
 WAS PRINTED ON 7/8/2015, BUT THE APPLICATION WAS
 SUBMITTED ON 9/17/15. AS MANUFACTURERS OFTEN UPDATE
 THEIR PRODUCTS, PRIOR TO SUBMITTING PERMIT APPLICATION,
 CONFIRM THAT THE VERSION PROVIDED IS THE MOST CURRENT
 VERSION.
  
 6. WHEN RESUBMITTING, PROVIDE TWO COMPLETE IDENTICAL
 COLLATED SETS OF PLANS FOR PERMIT ISSUANCE. THE OLD
 SHEETS SHOULD BE REMOVED AND MARKED "VOID" AND RETAINED
 IN THE PERMIT PACKAGE.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-10-22 Cont ID  
Sent By shill Date 2015-11-03 Time 09:24 Rev Time 0.00
Received By fstal Date   Time   Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-09-25 Cont ID  
Sent By fstal Date 2015-09-25 Time 16:45 Rev Time 0.00
Received By fstal Date   Time   Sent To B
Notes
2015-09-25 16:48:30SEE NOTES FROM BUILDING DEPARTMENT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-03 Cont ID  
Sent By shill Date 2015-11-03 Time 09:24 Rev Time 0.00
Received By shill Date 2015-10-20 Time 12:50 Sent To FIRE
Notes
2015-11-02 18:16:07TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-02 Cont ID  
Sent By shill Date 2015-10-02 Time 07:21 Rev Time 0.00
Received By shill Date 2015-09-17 Time 08:57 Sent To  
Notes
2015-09-22 08:25:369/22 TO FIRE
  
2015-09-18 08:57:37BLDG <5K