Plan Review Details - Permit 15090696
Plan Review Stops For Permit 15090696
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-11-03 Cont ID  
Sent By jwitmer Date 2015-11-03 Time 14:31 Rev Time 0.00
Received By jwitmer Date 2015-11-03 Time 14:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-30 Cont ID  
Sent By jwitmer Date 2015-10-30 Time 06:27 Rev Time 0.00
Received By jwitmer Date 2015-10-30 Time 06:13 Sent To  
Notes
2015-10-30 06:27:05BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090696
 ADD: 5200 N. FLAGLER DR. SUITE # 2006
 CONT: A & A DEVELPOMENT
 TEL: (561)719-0895
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. OCT.30/ 2015
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION AND PLANS BOTH INDICATE NEW
 24 X 24 INCH TILE FLOORING. PLANS ALSO INDICATE THE USE
 OF 1/4 INCH CORK FLOOR UNDERLAYMENT.
 PLEASE SUBMIT TEST REPORTS NOT JUST RESULTS OF THE
 TEST. NOTE EACH OF THE SOUND TEST HAVE 8 TO 10 PAGES
 AND THE FLAME SPREAD TEST MAY HAVE AS MANY AS 15 PAGES
 WITHIN THE REPORT. THE REASON WE REQUEST THE REPORT IS
 FOR AT WHAT THICKNESS OF THE SLAB WAS THE CONCRETE SLAB
 TESTED, OR WAS IT A WOOD FLOOR/ TRUSS SYSTEM.
 THE OTHER ISSUE IS ALOT OF MANUFACTURERS HAD THEIR
 PRODUCT TESTED WITH DROPPED CEILINGS LOADED WITH
 INSULATION WHICH IS NOT ACCEPTABLE.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
  
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-29 Cont ID  
Sent By jwitmer Date 2015-09-29 Time 13:24 Rev Time 0.00
Received By jwitmer Date 2015-09-29 Time 13:09 Sent To  
Notes
2015-09-29 13:14:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15090696
 ADD: 5200 N. FLAGLER DR. SUITE # 2006
 CONT: A & A DEVELPOMENT
 TEL: (561)719-0895
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 29/ 2015
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION AND PLANS BOTH INDICATE NEW
 24 X 24 INCH TILE FLOORING. PLANS ALSO INDICATE THE USE
 OF 1/4 INCH CORK FLOOR UNDERLAYMENT.
 PLEASE SUBMIT TESTING REPORTS FOR COMPLIANCE WITH THE
 FOLLOWING CODE SECTIONS;
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2014)
  
 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-10-28 Cont ID  
Sent By albarran Date 2015-10-28 Time 09:07 Rev Time 0.00
Received By albarran Date 2015-10-28 Time 08:36 Sent To  
Notes
2015-10-28 09:10:13THE SCOPE OF THIS PERMIT IS LIMITED TO MODERNIZATION OF
 THE EXISTING ELECTRICAL DEVICES. THE REPLACEMENTS WILL
 BE UP TO CURRENT CODE REQUIREMENTS. BEING THAT NO
 ADDITIONAL LOADS WILL BE PLACED ON THE ELECTRICAL
 SERVICE LOAD CALCS AND PANEL SCHEDULE WILL NOT BE
 REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By albarran Date 2015-10-02 Time 09:02 Rev Time 0.00
Received By albarran Date 2015-10-02 Time 08:40 Sent To I
Notes
2015-10-02 09:03:01PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE SECOND ELECTRICAL REVIEW OF
 THE ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
  
 1. PER THE CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED IN
 ACCORDANCE WITH SECTIONS 107.2.1 THROUGH 107.2.5. IN A
 NUT SHELL, THE PLANS HAVE TO DEFINE THE SCOPE OF WORK
 AS YOU HAVE BUT THE MINIMUM ALLOWABLE SCALE IS 1/8?.
 THE PERSON RESPONSIBLE FOR THE DESIGN SHALL INCLUDE
 THEIR NAME AND SIGNATURE.
 2. YOU SHALL INDICATE ON THE PLANS WHERE THE WORK IS TO
 BE DONE. THE ELECTRICAL PERMIT APPLICATION INDICATES
 NEW LIGHTING IN THE KITCHEN AND BATH YET THE SCOPE AS
 DEFINED ON THE PLAN ONLY ADDRESSES REPLACEMENT
 RECEPTACLES.
 3. NEC 406.4(D) HAS SPECIFIC REQUIREMENTS FOR
 REPLACEMENT RECEPTACLES WHICH SHALL BE ADHERED TO.
 ARTICLE 410 HAS THE SAME FOR THE NEW LUMINARIES.
 4. ALL NEW LIGHTING SHALL COMPLY WITH THE REQUIREMENTS
 OF THE 5TH EDITION OF THE FBC-ENERGY CONSERVATION 2014.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-30 Cont ID  
Sent By jwitmer Date 2015-10-30 Time 06:27 Rev Time 0.00
Received By jwitmer Date 2015-10-15 Time 16:04 Sent To  
Notes
2015-10-15 16:04:32B05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-10-02 Cont ID  
Sent By albarran Date 2015-10-02 Time 09:04 Rev Time 0.00
Received By albarran Date 2015-09-16 Time 09:51 Sent To  
Notes
2015-10-02 09:05:5310/2/15 FAILED EVERY TRADE REVIEW. CONTRACTOR NOTIFIED
 VIA EMAIL. SENT TO SMALL DENIED BIN "A". MA
2015-09-17 09:51:48B24

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-10-19 Cont ID  
Sent By gjohnson Date 2015-10-19 Time 13:18 Rev Time 0.00
Received By gjohnson Date 2015-10-19 Time 13:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-10-02 Cont ID  
Sent By tklarge Date 2015-10-02 Time 06:35 Rev Time 0.00
Received By tklarge Date 2015-10-02 Time 06:35 Sent To E
Notes
2015-10-02 06:33:461) THE PLUMBING APPLICATION NOTES NEW SHOWER PANS IN
 BOTH BATHROOMS BUT THE SUBMITTED FLOOR PLAN SHOWS A
 BATHTUB IN ONE OF THE BATHROOMS.INDICATE ON THE PLAN IF
 THE TUB IN THE MASTER BATH IS BEING REMOVED AND
 REPLACED WITH A SHOWER. IF SO, SHOW THE LENGTH & WIDTH
 OF THE NEW SHOWER. COMPLY WITH SEC. 417.4. OF
 FBC-PLUMBING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  