Plan Review Details - Permit 15090565
Plan Review Stops For Permit 15090565
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-10-21 Cont ID  
Sent By albarran Date 2015-10-21 Time 10:36 Rev Time 0.00
Received By aclange Date 2015-10-21 Time 09:44 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-09-23 Cont ID  
Sent By aclange Date 2015-09-23 Time 17:07 Rev Time 0.00
Received By aclange Date 2015-09-23 Time 17:07 Sent To  
Notes
2015-09-23 17:34:38****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. INSUFFICIENT INFORMATION SUBMITTED FOR PLAN REVIEW.
 SUBMIT PLANS SHOWING THE LOCATIONS AND TYPE OF WORK TO
 BE COMPLETED. FOR EXAMPLE, FRAMING DETAILS NOT SHOWN.
 WILL IT BE WOOD OR METAL STUDS AND WHAT GAUGE STUDS.
 STUD SPACING. NOTE: MANY CEMENT BOARD PRODUCT REQUIRE
 16" MAXIMUM STUD SPACING.
  
 2. R-307.2 TILE USED SHALL BE NO LESS THAN 6FT. ABOVE
 THE FLOOR. SHOW ON PLANS.
  
 3. R-307.1 MINIMUM SHOWER MEASUREMENTS ARE 30" IN EACH
 DIRECTION WITH A 24" CLEARANCE IN FRONT OF OPENING.
  
 4. NO ELECTRICAL SHOWN ON PLANS.
  
 5. FBC 1203.4.2.1 VENTILATION REQUIRED.
  
 6. FBC 1207 FLOOR SOUND TRANSMITTION SHALL COMPLY WITH
 THIS SECTION.
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-11-12 Cont ID  
Sent By dharvey Date 2015-11-12 Time 13:14 Rev Time 0.00
Received By dharvey Date 2015-11-12 Time 13:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-10-21 Cont ID  
Sent By albarran Date 2015-10-21 Time 10:16 Rev Time 0.00
Received By albarran Date 2015-10-21 Time 10:09 Sent To I
Notes
2015-10-21 10:28:52YOU SHALL SUBMIT AT A MINIMUM AN ELECTRICAL FLOOR PLAN
 SHOWING THE LOCATION OF THE PROPOSED WASHER & DRYER.
 HAVING DONE WORK INSIDE THE BATHROOM WILL REQUIRE THAT
 IT BE TO CODE AS WELL, MEANING THAT THERE HAS TO BE A
 GFCI PROTECTED OUTLET WITHIN 3' OF THE SINK AND THERE
 HAS TO BE A LIGHT WITH A WALL SWITCH FOR THE BATHROOM.
 THE CODE REQUIRES THAT WHEN YOU PLACE ADDITIONAL LOADS
 TO AN EXISTING PANEL THAT YOU PROVIDE LOAD CALCS AND A
 PANEL SCHEDULE. IN ADDITION TO THAT, THE HOME WILL HAVE
 TO BE MADE COMPLIANT TO SMOKE DETECTOR REQUIREMENTS IF
 IT ALREADY IS NOT IN COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-11-12 Cont ID  
Sent By dharvey Date 2015-11-12 Time 13:14 Rev Time 0.00
Received By dharvey Date 2015-09-18 Time 08:42 Sent To  
Notes
2015-09-18 09:01:36NO ELECTRICAL PLAN SUBMITTED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-10-21 Cont ID  
Sent By albarran Date 2015-10-21 Time 10:29 Rev Time 0.00
Received By albarran Date 2015-10-19 Time 12:55 Sent To B
Notes
2015-10-21 10:36:5010/21/15 FAILED ELECTRICAL REVIEW. SPOKE TO SCOTT OF
 AFFORDABLE BUILDERS TO MAKE HIM AWARE OF STATUS. HE
 WISHES TO COME IN TO THE OFFICE TO DISCUSS THE
 CORRECTIONS REQUIRED. SENT TO SMALL DENIED BIN "A". MA

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-09-23 Cont ID  
Sent By aclange Date 2015-09-23 Time 17:39 Rev Time 0.00
Received By aclange Date 2015-09-14 Time 14:43 Sent To  
Notes
2015-09-14 14:43:10PLUMBING INBOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-09-15 Cont ID  
Sent By tklarge Date 2015-09-15 Time 06:52 Rev Time 0.00
Received By tklarge Date 2015-09-15 Time 06:27 Sent To  
Notes
***NONE***