Plan Review Details - Permit 15090693
Plan Review Stops For Permit 15090693
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-10-15 Cont ID  
Sent By rmcdouga Date 2015-10-15 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2015-10-15 Time 09:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-10-15 Cont ID  
Sent By rmcdouga Date 2015-10-13 Time 09:38 Rev Time 0.00
Received By rmcdouga Date 2015-10-13 Time 09:13 Sent To  
Notes
2015-10-15 09:39:48SUBMIT A COPY OF THE SIGNED CONTRACT THAT SHOWS THE
 VALUE OF THE WORK IS LESS THAN $25,000.00.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-10-03 Cont ID  
Sent By rmcdouga Date 2015-10-03 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2015-10-03 Time 07:48 Sent To  
Notes
2015-10-03 08:13:01PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SOUND TRANSMISSION TESTS THAT WERE SUBMITTED ARE
 FOR A CEILING ASSEMBLY CONSISTING OF AN 8 INCH CONCRETE
 SLAB WITH A SUSPENDED 5/8" TYPE X GYPSUM BOARD CEILING
 WITH 3-1/2" LAY-IN FIBERGLASS INSULATION. THE CEILING
 ASSEMBLY FOR THIS PROJECT IS DIFFERENT FROM THE ONE
 TESTED, THEREFORE THIS UNDERLAYMENT IS NOT ACCEPTABLE.
  
 2) THE VALUE OF THE WORK IS MORE THAN $25,000,
 THEREFORE A FLORIDA LICENSED DESIGN PROFESSIONAL IS
 REQUIRED TO PREPARE THE PLANS. (A COPY OF THE SIGNED
 CONTRACT WILL BE REQUIRED TO VERIFY THE VALUE OF THE
 WORK.)
 FS 481.229 -EXCEPTIONS; EXEMPTIONS FROM LICENSURE.
 (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN
 ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS
 FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR
 ALTERATION OF:
 (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY
 FARMER, REGARDLESS OF THE COST OF THE BUILDING;
 (B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING,
 TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY
 ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST;
 OR
 (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING
 INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF
 A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR
 SCHOOL PROJECTS PURSUANT TO S. 1013.45.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-24 Cont ID  
Sent By rmcdouga Date 2015-09-24 Time 19:04 Rev Time 0.00
Received By rmcdouga Date 2015-09-24 Time 18:49 Sent To  
Notes
2015-09-24 19:04:37PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) A FLORIDA LICENSED DESIGN PROFESSIONAL IS REQURED TO
 PREPARE THE PLANS.
 FS 481.229 -EXCEPTIONS; EXEMPTIONS FROM LICENSURE.
 (1) NO PERSON SHALL BE REQUIRED TO QUALIFY AS AN
 ARCHITECT IN ORDER TO MAKE PLANS AND SPECIFICATIONS
 FOR, OR SUPERVISE THE ERECTION, ENLARGEMENT, OR
 ALTERATION OF:
 (A) ANY BUILDING UPON ANY FARM FOR THE USE OF ANY
 FARMER, REGARDLESS OF THE COST OF THE BUILDING;
 (B) ANY ONE-FAMILY OR TWO-FAMILY RESIDENCE BUILDING,
 TOWNHOUSE, OR DOMESTIC OUTBUILDING APPURTENANT TO ANY
 ONE-FAMILY OR TWO-FAMILY RESIDENCE, REGARDLESS OF COST;
 OR
 (C) ANY OTHER TYPE OF BUILDING COSTING LESS THAN
 $25,000, EXCEPT A SCHOOL, AUDITORIUM, OR OTHER BUILDING
 INTENDED FOR PUBLIC USE, PROVIDED THAT THE SERVICES OF
 A REGISTERED ARCHITECT SHALL NOT BE REQUIRED FOR MINOR
 SCHOOL PROJECTS PURSUANT TO S. 1013.45.
  
 3) SPECIFY THE LEVEL OF ALTERATION ON THE PLANS PER
 EXISTING BUILDING CODE CHAPTER 5.
  
 4) SUBMIT TEST REPORTS (AIR BORNE SOUND, STRUCTURE
 BORNE SOUND, FLAME SPRED AND SMOKE DEVELOPED) FOR THE
 REQUIRED FLOOR SOUND INSULATING UNDERLAYMENT.
 FBC 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
 FBC 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
 FBC 2603 FOAM PLASTIC INSULATION
 2603.3 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM
 PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE
 TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  
 5) SPECIFY THE FRAMING MATERIAL THAT WILL BE USED TO
 SHOW THAT IT WILL COMPLY WITH FBC 602.2.
 TYPES I AND II CONSTRUCTION ARE THOSE TYPES OF
 CONSTRUCTION IN WHICH THE BUILDING ELEMENTS LISTED IN
 TABLE 601 ARE OF NONCOMBUSTIBLE MATERIALS, EXCEPT AS
 PERMITTED IN SECTION 603 AND ELSEWHERE IN THIS CODE.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-09-24 Cont ID  
Sent By albarran Date 2015-09-24 Time 13:58 Rev Time 0.00
Received By albarran Date 2015-09-24 Time 13:51 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lmarchan Date 2015-10-08 Time 16:09 Sent To  
Notes
2015-10-08 16:10:06RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-03 Cont ID  
Sent By rmcdouga Date 2015-10-03 Time 08:26 Rev Time 0.00
Received By rmcdouga Date 2015-10-01 Time 13:17 Sent To  
Notes
2015-10-01 13:17:27RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-09-25 Time   Rev Time 0.00
Received By lmarchan Date 2015-09-16 Time 09:50 Sent To  
Notes
2015-09-17 09:50:40ROUTED TO ELECTRICAL


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved