Plan Review Details - Permit 15090715
Plan Review Stops For Permit 15090715
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-09-25 Cont ID  
Sent By jwitmer Date 2015-09-25 Time 09:14 Rev Time 0.00
Received By jwitmer Date 2015-09-25 Time 08:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-11-03 Cont ID  
Sent By dharvey Date 2015-11-03 Time 14:49 Rev Time 0.00
Received By dharvey Date 2015-11-03 Time 14:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-09-22 Cont ID  
Sent By pleduc Date 2015-09-22 Time   Rev Time 0.00
Received By pleduc Date 2015-09-21 Time 15:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-11-13 Cont ID  
Sent By ccole Date 2015-11-13 Time 09:25 Rev Time 0.00
Received By ccole Date 2015-11-10 Time 09:25 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-11-04 Cont ID  
Sent By lmarchan Date 2015-11-04 Time 12:49 Rev Time 0.00
Received By lmarchan Date 2015-09-16 Time 10:16 Sent To  
Notes
2015-09-17 10:16:16B26

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-11-13 Cont ID  
Sent By ccole Date 2015-11-13 Time 09:25 Rev Time 0.00
Received By ccole Date 2015-11-13 Time 09:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-10-06 Cont ID  
Sent By ccole Date 2015-10-06 Time 11:31 Rev Time 0.00
Received By ccole Date 2015-10-06 Time 11:31 Sent To  
Notes
2015-10-06 11:41:491ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15090715
 10/6/15
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES OF THE NEW TENANT OCCUPANCY- REFER TO
 TABLE 403.3 FBC-14 MECHANICAL AND SHOW THE REQUIRED AND
 PROVIDED CFM'S OF OUTSIDE AIR. INDICATE HOW THE O/A
 WILL BE CONTROLLED PER SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
 2) THE SUBMITTED AC CALCULATIONS ARE FOR COOLING ONLY.
 PLEASE PROVIDE DESIGN HEATING LOADS- REFER TO SECTION
 309.1 FBC-14 MECHANICAL.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-11-12 Cont ID  
Sent By ccole Date 2015-11-13 Time 09:25 Rev Time 0.00
Received By tklarge Date 2015-11-12 Time 14:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By tklarge Date 2015-10-02 Time 11:31 Rev Time 0.00
Received By tklarge Date 2015-10-02 Time 11:20 Sent To  
Notes
2015-10-02 11:30:261) HOT WATER OR TEMPERED WATER SSHALL BE SUPPLIED TO
 THE LAVATORY AND BREAKROOM SINK PER 2014 FBC-PLUMBING
 SEC.607.1
 2) SUBMIT A WATER RISER DIAGRAM THAT SHOWS THE HOT
 WATER AND ALSO THE SOURCE OF HOT WATER. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  